Wiring: Fire signal relay (E series)
Electrical Installation (cont.)
A contact closure across digital input terminals MI3 and DCM
will result in fan shutdown. The relay uses a Normally Open
(N.O.) contact as shown. The relay coil must be energized by
the FACP for fan shutdown.
Two additional relay coil leads are provided to facilitate
supervision pass-through where required.
From main FACP or
NAC box (if applicable)
Optionally, the relay can be used with a Normally Closed (N.C.)
contact as shown. The relay coil must remain energized by the
FACP for fan operation. This would be considered a fail safe or
fail open wiring arrangement.
Two additional relay coil leads are provided to facilitate
supervision pass-through where required.
From main FACP or
NAC box (if applicable)
An alarm condition will stop the
fan and issue an “EF,” External
Fault, at the fan controller’s wall
controller.
An alarm condition will stop the
fan and issue an “EF,” External
Fault, at the fan controller’s wall
controller.