CNCR-190 • Two-wire 4-20 mA/HART  

7

When mounting the sensor, 

distance it at least 200 mm (7.874 in)

 from the vessel wall. If the sensor 

is installed in the center of a round vessel top, multiple echoes can arise. However, these can be 

suppressed by a false signal suppression (see chapter 

“Setup”

).

If you cannot maintain this distance, you should carry out a false signal suppression during initial 

setup. This applies particularly if buildup on the vessel wall is expected. If this is the case, we 

recommend repeating the false signal suppression later with the additional buildup. 

In vessels with cone bottoms, the sensor can be mounted in the center of the vessel to measure 

material down to the outlet. 

Fig. 6: Mounting of the radar sensor on round vessel tops

Fig. 5: Polarization position

1. Middle of the printed label

Содержание CNCR-190

Страница 1: ...CNCR 190 Two wire 4 20 mA HART 1 Operating Instructions Radar sensor for continuous level measurement of liquids CNCR 190 Two wire 4 20 mA HART Document ID 925 0398 Rev B...

Страница 2: ...ctions 6 4 2 Mounting versions 6 4 3 Mounting instructions 6 5 Connecting to power supply 10 5 1 Preparing the connection 10 5 2 Wiring plan 10 6 Setup with smartphone tablet Bluetooth 11 6 1 Preparat...

Страница 3: ...ure Battery disposal This symbol indicates special information about the disposal of batteries and accumulators 1 About this document 2 For your safety 2 1 Authorized personnel All operations describe...

Страница 4: ...inciple of operation CNCR 190 is a radar sensor for continuous level measurement It is suitable for liquids and solids in practically all industries The instrument emits a continuous frequency modulat...

Страница 5: ...tebook Devices with signal output 4 20 mA HART can also be operated via a signal cable This is done via an interface adapter and a PC notebook using DTM PACTware Fig 3 Connecting the PC to the signal...

Страница 6: ...ed G1 plastic nut Take note of Figure 4 for the recommended distance to the wall Fig 4 Mounting via a mounting bracket 4 3 Mounting instructions The radar emits pulses of electromatic waves which are...

Страница 7: ...aintain this distance you should carry out a false signal suppression during initial setup This applies particularly if buildup on the vessel wall is expected If this is the case we recommend repeatin...

Страница 8: ...am The antenna edge of the device is the beginning of the measuring range and at the same time the reference plane for the min max adjustment see following diagram Do not mount the instruments in or a...

Страница 9: ...ecommended values for socket or stand pipe lengths and heights are in the following table The values come from typical applications For socket or stand pipe mount the pipe should be as short as possib...

Страница 10: ...arresters should be installed Warning Only connect or disconnect in de energized state Note Power the instrument via an energy limited circuit power max 100 W according to IEC 61010 1 e g Class 2 powe...

Страница 11: ...searches automatically for Bluetooth capable instruments in the area The message Connecting is displayed The devices found are listed and the search is automatically continued Select the requested in...

Страница 12: ...is deactivated which is default Parameter protection can be activated later if desired 6 3 Parameter adjustment The sensor adjustment menu is divided into two areas which are arranged next to each ot...

Страница 13: ...sensor Max adjustment 0 0 m Min adjustment 8 0 m Menu item Selection Basic settings Damping Integration time 0 s Current output Output characteristics 4 to 20 mA 0 to 100 Current range Min current 3 8...

Страница 14: ...5 F017 Adjustment span too small Adjustment not within specification Change adjustment according to the limit values difference between min and max 10 mm Byte 5 Bit 1 of Byte 0 to 5 F025 Error in the...

Страница 15: ...inish simulation Wait for the automatic end after 60 min Simulation Active in Standardized Status 0 Code Text message Cause Rectification F105 Determine measured value The instrument is still in the b...

Страница 16: ...Error when carrying out a reset False signal suppression faulty Carry out reset and repeat setup Bit 7 of Byte 14 to 24 M508 Data error in program memory Bluetooth controller Bit 8 of Byte 14 to 24 M5...

Страница 17: ...ted parts Antenna PVDF Counter nut depending on device version PP Materials non wetted parts Housing PVDF Cable entry seal NBR Connection cable PUR Weight Instrument 0 7 kg 1 543 lbs Connection cable...

Страница 18: ...76 F Storage and transport temperature 40 to 80 C 40 to 176 F Process conditions For the process conditions please also note the specifications on the type label The lowest value amount always applies...

Страница 19: ...CNCR 190 Two wire 4 20 mA HART 19 11 2 Dimensions CNCR 190 Fig 16 Dimensions CNCR 190...

Страница 20: ...l use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior notice BinMaster Phone 402 434 9102...

Отзывы: