The DCI-50 Cable identifier is used to identify isolated, de-energized URD 
cables. The unit features a transmitter with 2 alligator clips and is powered by a 
Milwaukee, 18V, rechargeable battery. The unit has 5 LEDs for power, low 
battery, pulse operation, short/ open continuity. An optional CT input can be 
used when there is excessive neutral current on the cable being tested. The unit 
outputs a short duration current pulse that can be detected using one of the 
receivers. The receivers available are the STRCV, the AVR receiver, and the 
CD1000.  

DC TRANSMITTER SET-UP AND TEST

 

1.

 

Make sure the unit is off. 

2.

 

Press the button on the front of the 18V Milwaukee Battery. if there is 
less than 2 lights, recharge the battery before operation 

3.

 

Install the battery to the unit by sliding the battery into the battery 
holder. 

4.

 

Make sure the alligator clips are not touching and turn the unit on. 

5.

 

The power, and open continuity light should be illuminated and the 
pulse light should blink on and off approximately once per second. 

6.

 

Turn the unit off. 

7.

 

Connect the two alligator clamps together. 

8.

 

Turn the unit on. 

9.

 

The power and short continuity lights should be illuminated and the 
pulse light should be blinking. 

10.

 

Turn off the unit. 

 

DCI TRANSMITTER INSTALLATION 

1.

 

Isolate section of cable to be tested at near end and ground on far end. 

2.

 

Verify voltage is not present on cable being tested using an OSHA 
approved test device such as a Bierer voltage detector. 

3.

 

. Install DCI50 as shown in Diagram 1. 

NOTE: if the need to use the CT on the tests being performed, please refer to 
page 8, “CT USE INSTRUCTIONS” before proceeding. 

4.

 

Turn unit on. 

 
 
 
 
 
 
 
 
 

 

Содержание DCI-50-CT

Страница 1: ...1 Operating Instructions DCI 50 CT Cable Identifier...

Страница 2: ...Liability Bierer Associates Inc warrants this product to be free from defects in workmanship and material under normal use and service conditions for a period of one year from date of shipment Due to...

Страница 3: ...MAN HOLE OR DITCH ODD MAN OUT DCI 50 RED LEAD BLACK LEAD DCI 50 H1B H1A X1 X3 X2 H1B H1A TRANSFORMER SWITCH GROUNDED FAR END MAN HOLE OR DITCH ODD MAN OUT H1A H2A H3A H1B H2B H3B SIGNAL MOVING IN OPP...

Страница 4: ...he battery before operation 3 Install the battery to the unit by sliding the battery into the battery holder 4 Make sure the alligator clips are not touching and turn the unit on 5 The power and open...

Страница 5: ...on and place the tip on the wire close to the transmitter to verify cable and direction of the pulse 4 At the test site slowly approach the cable with the tip of the STRCV And identify the cable with...

Страница 6: ...around the cable at the source so the red arrow faces away from the transmitter on the cable Pointing towards the grounded end of the cable 5 Adjust the sensitivity knob till a clear positive indicat...

Страница 7: ...es away from the transmitter on the cable Pointing towards the grounded end of the cable 5 If the red cable is attached to the center conductor and the black cable is attached to the ground the needle...

Страница 8: ...to unit 1 With power off of the unit plug the CT into the back of the transmitter 2 Clamp the CT around the neutral between the cable and the common neutral The unit will do the rest 3 When removing...

Отзывы: