CT USE INSTRUCTIONS 

 

The  CT  is  used  to  ensure  the  pulse  being  created  will  always  be 
produced at the peak of any excessive neutral current.  

 

WARNING

 

Always install and remove the CT with the unit off. 

Never clamp CT around a conductor until connected to unit. 

 
 
 

1.

 

With power off of the unit, plug the CT into the back of the 
transmitter. 

2.

 

Clamp the CT around the neutral between the cable and the 
common neutral. The unit will do the rest 

3.

 

When  removing,  always  turn  the  unit  off  first  and  remove 
the CT from the cable before unplugging from the unit. 

 
 
 
 

 

 

 

 

 

Technical & Service

   

 

 

 

 

 

 

Bierer & Associates Inc.      

 

 

 

 

 

 

Manufacturing & Repair   

 

 

 

 

 

 

10730 Farrow Rd.              

 

 

 

 

 

 

Blythewood, SC  29016   

 

 

 

 

 

Tel: (803) 786-4839               

 

 

 

      Fax: (803) 786-5457 

                                                  www.bierermeters.com 

 

 

Содержание DCI-50-CT

Страница 1: ...1 Operating Instructions DCI 50 CT Cable Identifier...

Страница 2: ...Liability Bierer Associates Inc warrants this product to be free from defects in workmanship and material under normal use and service conditions for a period of one year from date of shipment Due to...

Страница 3: ...MAN HOLE OR DITCH ODD MAN OUT DCI 50 RED LEAD BLACK LEAD DCI 50 H1B H1A X1 X3 X2 H1B H1A TRANSFORMER SWITCH GROUNDED FAR END MAN HOLE OR DITCH ODD MAN OUT H1A H2A H3A H1B H2B H3B SIGNAL MOVING IN OPP...

Страница 4: ...he battery before operation 3 Install the battery to the unit by sliding the battery into the battery holder 4 Make sure the alligator clips are not touching and turn the unit on 5 The power and open...

Страница 5: ...on and place the tip on the wire close to the transmitter to verify cable and direction of the pulse 4 At the test site slowly approach the cable with the tip of the STRCV And identify the cable with...

Страница 6: ...around the cable at the source so the red arrow faces away from the transmitter on the cable Pointing towards the grounded end of the cable 5 Adjust the sensitivity knob till a clear positive indicat...

Страница 7: ...es away from the transmitter on the cable Pointing towards the grounded end of the cable 5 If the red cable is attached to the center conductor and the black cable is attached to the ground the needle...

Страница 8: ...to unit 1 With power off of the unit plug the CT into the back of the transmitter 2 Clamp the CT around the neutral between the cable and the common neutral The unit will do the rest 3 When removing...

Отзывы: