16
Installation, Operation and Maintenance Manual
MAN 564 Rev. 6
June 2020
Installation
Section 2: Installation
2.4.2
Assembly Procedure
NOTICE
Failure to comply with the following procedures may impair product warranty.
!
WARNING
Installation, commissioning and maintenance and repair works should be carried out by
qualified staff. A non-conforming assembly could be the source of serious accidents.
For actuator assembly on the valve:
NOTICE
Check that the assembly position, as shown on the documentation, complies with
system’s geometry. Check the consistency of the parts of actuator-valve coupling.
•
Operate the actuator so that it reaches the position matching valve position
(Section 3.3).
•
Lubricate valve stem with oil or grease.
•
Properly clean and remove grease from coupling flange surfaces.
•
Connect, if supplied separately, the adjustment insert to valve stem and fasten it
with the special fastening pins.
•
Lift the actuator using the special lifting points (Section 2.2).
•
Install the actuator so that valve stem inserts in the coupling area. This coupling
should be made without forcing.
•
Fasten the two parts with the threaded connections (screws, tie rods, nuts). If
holes of coupling flanges are not aligned, adequately operate the actuator if
necessary move the mechanical stops backwards (Section 3.4).
•
Fasten threaded connections. Please refer to Table 9.