background image

UPSI-1208D

Revision 1

24

F6  Initial operation

The correct installation of UPS and energy storage has to be ensured. The energy storage can be unplugged 
and exchanged at any time in compliance with the connecting order (see chapter F5 „Connecting diagram“). 
There are three connections to consider: a data connection to the battery (BAT DATA), a power supply to the 
battery (BAT PWR) and the input / output to the UPS. 

After that the start is accomplished by connecting the upstream power supply: 

When an input  

voltage higher than 11.5 V is connected to the input terminals, the energy storage gets queried and transmits 
its data. The UPS sets the corresponding end-of-charge voltage and releases the pack via the system present 
signal. After that, the charging of the energy storage starts.

Only energy storages by Bicker Elektronik may be used. These are appropriately qualified and have the neces-
sary protective functions. In addition, the charging methods are set using internal codes and settings. 

The applied voltage at the input of the UPS is passed through to the output, reduced by a current-dependent 
voltage drop (V

OUT

 = V

IN

 – 0.6 V at maximum current). The device charges the energy storage and monitors the 

upstream voltage thresholds at the input (UPS function).

It must be ensured that the source supplies enough current to guarantee the charging process (see chapter  
F4 „Dimensioning the upstream power supply“). 

Even after disconnecting the upstream source and also no voltage is measurable at the output, 
the UPS can be still powered by the energy storage. 

Содержание UPSI-1208D

Страница 1: ...English Bicker Elektronik GmbH Ludwig Auer Stra e 23 86609 Donauw rth Germany User Manual UPSI 1208D UPSI SYSTEM DIN RAIL...

Страница 2: ...ry Date Change 09 08 2021 Revision 0 1 Initial version 12 01 2022 Revision 1 Release version Legend of used symbols Symbol Description Attention Important hazard warning Do not dispose of in the domes...

Страница 3: ...UPSI 1208D Revision 1 3...

Страница 4: ...ttery technology LiFePO4 Supercaps EDLC Ambient temperature Operating 20 70 C Storage Transport 30 70 C Operating altitude 4000 m Max permitted humidity 95 at 25 C no dew Dimensions W H D 36 x 120 x 1...

Страница 5: ...lation position 18 F3 Description of connectors 20 F4 Dimensioning the upstream power supply 22 F5 Connecting diagram 23 F6 Initial operation 24 F7 Overview connector Counterpart with description Scop...

Страница 6: ...input voltage is applied the UPS works in normal mode automatically The input voltage is passed through to the output and the connected energy storage device is charged simultaneously The charging cu...

Страница 7: ...and fire hazards and can then be used indoors and outdoors It is primary built for being mounted on a DIN Rail and is intended for professional use in applications such as industrial control communic...

Страница 8: ...e device must not be immersed in water or exposed to splash water 4 The device must not be operated in a humid environment or in an environment where dew and condensation are to be expected 5 The devi...

Страница 9: ...DC 0 6 VDC max depending on load Current consumption IN UN IOUT IN ICHARGE 0 IMAX UN IOUT ISTAT BOOST ICHARGE max IDYN UN IOUT IDYN BOOST ICHARGE 0 INO LOAD UN IOUT 0 ICHARGE 0 ICHARGE UN IOUT 0 ICHAR...

Страница 10: ...uit proof Yes No load proof Yes Overcurrent shutdown 8 5 9 5 A for max 3 s 9 6 10 8 A for max 100 ms 10 8 A for max 5 ms OUTPUT DATA UPSI 1208D BATTERY MODE Unless otherwise stated all specifications...

Страница 11: ...WG Stripping length 6 mm 7 mm Tightening torque 0 3 Nm 0 4 Nm BATTERY CHARGE UNIT Charging method CC CV CP End of charge voltage Depending on energy storage app 11V max Charging current Depending on e...

Страница 12: ...nnection method Lockable plug connector Conductor cross section solid 0 205 mm 1 3 mm 24 16 AWG Conductor cross section flexible 0 205 mm 1 3 mm 24 16 AWG Conductor cross section with ferrule 0 205 mm...

