Unit mounting sequence:

1. Fix the master plate from the delivery set on the wall with a sealing tape on 

required level, fig. 5.

2. Use the master plate to mark two Ø 140 mm holes for the air ducts and two 

Ø 8 mm holes for the dowels.

3. Remove the master plate and drill through holes sloped down by 2-3% 

for the air ducts and the holes for the dowels, 60 mm deep. Then insert the 

dowels from the delivery set. Fig. 6

4. Remove the perforated holes for the air ducts from the master plate. Re-

install it with a sealing tape. If you use either MS1 FRESHBOX 60 or MS2 

FRESHBOX 60 set, fix the master plate from the mounting set on outer wall 

side to align the air ducts with respect to each other. Fix this master plate 

somewhat lower to ensure the minimum required slope by 3% to outside. 

5. Inset the air ducts into the master plate holes and seal those with a mounting 

foam through the provided openings in the master plate, fig. 7.  Install the air 

ducts sloped down by 2-3% outside to ensure the condensate drainage.

6. After the mounting foam hardening (see the solidification time in the 

product specification) remove the master plates. At the inner wall cut the 

protruding parts of the air ducts to be flush with the  wall. On outer wall side, 

the air ducts must protrude by 10 mm to prevent condensate dropping on 

the wall.

7. Mounting sequence of the unit: 

a) take off the front cover and remove the heat exchanger, fig. 8;

b) connect the unit spigots to the air ducts, fig. 9;  

c) fix the unit to the wall with 5.0x50 screws (screws and matching  dowels are 

included into the delivery set);

d) Install the heat exchanger and the front panel. 

e) Mount the sensor speed switch, refer Connection to power mains and 

control, page 8.

 

I

nstall the ventilation hood AH FRESHBOX 60 on the outer side of the building 

to prevent ingress of foreign objects into the air ducts, fig. 10. The hood is not 

included into the delivery set of FRESHBOX 60 unit and is available on separate 

order (with the mounting kit MS2 FRESHBOX 60 or as AH FRESHBOX 60). The 

ventilation hood AH FRESHBOX 60 may be replaced with any ventilation grille 

or a ventilation hood of respective size. 

Fig. 5. 

Fig. 7. 

Fig. 8. 

Fig. 9. 

Fig. 10. 

Fig. 6. 

10 mm

slope 3%

slope 3%

60 mm

Ø 8 mm

2 holes 

Ø 140 mm 

2 holes 

Wall 

Fasteners 

FRESHBOX

unit 

Air duct 

Outer ventilation 

box 

Round air duct 

sloped down 

by 2-3%

Содержание FRESHBOX 60

Страница 1: ...OPERATION MANUAL FRESHBOX 60 SINGLE ROOM AIR HANDLING UNIT WITH HEAT RECOVERY ...

Страница 2: ...ansportation rules 3 Manufacturer s warranty 3 Unit design and operating logic 4 Delivery set 4 Technical data 5 Mounting and operation guidelines 5 Connection to power mains and control 8 Maintenance 9 Troubleshooting 9 Acceptance certificate 10 Connection certificate 10 Warranty card 10 CONTENTS ...

Страница 3: ...ection Technical data Do not close or block the unit intake or exhaust vent not to disturb the normal air passage Do not sit on the unit and do not put objects on the unit Follow the manual guidelines to ensure trouble free operation and long service life of the product Hazardous parts access and water ingress protection standard IP22 STORAGE AND TRANSPORTATION RULES Transportation of the unit is ...

Страница 4: ...g efficiency reaches 79 The air flows are fully separated within the heat exchanger Odours and con taminants contained in the extract air are not transferred to the supply air flow Heat recovery is based on the utilization of the thermal energy of the ex tract air for heating up the supply air The extract air transfers most of its heat to the intake air flow This reduces thermal energy losses in c...

Страница 5: ... construction stage It includes two plastic air ducts each 500 mm long and two master plates for marking the holes on inner and outer wall sides The mounting set MS2 FRESHBOX 60 is specially designed for mounting of the unit in a ready built premise It includes two plastic air ducts 500 mm long a master plate for matching holes and an outer ventilation hood AH FRESHBOX 60 that prevents ingress of ...

Страница 6: ... the solidification time in the product specification remove the master plates At the inner wall cut the protruding parts of the air ducts to be flush with the wall On outer wall side the air ducts must protrude by 10 mm to prevent condensate dropping on the wall 7 Mounting sequence of the unit a take off the front cover and remove the heat exchanger fig 8 b connect the unit spigots to the air duc...

Страница 7: ... mounting set includes plastic air duct Ø 125 mm 500 mm long 2 items paper master plate 1 item outer ventilation box AH FRESHBOX 60 1 item screw and dowel 8x40 4 items Mounting sequence of MS2 FRESHBOX 60 set 1 Fix the master plate from the delivery set on inner wall side with a sealing tape on required level fig 5 2 Use the master plate to mark two Ø 140 mm holes for the air ducts and two Ø 8 mm ...

Страница 8: ...uch a respective speed button to change the selected speed The respective speed button has blue highlighting Touch a current fan speed button once again to turn the air handling unit off The sensor panel has no light indication when the unit is off Every time the sensor panel is touched a sound signal is generated The control unit is installed under the protecting panel of the air handling unit fi...

Страница 9: ...peed switch mounting Mounting sequence of the sensor speed switch fig 13 1 Carefully undo the latches of the switch front panel with a screwdriver 2 Remove the front panel 3 Route the cable to the installation place of the speed switch 4 Fix the back panel to the wall through the fixing holes 5 Connect the control cable to the speed switch following the wiring diagram fig 12 6 Install the speed sw...

Страница 10: ...rective 2006 95 EC 73 23 EEC and CE marking Directive 93 68 EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date____________________ The single room air handling unit with heat recovery FRESHBOX 60 is connected to power ma...

Страница 11: ..._______________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ________________...

Страница 12: ...www blaubergventilatoren de FRESHBOX 60 v 5 3 EN ...

Отзывы: