User’s Manual UPSI-B-2410
User’s Manual UPSI-B-2410
1 General Information and Safety Warnings
Congratulations for choosing the UPSI-B-2410!
This manual explains the components and properties of the DC UPS UPSI-B-2410. All
information contained in this manual has been revised thoroughly to ensure accuracy
and completeness. Yet Bicker Electronic accepts no liability for any omissions or faults.
We will appreciate any notifications regarding faults, suggestions for improvements
and criticism.
Safety Warnings
Installation and connection must only be carried out by qualified personnel.
The relevant rules of electrical engineering must be observed!
A 15 A fuse must be installed at input line!
All connector cables must be dimensioned for the max. input current of the
UPSI-B-2410 (12.5 A) and an according additional protection must be provided.
The recommended cross section for the connector cables is 2.5 mm
2
.
A polarity reversal can damage the UPS as well as the connected load.
Charging the battery pack BP-2425C every six months with the DC UPS
UPSI-B-2410 is recommended during storage or when the battery pack
is not in use.
1.1 Contents of Delivery
DC UPS UPSI-B-2410
Pin-and-socket connector, Phoenix contact, 4- and 5-pole
Manual
1.2 Optional Accessories
Battery pack BP-2425C incl. pin-and-socket connector, Phoenix contact, 4-pole
RUPS 2000 OEM, UPS Management Software
Interface cable 9-pole SUB-D