7
Loop-Powered Process Meter
DPM-400
www.binmaster.com
▲
Connector Labeling for Fully Loaded DPM-400
CONNECTIONS
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all
connectors available with requested configuration.
Notes:
1. Panel cutout required: 1.772" x 3.622" (45 mm x 92 mm)
2. Panel thickness: 0.040 - 0.250" (1.0 mm - 6.4 mm)
3. Mounting brackets lock in place for easy mounting
MOUNTING DIMENSIONS
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.6"
(91mm)
4.68"
(119mm)
2.45"
(62mm)
DPM-400 LOOP POWERED DIGITAL PANEL METER
▲
Meter Dimensions - Side View
▲
Meter Dimensions - Front View
Units: Inch (mm)
4-20 mA
Transmitter
Power
Supply
DI+ DI- mA- mA+
BL-
X
4-20 mA
Transmitter
Power
Supply
DI+ DI- mA- mA+
BL-
X
Safe Area Input Loop (4-20 mA) Connections
The following figures show a 4-20 mA loop connected to the meter. The
first figure shows the connection without the backlight and the second
shows the connection with the backlight. The meter is powered by the
4-20 mA current loop.
▲
4-20 mA Input Connection without Backlight
▲
4-20 mA Input Connection with Backlight
Power
Supply
Device with
4-20 mA Input
I+
I-
Safe Area 4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the
connector terminals labeled mA OUT. The 4-20 mA output must be
powered from an external power supply.
Safe Area Digital Input Connection
A digital input is standard on the meter. This digital input is connected
with a normally open contact across DI+ and DI-, or with an active low
signal applied to DI+.
DI+ DI- mA- mA+
BL-
X
C
NO C
NO
Internal
Load
Load
Relay connections are made to a four-
terminal connector. Each relay’s C
terminal is common only to the normally
open (NO) contact of the corresponding
relay.
Safe Area Solid State Relay Connections