Biasi Parva HE M96.28SR/P Скачать руководство пользователя страница 4

Boiler installation and commissioning tips

n

The installation

must be carried out by

a qualified person who will be responsible for

observing the current Regulations.

Installing the boiler...

n

Do not forget to remove the transit caps

and plugs from the boiler connections these

are fitted to every boiler.

n

Keep the boiler clear of dust during in-

stallation and in particular do not allow any

dust or debris to enter the top of the boiler

where the flue connection is made. It is rec-

ommended that you put a dust sheet over the

top of the boiler until you are ready to make

the flue connection.

n

Because every boiler is fired and tested

live at the factory, a small amount of water re-

mains within the boiler. It is possible for this

water to initially cause the pump to seize. It is

therefore recommended that the pump rotor

be manually turned to free its rotation before

turning the boiler on.

n

Remember to release the auto air purge

before filling the boiler. See the instructions to

identify the location of this device.

n

Do not remove the cap of the pressure

test points of the air switch (top left side of the

boiler).

n

You are strongly advised to flush out the

system both cold and hot in order to remove

system and installation debris.

n

It is also sensible to initially fire and com-

mission the boiler before connecting any ex-

ternal controls such as a room thermostat. By

this method if you have a subsequent prob-

lem following the addition of an external con-

trol you can eliminate the boiler from your

fault analysis.

n

Do not forget to range rate the boiler to

suit the system requirements. This pro-

cedure is covered in the commissioning sec-

tion of the installation manual.

n

If the boiler is fitted with a digital pro-

grammer, when setting the times for auto-

matic operation, remember that for every

“ON” time there must be an “OFF” time to fol-

low and that on every occasion you enter a

time you must also indicate which days that

you want the boiler to follow the timed set-

tings.

n

Some products incorporate an anti cycl-

ing time delay. It is normal when first switch-

ing the boiler on for the boiler to operate on

heating for a few seconds then switch off.

After 3--- 4 minutes has elapsed the boiler will

then re ignite and operate perfectly normally.

The ignition delay cycle does not prevent

normal operation of the boiler to provide

d.h.w.

n

If you are in any doubts as to the installa-

tion or operation of the boiler please read the

instruction manuals thoroughly and then if

necessary contact Biasi UK for advice and

assistance.

Please remember that if you are in any doubt about the installation of this product you can contact our

Technical Helpline on tel. 0121 506 1350

Содержание Parva HE M96.28SR/P

Страница 1: ...Wall hung fan flue room sealed high efficiency gas boiler User manual and Installation instructions GARDA HE SYSTEM Models M96 28SR P M96 32SR P...

Страница 2: ...t is of the correct gauge for the flow to the boiler is fitted with all the safety and control de vices required by the current Regulations n Ensure that the installer has connected the pressure relie...

Страница 3: ...gh risk follow good hygiene prac tices wash handsbefore touching eyes consum ing food drinking or using the toilet First aid Medical attention must be sought fol lowing eye contact or prolonged redden...

Страница 4: ...It is also sensible to initially fire and com mission the boiler before connecting any ex ternal controls such as a room thermostat By this method if you have a subsequent prob lem following the addi...

Страница 5: ...20 6 3 Installing the bracket 20 6 4 Overall dimensions 21 6 5 Joints 21 6 6 Mounting the boiler 21 6 7 Fitting the flue system 22 6 8 Choice of flue 22 6 9 Electrical connections 24 6 10 External fro...

Страница 6: ...l knob 8 Service knob 9 Appliance operation lights The service knob 8 is useless for the normal oper ation of the boiler It must be used only by a qualified person during commissioning and servicing 1...

Страница 7: ...ry 2 seconds normally operating boiler Function selector in position C h operation Frost protect operation Faulty c h temperature probe NTC Faulty flue temperature probe NTC Faulty primary circuit no...

Страница 8: ...ro cedure you are advised to contact your In staller or an Approved Engineer This appliance is provided with a built in anti freeze system that operates the boiler when the temperature is below 5 C Th...

Страница 9: ...pre set in the factory can however be reduced in level according to actual system requirements Such adjustments must be carried out by a quali fied person therefore we advise you to contact your insta...

Страница 10: ...the electricity supply to the boiler by means of the fused spur isolation switch 2 Shut off the gas supply cock 12 and the valves for the water circuit fitted under the boiler Fig 2 8 3 Empty the wate...

Страница 11: ...will be inspected and cleaned This service can be part of a maintenance con tract In particular you are advised to have the following checks carried out primary heat exchanger burner exhaust fume duc...

Страница 12: ...case tempera ture rise in the circuit can cause the pressure relief valve to open So that this does not happen and to decrease the pressure to a normal value it is advisable to vent some of the water...

Страница 13: ...ow switch 21 C h temperature probe NTC 22 Flame detecting electrode 23 Ignition electrodes 24 Burner 25 Combustion chamber 26 Primary heat exchanger 27 Fan 28 Air switch pressure test points 29 Flue t...

Страница 14: ...Technical information 10 4 2 Main diagram 39 30 41 40 20 26 23 35 17 33 19 36 16 38 11 13 12 37 27 22 21 34 32 24 15 31 14 10 29 Fig 4 2 INSTALLATION...

Страница 15: ...ermostatic valves or sys tem component cocks the by pass valve ensur es a minimum flow of water through the primary heat exchanger 4 4 Expansion vessel Note this boiler is designed for operation only...

Страница 16: ...easonal efficiency G20 B band B 87 7 Seasonal efficiency G30 G31 B band B 87 1 Gas supply pressures Gas Natural G20 Butane G30 Propane G31 Norm Pa mbar 2 000 20 2 900 29 3 700 37 Max Pa mbar 2 500 25...

Страница 17: ...2 3 15 AF Flue design Flue pipe diameter Coaxial mm 60 100 Twin split pipes mm 80 Roof mm 80 125 Nominal heat flow rate A C kW 29 0 Exhaust temperature C C 90 Mass flow rate C g s 21 1 Flue gas figure...

Страница 18: ...Seasonal efficiency G20 B band B 86 8 Seasonal efficiency G30 G31 B band B 88 8 Gas supply pressures Gas Natural G20 Butane G30 Propane G31 Norm Pa mbar 2 000 20 2 900 29 3 700 37 Max Pa mbar 2 500 25...

Страница 19: ...2 3 15 AF Flue design Flue pipe diameter Coaxial mm 60 100 Twin split pipes mm 80 Roof mm 80 125 Nominal heat flow rate A C kW 33 3 Exhaust temperature C C 90 Mass flow rate C g s 21 5 Flue gas figure...

Страница 20: ...is drawn tothe requirementsof the current I E E Wir ing Regulations and in Scotland the electrical provisions of the Building Regulations applicable in Scotland with respect to the installation of the...

Страница 21: ...both to the boiler and the other appliance when they are in use at the same time Pipework must be of adequate size Pipes of a smaller size than the boiler inlet connection should not be used Installat...

Страница 22: ...ed to assure a minimum flow of 500 600 lts hr through the main heat ex changer If you are installing a system that includes thermo static radiator valves TRV and or small bore 8 10 mm it may be necess...

Страница 23: ...competent person and be in accordance with the current I E E Regulations and any local regulations which apply Reference should be made tu the current ETCI rules for electrical installations For Irel...

Страница 24: ...with during installation To allow maintenance procedures it is necess ary to leave the minimum gaps indicated in Fig 6 1 25 50 200 200 Fig 6 1 all dimensions in mm When installing the boiler in a cup...

Страница 25: ...lief valve 15 Condensate drain 25 plastic Tab 6 1 sizes in mm o d 6 6 Mounting the boiler 1 Take the protective caps off the boiler pipe work 2 Thoroughly clean the connections 3 Mount the boiler on i...

Страница 26: ...its are available for connecting to the boiler Standard horizontal flue kit Fig 6 6A Co axial 60 100mm nominal length 1m Thiskitisnormally supplied with the boiler and can be fitted to allow discharge...

Страница 27: ...he pipe that discharges the exhaust gasses Consequently it is possible to extend the flue system to a greater distance than that pro vided by the standard horizontal co axial flue If either an additio...

Страница 28: ...ute Each additional elbow reduces the overall accept able length of the flue system as follows 45 reduce length by 0 5 m 90 reduce length by 1 m 90 1 m 45 0 5 m max 8 5 m Only for M96 32SR max 6 m max...

Страница 29: ...ing from the fused spur isolation switch to the power supply terminal block of the boiler Fig 6 13 keeping the same connections for the live brown wire and the neutral blue wire External 3 A fuse or f...

Страница 30: ...olation switch Fig 6 15 6 10 External frost protection 10 Connect the frost thermostat between ter minals 1 and 2 as shown in Fig 6 16 Do not connect live wires to terminals to which the room thermost...

Страница 31: ...ration is controlled by the external control terminal block In Fig 6 18 the boiler is not permanently con nected to the supply line The boiler operation is controlled by switching the mains supply In...

Страница 32: ...erminal block Room thermostat A B 5 4 Cylinder thermostat C 1 2 8 7 6 GY WH OR GRYE BL 2 3 8 5 7 MAINS 230V a c Switched 3 Amp fused spur L N 2 3 1 Programmer HTG HW OFF HW ON L N 2 1 4 6 7 Power supp...

Страница 33: ...ink Room thermostat A B 4 5 Cylinder thermostat C 1 2 8 7 6 GY WH OR GRYE BL 2 3 8 5 7 MAINS 230V a c Switched 3 Amp fused spur L N 2 3 1 Programmer HTG HW OFF HW ON L N 2 1 4 6 7 Power supply L N 2 3...

Страница 34: ...nd check the gas connector on the appliance for leaks Open position 12 Fig 7 1 7 3 Initial filling of the system 1 Open the c h flow and return valves 2 Remove the front panel of the case see the sect...

Страница 35: ...ly normally If externalcontrols are fitted e g Timeclock room thermostat ensure they call for heat 1 Turn on the electricity supply to the boiler switching on the fused spur isolation switch The appli...

Страница 36: ...gas pressure adjustment procedure is given in the Gas Valve section of the service manual If maximum and or minimum gas pressures are adjusted then the ignition gas pressure must be checked and adjust...

Страница 37: ...ated in Fig 7 6 and ensure that the timer selector switch and room thermostat if fitted are set to heat demand 7 9 8 5 6 Fig 7 6 5 Keep pressed the reset button 6 for about 10 seconds until the lock o...

Страница 38: ...bout 5 seconds until the lamps 9 all brief ly simultaneously blink 14 To reset the boiler to the normal operation turn it OFF and ON by the function selector 7 In any case the boiler automatically res...

Страница 39: ...con densate traps 7 12 Instructing the user Hand over this combined User Installation man ual and the Service manual tothe end user and ex plain how to use the unit Take the User step by step through...

Страница 40: ...lfor detailed in structions 5 Carry out the conversion for the type of gas re placing the burner injectors correctly 6 Re assemble the burner the front panel of the combustion chamber and the lid of t...

Страница 41: ...it ON by the function selector 7 on the desired operation and checking the ignition pressure and that the burner lights up uniformly In any case the boiler automatically resets to its nor mal operati...

Страница 42: ...off the gas cock before carrying out any pro cedures whatsoever for cleaning mainten ance opening or dismantling boiler panels 9 2 Dismantling the external panels Front panel 1 Loosen the three screw...

Страница 43: ...e burner 1 Take off the front of the case 2 Take off the removable front of the air tight chamber and the front panelof the combustion chamber 3 Brush out the burner with a bristle paintbrush 9 7 Chec...

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...17962 1404 0 1607 48A5 UK Biasi UK Ltd Newman Park Western Way Wednesbury WS10 7BJ Sales Tel No 0121 506 1340 Sales Fax No 0121 506 1360 Service Tel No 0121 506 1350 Service Fax No 0121 506 1370 www...

Отзывы: