UNIT OPERATION MODES
Heat recovery
Warm extract air from the room flows into the unit and is cleaned in the extract filter. Then the air is moved through the heat exchanger
and is exhausted outside with the extract fan. Cold fresh air from outside flows into the unit, where it is cleaned in the supply filter.
Then the air flows through the heat exchanger and is directed to the room with the supply fan. Supply air is heated in the heat exchanger
by transferring the heat energy of warm and humid extract air to the cold fresh air. The air flows are fully separated while flowing through
the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
SUPPLY AIR
EXHAUST AIR
INTAKE AIR
EXTRACT AIR
Summer Cooling mode (for the units with bypass only)
The bypass damper is opened, the extract air that is removed from the premises is routed along the bypass duct and does not come in
contact with the heat exchanger. The temperature of the air is not changed after passing through the heat exchanger.
SUPPLY AIR
EXHAUST AIR
INTAKE AIR
EXTRACT AIR
Freeze protection
(danger of freezing appears when the exhaust air temperature downstream of the heat exchanger is lower than
+5 °C and intake air temperature upstream of the heat exchanger is lower than -3 °C for the units with preheating, and when exhaust
temperature downstream of the heat exchanger is lower than +3 °C for the units without preheating): to protect the heat exchanger from
freezing in the cold season, the unit has a Frost Protection mode based on the temperature sensor readings. The temperature sensor is
installed in the exhaust air duct downstream of the heat exchanger. The Frost Protection mode is activated at an exhaust air temperature
of +3 ˚C. After temperature increase the unit returns to the previous operation mode.
In the KOMFORT (EC) D5(B)180-E S11 units the frost protection mode must be activated, see the User’s manual of the control panel.
In case of freezing danger, the supply fan is turned off in the KOMFORT (EC) D5(B)180-E S14 units. After temperature increase the unit
returns to the previous operation mode.
The KOMFORT (EC) D5(B)180-E S21 units have three frost protection modes:
- gradual reduction of the supply fan speed
- with the bypass
- with the electric preheater (if the unit is equipped with a duct preheater).
Mode selection and settings are described in the control system user’s manual.
www.blaubergventilatoren.de
KOMFOrt (EC) d5(B)180(-E)
8