Manual Settings

Without specific address:

Parameter

Step 1

   Step 2

   Field size
   Functionality 
   Field geometry

  Press [<] briefly
  Press [>] briefly
  Press [<] and [>] briefly at the same time

  # of flashes of the 

   green LED (1-9 times) indicates 
   the current parameter level

Note:
If no key is touched for 25 seconds, the configuration mode is automatically exit-
ed and the green LED briefly flashes. The settings created up to that point are
saved.

How to find out the value of each parameter.

5.1

Sensor parameters status 

6.2

Mode of operation

Activation:       – After connecting the sensor to the power supply 

or

                       – Briefly disconnect the sensor from the power supply 

or

                       – Press either key [<] or [>] on the sensor

Exiting:            – Press key              combination 

or

                       – Automatically after 30 Minimum.

Note:
If no button is pushed for 30 seconds, the connection is closed. The settings 
made up to that point are saved.

1, 2, 3  small

4, 5, 6* medium

7, 8, 9

large

for Reflex 2 version with direction recognition

Le

ve

l

1*

detects approaching targets, mounting height standard

2

detects approaching targets, mounting height high

3

detects going away targets, mounting height standard

4

detects going away targets, mounting height high

5

direction recognition OFF, mounting height standard

6

direction recognition OFF, mounting height high

7

ap MTO, mounting height standard (MTO, see chap. 8)

8

ap MTO, mounting height high (MTO, see chap. 8)

1

narrow field

2*

wide field

Changing the functionality from level 6 to level 2:
1)   Keep [<] and [>] pressed for 4 seconds, the green LED blinks once after     

     2 seconds, once again after 4 seconds

2)   Green LED flashes 6 times, indicating the current parameter level
3)   Press the key [<] four times in a row to decrease the parameter level 

     (green LED flashes twice and indicates the new parameter level)

4)   Press [<] and [>] at the same time

The data transmission to and from the sensor is ensured by an IR interface. The  
connection between the remote control and the sensor can only be established
when the sensor is in configuration mode.

With specific address:

1. Press the      start key

1. Cover the IR interface of the 

   remote control with your hand

2. Press the     start key >

flashes

3. Release the IR interface 

   (remove hand) 

4. Press the corresponding numerical 

   key (     to     )

–  G and one of the keys 1 through 4 light up:

Connection successfully 

established

 

G flashes:

Connection not established

   > Activate configuration mode (see above)
   > Hold remote control closer to the sensor and point directly at it
   > Check batteries in remote control

–  No keys light up

   > Check/replace batteries in remote control

6.3

Setting / changing parameters

Door open: Keeps the door open manually for 15 Minimum.
Afterwards, the door will close if no object is in the detection area.

Door closed: Door closes if no object is in the detection area,
afterwards standard operation.

After the connection has been successfully established, the parameters of the
sensor can be changed.

General procedure

[>]

[<] 

Changing the field size: 

Press [<] and [>] for 2 seconds

Changing the functionality: 

Press [<] and [>] for 4 seconds

for Reflex 2 version without direction recognition

1*

mounting height standard

2

mounting height high

Changing the field shape: Press [<] and [>] for 6 seconds

Example

Restore factory settings:

Press [<] and [>] for 8 seconds

Configuration mode

   

+     

A

3

Establishing the connection

Each sensor can be assigned an address (1*, 2, 3 or 4). Different addresses are
necessary when several sensors are within the range of a remote control.

Address 1*

Address 2

Address 3

Address 4

6.1

Sensor addressing

G

G

G

1

4

   

+     

A

1

   

+     

A

2

   

+     

A

3

Numerical keys     to

1

9

IR interface (infrared)

Control keys     to

A

F

Start

G

1)   Keep [<] and [>] pressed for an equal length of time, every 2 seconds the 

     green LED will flash once

2)   # of flashes of the green LED (1–9 times) indicates current parameter level
3)   The parameter level can be decreased or increased with [<] and [>] 

     respectively

4)   Press [<] and [>] briefly to exit the configuration mode (settings are saved)

Le

ve

l

Le

ve

l

Le

ve

l

2

* Factory setting

6

Remote Control Settings

Exit configuration mode: Configuration mode is ended, door closes
when no object is in the detection area, afterwards standard opera-
tion.