FAULT CAUSE
REMEDY
• The heater does not start:
lamp
is off
• No power supply
• Check functioning and position of switch
• Check the mains
• Check power connections
• Check the fuse
• Switch (a) in wrong position
• Select correct position
• Defective room thermostat
• Check that thermostat connection plug is inserted
• Verificare il collegamento elettrico del termostato
• Check thermostat setting and correct it
• Check functioning of thermostat
• The heater does not start:
lamp
is on
• Gas pressure switch tripped due to no gas or
insufficient pressure
• Check that gas feed pipe has been bled
• Check gas feed pressure
• Gas flow
• Check and clean gas filter.
• Clean and recalibrate the burner.
• The heater works erratically and the burner
goes on and off alternately:
lamp
goes on and off
• Burner thermostat has tripped due to
overheating
• Check correct position of air distribution channels and opening
of any flaps, openings, etc.
• Remove any foreign bodies trapped in the air ducts or ventilation
grilles
• The heater does not work:
lamp
is on
• Manual reset safety thermostat has tripped due
to excessive overheating of combustion
chamber
• Check that the fan motor starts correctly and is not obstructed
• Check that the fan motor is not burned out or that the motor
condenser is not broken
• Check burner calibration
• Check the chimney and correct discharge of fumes
• The heater does not work:
lamp
flashes
• Voltage control has tripped due to insufficient
electrical supply (V < 190V)
• The heater restarts automatically when sufficient voltage is
restored (V>190V)
• Check the power line if the heater starts and stops several times
• Check the power line if the heater does not start and remains in
safety stop
• The heater does not work:
lamp
is steady on
LAUNCH THE SELF-DIAGNOSIS PROCEDURE
PUSH BUTTON (D) FOR 7 SECONDS AND RELEASE:
THE BUTTON LAMP FLASHES WITH 2 TO 7 FLASHES
2
• No flame during ignition cycle
• Check gas pressure at burner
• Check and clean gas filter
• Check that ionisation probe is not discharging to earth
• Check ionisation probe connection cables (they must not
discharge to earth)
3
• Air pressure switch has tripped (electrical
contact remained open) at start of ignition cycle
• Check connection of pressure switch pipes
• Check pressure switch and replace if necessary
4
• Parasite flame detected in pre-wash phase
during ignition cycle
• Check that there are no gas pockets in the combustion chamber
• Check that ionisation probe is not discharging to earth
• Check ionisation probe connection cables (they must not
discharge to earth)
5
• Air pressure switch has tripped (electrical
contact has opened) during ignition cycle
• Check connection of pressure switch pipes
• Check that burner motor and fan are not blocked or broken;
replace if necessary
• Check that smoke exhaust chimney is not partially or totally
obstructed
• Check pressure switch and replace if necessary
6
• Air pressure switch has tripped (electrical
contact has opened) during work cycle
• Check connection of pressure switch pipes
• Check that burner motor and fan are not blocked or broken;
replace if necessary
• Check that smoke exhaust chimney is not partially or totally
obstructed
• Check pressure switch and replace if necessary
Number of flashes of lamp (d)
7
• No flame during work cycle
• Check gas pressure at burner
• Check and clean gas filter
• Check that ionisation probe is not discharging to earth
• Check ionisation probe connection cables (they must not
discharge to earth)
• Dirt on fan blades
• Remove dirt
• Fan is noisy or vibrates
• Poor air circulation
• Eliminate all obstacles to air flow
• Insufficient heating
• Insufficient burner capacity
• Contact Customer Service
Содержание BH 100
Страница 2: ...L L 195 04 BM 2 76...
Страница 46: ...RU L L 195 04 BM 46 76 1 6 4 G20 G30 G31 I II d 2 200 1 1 1 1 1 3 3...
Страница 47: ...RU L L 195 04 BM 47 76 4 4 1 5 1 4 2 H07RN F 1 5 2 25 2 L N L N HET...
Страница 48: ...RU L L 195 04 BM 48 76 c c 2 3 2 3 c 4 3 4 4 I II 1 2 3 4 1 2 3 4 5 3 100 6 4 6 EN 1443 1...
Страница 50: ...RU L L 195 04 BM 50 76 3 I 4 8 Honeywell SIT 6 4 8 O2 4 6 25 40 5 5 1 a 0 b a f d 3 5 2 a 0 f 5 3 a 6...
Страница 51: ...RU L L 195 04 BM 51 76 X X X X X X X X X X 6 1 6 2 6 3 A B C 6 4 6 5 A B 4 7 4 8 6 6...
Страница 52: ...RU L L 195 04 BM 52 76 6 7 70 30 6 8 A B 7 d d 3 d 7 7 b 7 d 7 a e b f d 7...
Страница 53: ...RU L L 195 04 BM 53 76 a V 190 V 190...
Страница 54: ...RU L L 195 04 BM 54 76 D 7 2 7 2 3 4 5 6 d 7...