5.6 FIT THE FLUE - Figs. 5.5 and 5.6
The following procedure applies to fitting an Alpha CD Easy-Flue to both rear or side exit flue - horizontally only.
Alpha E-Tec S 20, 30 and 35 - Installation
2. Determine the overall length (L) of flue required, (see Fig. 5.7) as follows:-
Rear flue
L = wall thickness (B) + 60 mm (105 mm if the wall jig is used)
Side flue
L = wall thickness (B) + distance between boiler and wall (C) + 145 mm
Fig. 5.7
Fig. 5.5
Fig. 5.6
CD Easy-Flue
500 mm
1000 mm
B (mm)
Max
530
975
Min
305
765
CD Easy-Flue
500 mm
1000 mm
Max
440
885
Min
215
675
B + C (mm)
Note:
Add 45 mm to
dimension B if the wall jig is
used.
(B)
Rear Flue
(B + C)
Side Flue
Seal Joint with Tape
L
1. The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below.
Note:
Where the length is less than the minimum or more than the maximum, refer to Section 5.7.
3. Adjust the telescopic section of the flue to the distance ‘L’, ensuring that the two labels marked ‘TOP’ are aligned, then
seal and secure the joint between the ducts with the sealing tape supplied.
Note:
Always ensure that there is a minimum overlap of 25 mm when fully extending the telescopic section.
4. Pass the flue assembly through the wall (from inside or outside).
Note: Internal fitting -
If there is no access to make good the outside wall, locate the outside (black) flue sealing collar
onto the outer duct of the flue immediately before the terminal grille onto the location provided. Push the flue assembly
through the 130 mm flue hole, so that the collar completely passes through the wall. Then pull the flue assembly back
into the correct position. Visually check that the collar is sealing the outside wall and that it is not restricting any of the
openings of the flue terminal.
Note: Silicone grease or other lubricants must not be used on the flue joints or seals.
Where a flue terminates less than 150 mm below a gutter, eaves or other obstructions it is possible to extend the flue to
allow the flue termination to clear the obstruction, providing the flue is not extended beyond the first joint. For situations
below balconies or large eaves where extensions may be required, the flue must be supported using the correct
brackets. Alternatively plume management components can be used with supports where necessary.
All joints between flue sections should be connected using the clamps provided. It is not required to add additional
screws through the clamps and into the flue sections.
Содержание BLADE TWIN PLUS TPWH60
Страница 2: ......
Страница 6: ...4 Blade 60 80 Twin Plus Water Heater Manual July 2020 3 0 BLADE WATER HEATER SCHEMATIC LAYOUT ...
Страница 7: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 5 3 1 SCHEMATIC LEGEND ...
Страница 17: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 15 9 0 MAINTENANCE AND SERVICING CLEARANCES ...
Страница 18: ...16 Blade 60 80 Twin Plus Water Heater Manual July 2020 10 0 INSTALLATION SCHEMATIC LAYOUT ...
Страница 21: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 19 13 0 WIRING DIAGRAM ...
Страница 29: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 27 Notes ...
Страница 30: ...APPENDIX A ALPHA BOILER MANUAL ...
Страница 89: ...59 Alpha E Tec S 20 30 and 35 Page intentionally Blank ...
Страница 99: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 29 APPENDIX B DAB PUMP MANUAL ...
Страница 113: ...ENGLISH 41 It is dangerous to touch the circulator DANGER OF SCALDING ...
Страница 123: ...ENGLISH 51 18 PERFORMANCE CURVES EVOSTA2 40 70 XXX ...
Страница 124: ...ENGLISH 52 EVOSTA2 80 XXX ...
Страница 125: ...ENGLISH 53 EVOSTA3 40 XXX ...
Страница 126: ...ENGLISH 54 EVOSTA3 60 XXX ...
Страница 127: ...ENGLISH 55 EVOSTA3 80 XXX ...