Страница 13: ...on length 10 m Access time 1 s Voltage level 6 VDC 6 VDC Electrical isolation No GENERAL DATA Flammability class according to UL 94 housing terminal blocks V0 Weight 0 25 kg UPS connection in parallel...

Страница 14: ...torage transport 30 70 C Max permitted humidity 95 at 25 C no dew Operating altitude 4000 m Climate class 3k3 EN 60721 Degree of pollution 2 Overvoltage category EN 61010 1 EN 61010 2 201 I I Indoor O...

Страница 15: ...nt 4 kV 8 kV Criterion B Electromagnetic HF field EN 61000 4 3 Frequency range Test field strength Frequency range Test field strength Comment 80 MHz 1 GHz 10 V m 1 4 GHz 2 GHz 3 V m Criterion A Fast...

Страница 16: ...iour that is corrected by the device itself EMISSION ACCORDING TO EN 55016 2 3 DOMESTIC Basic standard CE Fulfilled requirements according to EN 55016 2 3 CE Domestic Conducted emission from the power...

Страница 17: ...awing E Name Address Support E Mail Phone number of the manufacturer Bicker Elektronik GmbH Ludwig Auer Stra e 23 86609 Donauw rth Germany E Mail support bicker de Tel 49 0 906 70595 0 Unless otherwis...

Страница 18: ...ion to correct polarity Before commissioning check all the connections for correctness F2 Convection and installation position For this DIN rail version vertical mounting on a horizontal rail DIN rail...

Страница 19: ...UPSI 1208D Revision 1 19 DIN Rail mounting and DIN Rail profile according to EN 60715 2 3 4 1 Push down...

Страница 20: ...INPUT OUTPUT IN OUT Vin Vout 4 3 2 1 The function of the relay connection is configurable via software When closing the relay the resistor value between both contacts is approx 0 otherwise they are op...

Страница 21: ...re sensor to energy storage connector 1 2 I C_0 SCL 3 Internal temperature sensor to energy storage connector 2 4 I C_0 SDA 5 NC 6 SP0 battery enable 7 5 V max 50 mA 8 GND BATTERY TYPE USED PINS LiFeP...

Страница 22: ...pplied from a SELV or PELV power supply In order to operate the UPSI 1208D with complete functionality the upstream power supply has to provide at least 12V 10A and use no constant current function If...

Страница 23: ...te polarity 2 AWG16 wire should be used 1 5 mm2 CONNECTING ORDER 1 BAT PWR 2 BAT DATA 3 APPLICATION VOUT 4 DC SOURCE VIN 5 RELAY USB RS232 Dismantling order reverse to connection ENERGY STORAGE VIN BA...

Страница 24: ...nd releases the pack via the system present signal After that the charging of the energy storage starts Only energy storages by Bicker Elektronik may be used These are appropriately qualified and have...

Страница 25: ...Data The status LED indicates the error status by means of a very rapid flashing sequence A restart attempt occurs every 10 seconds in normal mode During battery mode there is no restart attempt Shor...

Страница 26: ...percapacitors in particular an additional switch off threshold can take effect if the discharge current of the energy storage device is too high 15 A This can occur at very high load currents at the o...

Страница 27: ...pause 2s Status Reboot Output is deactivated and time until reboot runs Reboot phase UPS FAILURES Quick flashing without pause Status UPS failure Output current too low UPS is deactivated Overcurrent...

Страница 28: ...l True Shutdown SOC Threshold Reached Max Backup Time Timeout Shutdown Timer Timeout Shutdown SOC Enabled Max Backup Enabled Shutdown Timer OS Enabled Ignition Timer Timeout Ignition Pin High True Fal...

Страница 29: ...an actually required should always be used The less deep the packs are discharged the longer the service life lasts F15 Maintenance The UPS contains no serviceable parts In case of a malfunction the u...

Страница 30: ...not intended Power Fail could be caused With maximum load the voltage at the input of the device must not undercut 11 5V Even after the upstream supply has been disconnected the device continues to r...

Страница 31: ...tions Windows is a registered trademark of the Microsoft Corp Status as at 12 01 2022 Revision 1 Bicker Elektronik GmbH Ludwig Auer Stra e 23 86609 Donauw rth Germany Tel 49 0 906 70595 0 Fax 49 0 906...

Отзывы: