KoMFort erv d

6

www.blaubergventilatoren.de

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above 
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum 
(20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic 
components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

Parameter

KOMFORT ERV D 

100

KOMFORT ERV D 

200

KOMFORT ERV D 

300

KOMFORT ERV D 

450

Unit supply voltage, 50 Hz [V]

1~ 230

Maximum unit power [W] 

76

141

193

354

Maximum unit current [A]

0.33

0.63

0.84

1.54

Maximum flow rate [m

3

/h] 

160

280

340

500

RPM [min

-1

]

 

 2750

2840 

2720 

 2870

Sound pressure level at 3 m distance [dBA]

47

49

52

57

Transported air temperature [°С]

-15...+40

Casing material

Painted steel

Insulation

Foamed rubber, 5 and 10 mm

Extract filter

G4

Supply filters

G4 + F8 (PM2.5 93 %)

Connected air duct diameter [mm]

100

100

150

150

Heat recovery efficiency [%]

75-7

72-87

66-87

71-87

Humidity recovery efficiency [%]

32-47

27-47

22-47

23-40

Heat exchanger type

Cross-flow enthalpy

Weight [kg]

17

24

27

39

SEC class

D

D

E

E

Содержание KOMFORT ERV D 100

Страница 1: ...Heat and energy recovery air handling unit USER S MANUAL EN KOMFORT ERV D 100 KOMFORT ERV D 200 KOMFORT ERV D 300 KOMFORT ERV D 450...

Страница 2: ...ractical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of th...

Страница 3: ...ospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in a hazardous or explosive environment cont...

Страница 4: ...f the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the unit is switched off from the su...

Страница 5: ...ltered stream of intake air The unit is not intended for organizing ventilation in swimming pools saunas greenhouses summer gardens and other spaces with high humidity Due to the ability to save heati...

Страница 6: ...ample of new buildings The unit is rated as a Class I electrical appliance Hazardous parts access and water ingress protection rating IP22 for the unit connected to the air ducts IP44 for the unit mot...

Страница 7: ...D B L L A B A B Model Dimensions mm D A A1 B B1 H H1 L KOMFORT ERV D 100 100 734 600 481 571 204 223 300 KOMFORT ERV D 200 100 987 854 704 793 222 241 480 KOMFORT ERV D 300 150 987 854 704 793 227 246...

Страница 8: ...hen the air flows through the heat exchanger and is directed to the room with the supply fan Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to...

Страница 9: ...s 3 After temperature increase the unit returns to the previous operation mode In the Defrosting mode the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow To set...

Страница 10: ...alist Before mounting make sure the casing does not contain any foreign objects e g foil paper The minimum distance between the unit and the ceiling should be at least 20 mm To attain the best perform...

Страница 11: ...t label It is recommended to select the nominal current of the circuit breaker from the standard series following the maximum current of the connected unit The circuit breaker is not included in the d...

Страница 12: ...nce a year Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters To maintain high heat exchange efficiency periodical dry cleaning is recommended Use...

Страница 13: ...and mechanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transpor...

Страница 14: ...the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual inc...

Страница 15: ...RTIFICATE The _____________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation...

Страница 16: ...www blaubergventilatoren de B147 1EN 02...

Отзывы: