5.17

Special settings

Manual industrial door opening

Reset A+9

This function resets all device parameters to the factory settings (see 4.1)
and a new initialisation phase starts as if the device had been switched
on again.

The reset also deletes the access code. There are two possible ways of
resetting the device to its factory settings:

1)  

With the remote control

A + 9 =

Reset

2)  

With the keys:
Press keys X and Y simultaneously and hold for 8 seconds.

Every 2 seconds, both LEDs light up briefly. Both LEDs light up after 8
seconds. The reset is performed when the keys are released.

A + 1 =

Both relays off

A + 2 =

Relay 1 on

A + 3 =

Relay 2 on

A + 4 =

Both relays off, exit configuration mode

Switching off access code function (deleting code) without
remote control

1.

Press start key G

➔ 

G

and one of keys 1...7 light up

2.

Press 

C

then 

9

➔ 

C and 2 light up

➔ 

The access code function is switched off (no code stored)

3. 

Enter the 4-digit code (any number between 

1111 – 9998

)

4. 

Press 

C

➔ 

C + 1

lights up

➔ 

The access code function is switched on (code stored)
Configuration mode is deactivated (device is protected).

Switching off access code:

The code can only be deleted if the detector is already in configuration
mode.

1. 

Press start key 

G

➔ 

G

and one of keys 

1...7

light up

2.

Press

C

then 

9

➔ 

C + 1

light up

➔ 

Access code function is switched on

3. 

Press

9

four times, then press 

C

➔ 

C

and 

2

light up

➔ 

The access code function is switched off (code deleted)

Configuration mode can only be activated with the remote control if a
code has been stored previously (see access code)

1. 

Press start key 

G

➔ 

G

and one of keys 

1...7

light up

2. 

Press

then 

9

➔ 

C

and 

1

light up

➔ 

Access code function is switched on

3. 

Enter four-digit code 1111 – 9998

4. 

Press

C

➔ 

C

and 

1

light up

➔ 

Configuration mode is activated

➔ 

Detector is ready for programming

➔ 

If 

C

and 

2

light up, code was incorrect

➔ 

Start again from step 

1

Press both keys X and Y simultaneously and hold for 8 seconds. Both
LEDs light up briefly every 2 s.

➔ 

Device is reset to factory settings

➔ 

Access code function is switched off

➔ 

(Code deleted)

➔ 

New initialisation and teach-in phase starts (see 4.1)

Digital filter function

In special mounting situations, it might be necessary to activate the
filter function under certain circumstances. Sources of interference
located close to the detector can lead to malfunctions.

F + 6 + 1 =

On

S.7 + 1

F + 6 + 2 =

Off

S.7 + 2

Addressing Herkules 2

Seven  different  addresses  for  communication  with  the  Reglobeam
remote control can be set on the Herkules 2.
Addresses 1 – 4 are set using the built-in DIP switch.

Addresses 5 – 7 are set using the remote control.

F + 8 + 5 =

Adress 5

F + 8 + 6 =

Adress 6

F + 8 + 7 =

Adress 7

F + 8 + 9 =

Read in set address from DIP switch

Different addresses should be set if detectors are mounted next to or
opposite to one another and are within range of the same remote
control.

Remote Control  Function

Keys

F + 3 + 1

Off 

S.5 + 1

F + 3 + 2…5

Decreasing sensitivity 

S.5 + 2… 5

F + 3 + 6…9

Constant sensitivity 

S.5 + 6… 9

Access code

Herkules 2 can be protected against unwanted manipulation by means of
a  four-digit  access  code.  This  code  enables  configuration  mode  to  be
reactivated at any time by remote control in order to perform settings.
This function is inactive by default.

Switching on access code:

The code can only be stored if the detector is already in configuration
mode. The device is protected as soon as the code has been stored.
(Configuration mode is deactivated)

Adress 1*

Adress 2

Adress 3

Adress 4

*

 F

ac

to

ry

 s

et

tin

g

SMD-Field

Detektion area

Additional SMD field

Configuration mode is activated when the detector is switched on. This is
deactivated  automatically  30  minutes  after  the  last  setting  has  been
made.

Configuration mode can be activated by:
– Pressing any key on detector (x or y)
– Interrupting electrical power supply
– Via access code on remote control

Switch adressing

Activating configuration mode

The  connection  between  the  remote  control  and  Herkules  can  only  be
established when the detector is in configuration mode.

Содержание Herkules 2

Страница 1: ...nom r ckvidden f r en fj rrstyrning Givaren m ste monteras p en plan yta Undvik vibrationer F rem l som v xter flaggor fl ktar osv f r inte komma in i detektorf ltet Givaren f r inte t ckas ver med lo...

Страница 2: ...av str mf rs rjningen Med beh righetskod med fj rrstyrningen Idrifttagningsfas SMD Slow Motion Detection Minimala n stan statiska r relser detekteras s snart porten ppnar Den st ngs f rst n r ingen r...

Страница 3: ...arn Alternativ 5 R2 Mot radarn R1 fr n radarn Alternativ 8 R2 Mot radarn R1 fr n radarn Alternativ 5 R2 mot radarn R1 fr n radarn Alternativ 1 R2 fordon R1 person Alternativ 1 R2 fordon R1 person Alte...

