Table 1. Technical data of the unit

TECHNICAL DATA

MOUNTING AND OPERATION GUIDELINES

Parameters

FRESHBOX 60

Unit voltage / 50-60 Hz [V]

100-240

Speed

min

med

max

Power [W]

4.2

9.6

15.4

Current [А]

0.02

0.04

0.07

Max. air flow [m

3

/h]

30

45

60

RPM

1165

1720

2685

Sound pressure level at 3 m distance [dBA] 

22

25

29

Max. transported air temperature [°С]

-20 up to +50

Filter: extract/supply

G2

Heat recovery efficiency [%]

79

74

70

Heat exchanger type

counter-flow

Heat exchanger material

polystyrene

Ingress Protection Rating

IP22

Weight [kg]

10.3

The unit is mounted with the master plate from the delivery set, fig. 4. Please 

prepare also two air ducts of required length or one of the mounting sets 

(MS1 FRESHBOX 60 or MS2 FRESHBOX 60). 

The mounting set MS1 FRESHBOX 60 is specially designed for mounting of 

the unit at general construction stage. It includes two plastic air ducts, each 

500 mm long and two master plates for marking the holes on inner and outer 

wall sides. 

The mounting set MS2 FRESHBOX 60 is specially designed for mounting of the 

unit in a ready-built premise. It includes two plastic air ducts, 500 mm long, a 

master plate for matching holes and an outer ventilation hood AH FRESHBOX 

60 that prevents ingress of foreign objects inside the unit. If the building’s 

wall thickness is above 500 mm, please prepare two  Ø125 mm air ducts of 

required length.

393

526

187

124

159

121

* Allowable deviation of the rated voltage: ±10%.

**Noise level is measured at 3 m distance from the unit connected to the air 

ducts, in free room.

Fig. 3. Overall dimensions

Drill 2 holes, 60 mm deep,  

with Ø 8 mm

Drill 2 holes, 60 mm deep,  

with Ø 8 mm

2 holes with Ø 130 mm for 

Ø125 mm round duct. Fill the gap 

between the air duct and the wall

 with mounting foam.

2 holes with Ø 130 mm for 

Ø125 mm round duct. Fill the gap 
between the air duct and the wall

 with mounting foam.

Fig. 4. Master plate

Содержание FRESHBOX 60

Страница 1: ...OPERATION MANUAL FRESHBOX 60 SINGLE ROOM AIR HANDLING UNIT WITH HEAT RECOVERY ...

Страница 2: ...ansportation rules 3 Manufacturer s warranty 3 Unit design and operating logic 4 Delivery set 4 Technical data 5 Mounting and operation guidelines 5 Connection to power mains and control 8 Maintenance 9 Troubleshooting 9 Acceptance certificate 10 Connection certificate 10 Warranty card 10 CONTENTS ...

Страница 3: ...ection Technical data Do not close or block the unit intake or exhaust vent not to disturb the normal air passage Do not sit on the unit and do not put objects on the unit Follow the manual guidelines to ensure trouble free operation and long service life of the product Hazardous parts access and water ingress protection standard IP22 STORAGE AND TRANSPORTATION RULES Transportation of the unit is ...

Страница 4: ...g efficiency reaches 79 The air flows are fully separated within the heat exchanger Odours and con taminants contained in the extract air are not transferred to the supply air flow Heat recovery is based on the utilization of the thermal energy of the ex tract air for heating up the supply air The extract air transfers most of its heat to the intake air flow This reduces thermal energy losses in c...

Страница 5: ... construction stage It includes two plastic air ducts each 500 mm long and two master plates for marking the holes on inner and outer wall sides The mounting set MS2 FRESHBOX 60 is specially designed for mounting of the unit in a ready built premise It includes two plastic air ducts 500 mm long a master plate for matching holes and an outer ventilation hood AH FRESHBOX 60 that prevents ingress of ...

Страница 6: ... the solidification time in the product specification remove the master plates At the inner wall cut the protruding parts of the air ducts to be flush with the wall On outer wall side the air ducts must protrude by 10 mm to prevent condensate dropping on the wall 7 Mounting sequence of the unit a take off the front cover and remove the heat exchanger fig 8 b connect the unit spigots to the air duc...

Страница 7: ... mounting set includes plastic air duct Ø 125 mm 500 mm long 2 items paper master plate 1 item outer ventilation box AH FRESHBOX 60 1 item screw and dowel 8x40 4 items Mounting sequence of MS2 FRESHBOX 60 set 1 Fix the master plate from the delivery set on inner wall side with a sealing tape on required level fig 5 2 Use the master plate to mark two Ø 140 mm holes for the air ducts and two Ø 8 mm ...

Страница 8: ...uch a respective speed button to change the selected speed The respective speed button has blue highlighting Touch a current fan speed button once again to turn the air handling unit off The sensor panel has no light indication when the unit is off Every time the sensor panel is touched a sound signal is generated The control unit is installed under the protecting panel of the air handling unit fi...

Страница 9: ...peed switch mounting Mounting sequence of the sensor speed switch fig 13 1 Carefully undo the latches of the switch front panel with a screwdriver 2 Remove the front panel 3 Route the cable to the installation place of the speed switch 4 Fix the back panel to the wall through the fixing holes 5 Connect the control cable to the speed switch following the wiring diagram fig 12 6 Install the speed sw...

Страница 10: ...rective 2006 95 EC 73 23 EEC and CE marking Directive 93 68 EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date____________________ The single room air handling unit with heat recovery FRESHBOX 60 is connected to power ma...

Страница 11: ..._______________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ________________...

Страница 12: ...www blaubergventilatoren de FRESHBOX 60 v 5 3 EN ...

Отзывы: