BLAUBERG Ventilatoren S25 Скачать руководство пользователя страница 12

www.blaubergventilatoren.de

S25

12

 

Main page

   

Menu

   

Alarms

   

Current alarms 

Alarms

0

 — number of current alarms. Indicates a serious 

malfunction.  The unit is forced to shut down. The alarms must be reset 
manually. 

Warnings

0

  —  number of current warnings. The unit is not forced 

to shut down. Warnings are reset automatically once the causes have been 
addressed. 

Code

5

 — Code 5 — current alarm/warning code. The 

malfunction codes are detailed below.  

Reset the alarms

  —  this button resets the current alarms.

 

Main page

   

Menu

   

Alarms

   

Alarm history 

Each entry to the Alarms history contains the alarm/warning code and its 
date and time. The warning and alarm codes are detailed below. 

 

Main page

   

Menu

   

Language  

Interface language selection.

 

Main page

   

Menu

   

Display 

Sound

: on-screen button sounds.

Screen brightness

: selectable in the range of 1–64 (1–100 %).

Auto-lock time

: time to automatic screen lock (0–300 s).

Unlock password:

 — Enable/disable the screen unlock password.

 — Password change. The password length is 1 to 4 characters. The 

default password is 1111. The factory password (in case the user password 
is lost) is 2604.  

If the unlock password is enabled, the screen will show the authorisation 
window after unlocking. 

Содержание S25

Страница 1: ...Sensor control panel EN S25 USER S MANUAL ...

Страница 2: ...ion of its products at any time in order to incorporate the latest technological developments No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company Please read the user s manual carefully prior to installing...

Страница 3: ...e Do not put any foreign objects on the power cable Unpack the unit with care Do not use damaged equipment or cables when connecting the unit to power mains When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not touch the unit controls with wet hands Do not carry out the installation and maintenance operations with wet hands Do not...

Страница 4: ...S OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN The wall control panel with a sensor display is designed for controlling industrial and domestic supply and exhaust ventilation units AHU as well as o...

Страница 5: ...us ATTENTION COMBINING 24 V POWER LINES FROM SEVERAL AIR HANDLING UNITS IS STRICTLY PROHIBITED Example 1 A B A B A B A B A B A B A B A B AHU 1 Control panel1 AHU 2 Control panel2 AHU 16 Control panel16 ATTENTION CONNECTINGMORETHAN5CONTROLPANELSTOASINGLEAHUREQUIRESANEXTERNALPOWERSUPPLYUNIT Example 2 A B A B A B A B A B A B A B A B AHU Control panel1 Control panel2 Control panel3 Control panel4 Cont...

Страница 6: ...gramming the control panel Rocker 2 must be set to ON if the control panel is the first or the last device on an RS 485 bus This rocker activates or de activates the terminal resistor ON OFF Temperature sensor optional DIP switch Power cable connector The temperature sensor is an optional device which measures the temperature in the room If physically present in the panel configuration select Sens...

Страница 7: ...l connections diagram K1 XS1 B A 24V A B GND 24V A B GND X1 White Green Brown Yelow White Green Brown Yelow 5 Remove the connector with the cable from the bracket and connect it to the female connector on the circuit board 6 Match the prongs of the lower part of the front panel with the slots in the lower part of the back panel at 45 and join the halves until they lock in place 4 5 www blaubergven...

Страница 8: ...up 1 Use the mobile application to assign a unique address from 1 to 16 for each AHU 2 Go to the Connection window in the control panel and assign a unique address to each control panel and then select the address of the AHU to be controlled Main page Menu Engineering menu Connection Engineering menu password 1111 default Controller address from 1 to 16 a unique address of the AHU to be controlled...

Страница 9: ...ert Main page Menu Basic settings Filter Fireplace mode Main page Menu Engineering menu Temperature Boost Boost mode Main page Menu Engineering menu Temperature Electric preheater or reheater blowing prior to air handling unit shutdown Return water heater prior to AHU activation in winter Sensors current temperature readings from the selected sensor in the supply air duct extract air duct or in th...

Страница 10: ...automatically maintain the user values by smoothly increasing or decreasing the fan speed Main page Menu Basic settings Timers Once the Main timer is enabled via the Main page menu the air handling unit temporarily switches to the following settings Speed off pre set speed selection 0 Standby 1 2 3 Hours 15 Minutes 0 timer set up Temp off C select the desired temperature control level 0 off 15 C 3...

Страница 11: ... always ends at 24 00 23 C control temperature selection 0 off 15 C 30 C If the off is selected temperature control is disabled for the selected time period Main page Menu Basic settings Date and time To enable weekly schedule operation set the current date and time in the respective fields Main page Menu Basic settings Filter Setting the filter maintenance timer upon elapsing of a pre set period ...

Страница 12: ...ain page Menu Alarms Alarm history Each entry to the Alarms history contains the alarm warning code and its date and time The warning and alarm codes are detailed below Main page Menu Language Interface language selection Main page Menu Display Sound on screen button sounds Screen brightness selectable in the range of 1 64 1 100 Auto lock time time to automatic screen lock 0 300 s Unlock password ...

Страница 13: ...ation of all the existing protective functions or heat recovery which remain enabled Main page Menu Engineering menu Temperature Current temperature Intake air temperature Supply air temperature Extract air temperature upstream of the heat exchanger Exhaust air temperature downstream of the heat exchanger Room temperature This remote sensor can be contained inside the control panel or a special de...

Страница 14: ...able if the AHU is configured to heat exchanger freeze protection by the supply fan or by the bypass with the heater disabled 0 10 V control device If this input is enabled the AHU stops responding to pre set speeds 1 2 3 and will respond to an external pot resistor connected to the control circuit board To enable this control option the AHU must be in any mode other than Standby When enabling the...

Страница 15: ...start in winter at outdoor temperature 30 C Min start temp initial value of the return water temperature required for the AHU start in winter at outdoor temperature 10 C Max alarm temp final value of the return water temperature for the AHU shutdown caused by a freeze alarm in winter at outdoor temperature 30 C Min alarm temp initial value of the return water temperature for the AHU shutdown cause...

Страница 16: ... configuration use this window to select the necessary control mode for the bypass rotary heat exchanger with discrete or analogue control Main page Menu Engineering menu Heat recovery Freeze protection Freeze protection type of heat exchanger freeze protection Note disable protection at your own risk the respective warning is also displayed on the screen While selecting protection by preheater ma...

Страница 17: ...lled on the AHU and the control panels Main page Menu Engineering menu Factory settings The reset may cause a temporary loss of connection to the device as it affects the Wi Fi RS 485 and Ethernet settings If necessary repeat the Wi Fi RS 485 and Ethernet parameter setup using the mobile application see the Wireless control system manual ...

Страница 18: ...the exhaust air temperature downstream of the heat exchanger detected Determined if the heat exchanger freeze protection is active 9 Alarm Short circuit of the exhaust air temperature sensor Determined if the heat exchanger freeze protection is active 10 Alarm Preheater protective thermostat activated Determined if the preheater is selected for protecting the heat exchanger from freezing NKP IN 11...

Страница 19: ...ract air filter Determined if the pressure switch is triggered closing the discrete input FILTER IN EXH 30 Alarm No water pressure detected Determined if no water pressure is detected provided that the water heater and the water pressure sensor are enabled 31 Alarm No water flow detected Determined if no water flow is detected provided that the water heater and the water flow sensor are enabled 32...

Страница 20: ...www blaubergventilatoren de B206EN 01 ...

Отзывы: