- 24 -
MAIN ElEctroNIc coNtrol/IgNItIoN p.c.b.
parameter
lcd
values (set)
Chimney sweep function
p 09
00 =
No chimney sweep
fun (factory set)
01 =
D.h.w. low power
sweep---test
02 =
C.h. low power
sweep---test
03 =
C.h. max power
sweep---test
04 =
D.h.w. max power
sweep---test
C.h. reignition frequency
p 10
00÷99
(0÷600 sec.)
(factory set
30 =
3 minutes)
C.h. pump post-circu-
lation
p 11
00÷99
(0÷600 sec.)
(factory set
10 =
1 minute)
Max. useful output in
c.h. mode
p 12
00÷99
(0÷100%)
factory set
74
= Inovia 25C ERP
78
= Inovia 30C ERP
84
= Inovia 35C ERP
99
= Inovia 25S ERP
C.h. pump working type
p 13
00 =
Depends on room
thermostat (factory set)
04 =
Always running
Ignition power
p 14
00÷99
(0÷100%)
factory set:
natural gas (G20)
20
= Inovia 25C ERP
31
= Inovia 30C ERP
25
= Inovia 35C ERP
37
= Inovia 25S ERP
Ignition power
p 14
lpG propane (G31)
26
= Inovia 25C ERP
37
= Inovia 30C ERP
31
= Inovia 35C ERP
43
= Inovia 25S ERP
K value (external probe
diagram)
p 15
00 =
Off
(factory set)
01
(=0,1)÷
60
(=6,0)
K value
Min. useful output c.h.
p 16
00
÷
99
(0%÷100 %)
(factory set
00
= 0%)
D.h.w. burner turn off
function
p 17
00 =
Burner off at fixed
d.h.w. = 65 °C
(factory set)
01 =
Burner off at set
point +5 °C
NTC on the c.h. return
p 18
00 =
Probe not present
01 =
Probe present
LCD type
p 19
00 =
TOP
02 =
MEDIUM
(factory set)
Not used
p 20
Not used
p 21
Not used
p 22
Not used
p 23
Not used
p 24
Not used
p 25
Not used
p 26
parameter
lcd
values (set)
C.h. minimum setpoint
p 27
25÷45
(factory set 25 °C)
Maintenance intervals
p 28
00
÷
48
(= months)
(factory set
12
months)
Presence of domestic
cold water temp.
probe or set of inlet cold
water with solar control
p 29
00
= No NTC probe
01
= Yes NTC probe
04
÷
45
(°C) temp.
NTC inlet probe with solar
control
Correct pressure c.h.
system
p 30
05
(0,5 bar) ÷
15
(1,5 bar)
factory set
10
(=1 bar)
Tab 9.1