External wiring diagram for units KOMFORT (EC) D5(B)180(-E) S14
2 1
2 1
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SM-N SM-L +U Rx Tx GND C NO GND 0-10V +U PK PK N L
P1
SM1* SM2*
N L1 N L1
+ Rx Tx —
CO2*
PK1*
X1
Power input
230 VAC
Remo
ve
the jumper
— ELECTRIC SHOCK HAZARD!
Designation
Name
Model
Wire**
NO
Remote control panel
4 x 0.75 mm
2
CO2*
CO
2
sensor
NO
2 x 0.25 mm
2
PK1*
Contact from fire alarm panel
NC
2 x 0.75 mm
2
SM1*/SM2*
External damper supply/exhaust
2 x 0.75 mm
2
* Not included in the delivery set. Available upon a separate order.
**Wire cross-section with a cable length of no more than 100 m.
Maximum cable length from the controller to the control panel
Cable type
Distance to power source
Shielded cable AWG24
up to 20 m
www.blaubergventilatoren.de