TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a
minimum (20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage
electronic components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP20 for the unit connected to the air ducts.
IP44 for the unit motors.
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Parameter
CIVIC EC DB 300
CIVIC EC D1B 300
CIVIC EC DBE 300
CIVIC EC D1BE 300
CIVIC EC DBE2 300
CIVIC EC D1BE2 300
CIVIC EC DB 500
CIVIC EC D1B 500
CIVIC EC DBE 500
CIVIC EC D1BE 500
CIVIC EC DBE2 500
CIVIC EC D1BE2 500
Power supply voltage, 50(60*) Hz [V]
1~230
1~230
Maximum unit power without electric heater [W]
125
170
Preheater power [W]
-
1050
-
1750
Reheater power [W]
-
-
1400
-
-
1750
Maximum unit current without electric heater [A]
1.3
1.7
Maximum unit current with electric heater [A]
-
7.3
13.6
-
10.4
18.2
Maximum air flow [m3/h]
300
510
RPM [min
-1
]
2150
1700
Sound pressure level at 1 m [dBA]
33
34
Sound pressure level at 3 m [dBA]
23
24
Maximum transported air temperature [˚C]
-25...+40
-25...+40
Casing material
painted steel
painted steel
Insulation
30 mm, polyester
30 mm, polyester
Extract air filter
G4
G4
Supply air filter
G4, F8
(optional: F8 C + H11)
G4, F8
(optional: F8 C + H11)
Connected duct diameter [mm]
200
250
Weight [kg]
78
119
79
121
80
123 126 163 128 165 130 167
Heat recovery efficiency [%]
76...88
74...86
Heat exchanger type
counter-flow
counter-flow
SEC class
A
A
A
A
A
A
Units without a drain pump are designed to operate in an electrical supply network with a frequency of 50(60) Hz, with a
pump — only 50 Hz.