CNCR-190 • Two-wire 4-20 mA/HART
14
8 Diagnostics and servicing
8.1 Maintenance
If the device is used properly, no special maintenance is required in normal operation.
In some applications, buildup on the antenna system can influence the measurement. Depending
on the sensor and application, be careful to avoid heavy soiling of the antenna system. If
necessary, clean the antenna system periodically.
8.2 Status messages
The status messages are divided into the following categories:
• Failure
• Function check
• Out of specification
• Maintenance required
Failure
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
F013
No measured value
available
No measured value in the
boot up phase or during
operation
Check or correct installation and/or
parameter settings
Clean the antenna system
Byte 5, Bit 0 of
Byte 0 to 5
F017
Adjustment span too
small
Adjustment not
within specification
Change adjustment according to the
limit values
(difference between min.
and max. ≥ 10 mm)
Byte 5, Bit 1 of
Byte 0 to 5
F025
Error in the
Linearization table
Linearization values are not
continuously rising, for
example illogical value pairs
Check Linearization table
Delete table/Create new
Byte 5, Bit 2 of
Byte 0 to 5
F036
No operable software
Checksum error if software
update failed or aborted
Repeat software update
Send instrument in for repair
Byte 5, Bit 3 of
Byte 0 to 5
F040
Error in the electronics
Limit value exceeded
in signal processing
Hardware error
Restart instrument
Send instrument in for repair
Byte 5, Byte 5,
Bit 4 of Byte 0
to 5
F080
General software error
General software error
Restart instrument
Byte 5, Byte 5,
Bit 5 of Byte 0 to 5
Menu item
Selection
Basic settings
Status
Sensor status
Measured value status
Status output
HART Device Status
Status additional measured value
-
Echo curve
Indication of echo curve
-
Diagnostics