After entering into configuration mode, you are able to change all the settings on tool panel, as below detailed
explanations.
3.1.1 Basic Setting
Click the ‘Basic Setting’ label, you are allowed to change the Device ID, SIM Card Number, Work Mode, and
select the Modbus work mode, Modbus device address, update interval. Also RTC Setting.
Figure 18: Basic Setting
Parameter Name
Description
Device ID
Setting the TG501 device ID, it is used for recognizing the
device during register and keep alive with server.
8 digital HEX value only.
SIM card No.
Helpful for distinguishing the device.
Work Mode
TG501 supports DTU and MODEM modes
Modbus Work Mode
‘Modbus Disable’ to disable Modbus feature, while ‘Network
RTU’ is for transparent transmit with serial ports, or read the
device ADC/DI/Relay