Electrical Installation (cont.)
Wiring: Fire signal relay (M series)
A contact closure across digital input terminals M3 and GND will
result in fan shut down. The relay uses a Normally Open (N.O.)
contact as shown. The relay coil must be energized by the
FACP for fan shutdown.
Two additional relay coil leads are provided to facilitate
supervision pass-through where required.
Optionally, the relay can be used with a Normally Closed (N.C.)
contact as shown. The relay coil must remain energized by the
FACP for fan operation. This would be considered a fail safe or
fail open wiring arrangement.
Two additional relay coil leads are provided to facilitate
supervision pass-through where required.
An alarm condition will stop the
fan and issue an “EF,” External
Fault, at the fan controller’s wall
controller.
An alarm condition will stop the
fan and issue an “EF,” External
Fault, at the fan controller’s wall
controller.
RUN
STOP
FWD
REV
MODE
RUN
ENTER
STOP
RESET
1.5KW
VFD-M
U
T1
V
T2
W
T3
Brake
B1
B2
U
T1
V
T2
W
T3
Brake
B1
B2
RUN
STOP
FWD
REV
REM
LOC
U
H
F
(-)
(+)
White(X2)-
Red(X2)-
C
NC
-Blue
-Yellow
NO -Orange
Coil: 20-32VDC
@ 20mA
RUN
STOP
FWD
REV
REM
LOC
U
H
F
(-)
(+)
White(X2)-
Red(X2)-
C
NC
-Blue
-Yellow
NO -Orange
Coil: 20-32VDC
@ 20mA
RUN
STOP
FWD
REV
MODE
RUN
ENTER
STOP
RESET
1.5KW
VFD-M
U
T1
V
T2
W
T3
Brake
B1
B2
U
T1
V
T2
W
T3
Brake
B1
B2
From Main FACP or
NAC Box (if applicable)
From Main FACP or
NAC Box (if applicable)