Страница 4: ...n p separata utg ngar Standard port Reagerar endast p Fordon Standard port Reagerar endast p personer Standard port Personer och Fordon p samma utg ng Standard port Personer och Fordon En riktning per...

Страница 5: ...av funktion Genom tryckning p knappen X Varje tryckning h jer v rdet med v rdet 1 Funktions nr N r den sista funktionen r n dd hoppar programmet ter till f rsta funktionen Gr n LED anger d numret p d...

Страница 6: ...v rtrafik V rde 9 Porten ppnar vid tv rtrafik eller n rmanden fr n sidan Steg 1 Fj rrstyr ning Funktion Knappar C 1 Standard k nner av alla objekt P 1 1 C 2 Trafik rakt framifr n mot radarn alla objek...

Страница 7: ...var koden fel B rja om vid 1 Tryck samtidigt knapparna X och Y under 8 sekunder Varannan sekund blinkar b da LED kort Apparaten r terst lld till fabriksinst llningarna Funktion Beh ringhetskod r fr n...

Страница 8: ...0 14 mm2 Godk nnande CE 0682 FCC IC L nder EU EFTA US CA F ltm tt vid 30 lutning Fr n 2 5 m x 3 m BxD H jd 2 m Till 5 m x 7 m BxD H jd 7 m EG F rs kran om verenst mmelse Bircher Reglomat AG uppger h...

Страница 9: ...dde af en fjernbetjening F leren skal fastmonteres p en plan flade Undg vibrationer Objekter som fx planter flag ventilatorer osv m ikke komme inden for registreringsfeltet F leren m ikke v re d kket...

Страница 10: ...f leren x eller y at afbryde str mtilf rslen hj lp af adgangskoden og fjernbetjeningen Opstartsfase SMD Slow Motion Detection De mindste n sten um rkelige bev gelser registreres s snart porten bnes Re...

Страница 11: ...af rel er Trin 5 R2 forl ns R1 bagl ns Trin 5 R2 forl ns R1 bagl ns Trin 8 R2 forl ns R1 bagl ns Trin 5 R2 forl ns R1 bagl ns Trin 1 R2 K ret j R1 person Trin 1 R2 K ret j R1 person Trin 6 R2 K ret j...

Страница 12: ...soner k ret jer Standard port undertrykkelse af personer Standard port undertrykkelse af k ret jer Standard port personer k ret jer samme udgang Standard port personer k ret jer udgange retningsadskil...

Страница 13: ...f leren Funktions ndring Ved tryk p knap X Pr tryk p knappen forh jes v rdien med 1 funkti onsnr N r den sidste funktion er n et springer programmet igen til den f rste funktion Den gr nne LED angive...

Страница 14: ...afik Trin 9 Port bner ved krydsende trafik eller sidev rts tiln rmelse trin 1 Fjernbet jening Funktion Knapper C 1 Standard registrerer alle objekter P 1 1 C 2 Frontal trafik alle objekter P 1 2 C 3 H...

Страница 15: ...og Y og hold dem nede i 8 sekunder Hvert 2 sekund lyser begge LED kort Enheden er tilbagestillet til fabriksindstilling Funktionen adgangskode er sl et fra Kode slettet Ny initialiserings og indl ring...

Страница 16: ...lande EU EFTA US CA Feltdimensioner ved 30 h ldning fra 2 5 m x 3 m BxD h jde 2 m til 5 m x 7 m BxD h jde 7 m EU Overensstemmelseserkl ring Hermed erkl rer Bircher Reglomat AG at produktet Herkules op...

Страница 17: ...oles according to values given 2 Route cable through opening provided in mounting bracket and make sure length is sufficient for wiring 3 Screw mounting bracket on tightly 4 Hook detector into mountin...

Страница 18: ...tector x or y Interrupting electrical power supply Via access code on remote control Start up phase SMD Slow Motion Detection The slightest quasi static movements are detected as soon as the industria...

Страница 19: ...backwards Level 5 R2 forwards R1 backwards Level 8 R2 forwards R1 backwards Level 5 R2 forwards R1 backwards Level 1 R2 Vehicle R1 Person Level 1 R2 Vehicle R1 Person Level 6 R2 Vehicle R1 Level 1 R2...

Страница 20: ...hicles Standard industrial door people suppression Standard industrial door vehicle suppression Standard industrial door people and vehicles same output Standard industrial door people and vehicles ou...

Страница 21: ...hanging the function Press key X The value increases by 1 for every key press function no Once the last function has been reached the program jumps back to the first function The green LED then indica...

Страница 22: ...laterally level 1 Remote control Function Keys C 1 Standard detects all objects P 1 1 C 2 Frontal traffic all objects P 1 2 C 3 High speed industrial door all objects P 1 3 C 4 Detects slow movements...

Страница 23: ...imultaneously and hold for 8 seconds Both LEDs light up briefly every 2 s Device is reset to factory settings Access code function is switched off Code deleted New initialisation and teach in phase st...

Страница 24: ...m x 3 m WxD height 2 m to 5 m x 7 m WxD height 7 m EU Declaration of Conformity Bircher Reglomat AG herewith declares the product Herkules 2 to be in conformance with the basic requirements and other...

Отзывы: