MOUNTING AND SET-UP

READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.

WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT 

MAINTENANCE AND REPAIR. 

The unit is designed for suspended ceiling mounting with anchor threaded rods, nuts and anti-vibration rubber. 
Fasteners for fan mounting are not included in the delivery set and should be ordered separately.
While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the Technical data 
section. Fasteners for unit mounting should be selected by a qualified specialist! Before mounting make sure the casing does not 
contain any foreign objects (e.g. foil, paper).
The minimum distance between the unit and the ceiling should be at least 20 mm. 
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses, connect the straight air duct section 
to the spigots on both sides of the unit while mounting.
Minimum straight air duct length:
•  equal to 1 air duct diameter on the intake side
•  equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects. 
To prevent uncontrollable access to the fan, the spigots may be covered with a protecting grille or other protecting device with mesh 
width not more than 12.5 mm.

Washer 
Nut

Threaded rod
Vibration absorbing rubber 

min 20 mm

Содержание KOMFORT ERV D 100

Страница 1: ...Heat and energy recovery air handling unit USER S MANUAL EN KOMFORT ERV D 100 KOMFORT ERV D 200 KOMFORT ERV D 300 KOMFORT ERV D 450...

Страница 2: ...ractical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of th...

Страница 3: ...ospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in a hazardous or explosive environment cont...

Страница 4: ...f the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the unit is switched off from the su...

Страница 5: ...ltered stream of intake air The unit is not intended for organizing ventilation in swimming pools saunas greenhouses summer gardens and other spaces with high humidity Due to the ability to save heati...

Страница 6: ...ample of new buildings The unit is rated as a Class I electrical appliance Hazardous parts access and water ingress protection rating IP22 for the unit connected to the air ducts IP44 for the unit mot...

Страница 7: ...D B L L A B A B Model Dimensions mm D A A1 B B1 H H1 L KOMFORT ERV D 100 100 734 600 481 571 204 223 300 KOMFORT ERV D 200 100 987 854 704 793 222 241 480 KOMFORT ERV D 300 150 987 854 704 793 227 246...

Страница 8: ...hen the air flows through the heat exchanger and is directed to the room with the supply fan Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to...

Страница 9: ...s 3 After temperature increase the unit returns to the previous operation mode In the Defrosting mode the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow To set...

Страница 10: ...alist Before mounting make sure the casing does not contain any foreign objects e g foil paper The minimum distance between the unit and the ceiling should be at least 20 mm To attain the best perform...

Страница 11: ...t label It is recommended to select the nominal current of the circuit breaker from the standard series following the maximum current of the connected unit The circuit breaker is not included in the d...

Страница 12: ...nce a year Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters To maintain high heat exchange efficiency periodical dry cleaning is recommended Use...

Страница 13: ...and mechanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transpor...

Страница 14: ...the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual inc...

Страница 15: ...RTIFICATE The _____________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation...

Страница 16: ...www blaubergventilatoren de B147 1EN 02...

Отзывы: