UPSI-1208D
Revision 1
4
Input voltage
12 V DC (11.5…16 V)
Input current
9.2 A max.
Output voltage
Normal mode: V
IN
– 0.6 V DC max. (depending on load)
Battery mode: 12 V DC
Output current
8 A nominal
Capacitive load
3000 µF (at start)
Charging method
CC / CV / CP
Protection
Input: Reverse polarity protection
Output: Overcurrent protection, Short circuit protection
Interface
USB, RS232, HID UPS
Possible battery technology
LiFePO4, Supercaps (EDLC)
Ambient temperature
Operating: -20…+70 °C
Storage / Transport: -30…+70 °C
Operating altitude
≤4000 m
Max. permitted humidity
≤95 % (at +25 °C, no dew)
Dimensions W/ H / D
36 x 120 x 100 mm ±0.5 mm
(without front connectors and DIN-Rail mounting bracket)
Weight
0.25 kg
Technical Data
A Brief specification
UPSI-1208D
12 V DC / 8 A
12 V DC UPS (DIN rail version)
Intelligent input current detection
Regulated output voltage in battery mode
Minimum load detection
Power fail timer function
Relay dry contact on power fail
Reboot function
Fuel gauge
Shutdown via external signal