OPERATORS MANUAL
CLP
36917 r#1
Controller Programming
Operation Mode Cont.
Advanced Setup Mode
There are 2 additional features which may be accessed through the controller.
1.
Memory
2.
Fault Contact Configuration
The memory feature allows the user to decide if the controller resumes at the point where it left off (LP 0), after a power reset.
The fault contact feature allows the user to decide if the fault contact signal (Pin 3 on the DIN connector for options Y and Z) normally sits
at +vdc, and opens in the event of a fault (F nC) or is normally open and switches to +VDC in the event of a fault (FnO).
To enter Advance Setup Mode:
Fault Conditions:
• ”
EELL
”-Low Level Switch activated
(All Modes) Check and replace cartridge. Hit “R” to resume lubrication once more (see page 8).
• “
EEcY
”-Monitor time-out
(Mode d3 - Progressive) Cycle switch did not activate within monitor time.
• ”
EE
”-Internal memory failure
(Checked at power up) No recovery. Turn off power and try again. If problem persists, replace control.
• ”
LLPP
”-”Green LED” -Low Voltage
Check and apply correct voltage
PRESS AND HOLD KEYS.
S
WHILE HOLDING , PRESS THE KEY.
ADVANCED SETUP MODE
PRE-LUBE AT
POWER ON
FAULT RELAY
STATE
Upon power on, lubrication resumes
at last know position. (default)
Upon power on, a lube cycle will
initiate. (Pre-lube)
Fault contacts close during alarm
condition. For use with alarm light. (default)
Fault contacts open during alarm
condition. Failsafe, for use with PLC.
“
S
”
“
R
”
RUN
“
S
”