Biasi GARDA HE M96.24SM/B Скачать руководство пользователя страница 31

29

15

D.h.w. flow switch, filter and flow

limiter

15.1

Function

The d.h.w. flow switch

A

in Fig. 57 is a device that gener-

ates an electrical signal when hot water is drawn.

A

Fig. 57

When the flow rate through the d.h.w. circuit reaches

about 2,5 litres/min’, the float 4 (Fig. 59) is drawn to-

wards the right.

The resulting magnetic field of ring 3 increases and re-

aches the flow switch sensor 1.

The sensor generates an electrical signal that switches

the boiler d.h.w operation ON.
The state of the sensor is also indicated by means of the

lamp

B

placed on the sensor body.

B

C

Fig. 58

15.2

Nomenclature and location of parts

(Fig. 59)

1

Flow switch sensor

2

Plug

3

Magnetic ring

4

Float

5

Spring

6

Filter

7

Body

8

Spring seat

9

Flow limiter (M96.28SM/... optional accessory)

10

Threaded ring

1

2

3

4

5

6

7

8

9

10

Fig. 59

15.3

Checks

Warning: isolate the boiler from the mains

electricity supply before removing any

covering or component.

n

Flow switch sensor operation

1

Remove the front panel of the case.

2

Switch on the boiler and open a d.h.w. tap. The

lamp

B

(Fig. 58) placed on the sensor body is

switched on when the flow rate reaches about 2,5

litres/min’.

15.4

Removal of the f

low switch sensor

Warning: isolate the boiler from the mains

electricity supply before removing any

covering or component.

1

Remove the front panel of the case.

2

Disconnect the connector

C

(Fig. 58) and remove

the sensor by pulling it towards the front of the

boiler (the sensor is held in place by means of a

spring).

15.5

Removal of the flow switch group and

d.h.w. circuit filter

Warning: isolate the boiler from the mains

electricity supply before removing any

covering or component.

1

Remove the front panel of the case and empty the

d.h.w. circuit.

Содержание GARDA HE M96.24SM/B

Страница 1: ...igh efficiency gas boiler Service manual GARDA HE Models G C Appl No M96 24SM B 47 970 25 M96 28SM B 47 970 26 GARDA HE SILVER Models G C Appl No M96 24SM D 47 970 27 M96 28SM D 47 970 28 Leave this m...

Страница 2: ...11 1 Function 23 11 2 Checks 23 11 3 Removal 23 11 4 Ignition and control sequence 24 12 Modulating gas valve 25 12 1 Function 25 12 2 Nomenclature of the parts 25 12 3 Adjustment 25 12 4 Checks 26 12...

Страница 3: ...lease Pump D h w temp probe D h w heat exchanger Expansion vessel Detection electrode valve Condensing Diverter valve Air pressure switch Main circuit Flue thermostat heat exchanger Condensate trap fl...

Страница 4: ...A Fig 2 lift the panel and remove it A Fig 2 To remove the side panels loosen the screws B and C Fig 3 bring the base of the panels away from the boiler and lift them freeing them from the top hooks B...

Страница 5: ...d of the sealed chamber For this purpose remove the front and side panels of the case remove the screws G as indicated in Fig 6 and remove the lid 2 5 Emptying the primary circuit 1 Close the c h circ...

Страница 6: ...low switch C h temperature probe NTC Electronic control p c b Full sequence ignition device gn green ye yellow rd bu wh rd bu rd bu bn bu bn bn bu bn bu bk bn bu 3 1 2 bk gnye bu rd bu bn gnye gnye gn...

Страница 7: ...NTC Three way diverter valve gas valve DHW flow switch flow switch CH temperature probe NTC Electronic control p c b Full sequence ignition device gnye gnye bu gnye gy rd bu wh rd bu rd bu bn bu bn bn...

Страница 8: ...L Transformer ACTIVE CIRCUIT INACTIVE CIRCUIT L LINE N NEUTRAL N Electronic control p c b low voltage section J1 2 J3 3 J3 5 J3 4 J3 2 J3 1 J2 4 J2 5 Three way diverter valve Pump Full sequence igniti...

Страница 9: ...h operation only during d h w operation 230 230 230 0 Pump Full sequence Ignition device 3 way diverter valve 0 0 Electronic control p c b 230 230 Modulating Gas valve Safety thermostat 0 Fan 230 230...

Страница 10: ...ration only during d h w operation 230 230 230 0 Pump Full sequence Ignition device 3 way diverter valve 0 0 Electronic control p c b 230 230 Modulating Gas valve Safety thermostat 0 Fan 230 230 0 Ele...

Страница 11: ...Pressure gauge By pressing the reset push button the boiler turns on and operates correctly J J 6 J J J By pressing the reset push button the boiler starts the ignition cycle The burner doesn t light...

Страница 12: ...e safety valve during operation on c h J J J J Water leaks from the safety valve when the boiler is off J J J Note Useful information can be obtained also from the optical indication given by the appl...

Страница 13: ...it from the wiring E M C B F C D G I J N K L H Fig 11 7 Loosen the connection K and move the pipe L downwards freeing it from the connection of the primary het exchanger 8 Remove the clip M 9 Move th...

Страница 14: ...see section 21 3 5 Completely loosen the connection G and slightly move the pipe H upwards 6 Remove the clip I and move the pipe J down wards freeing it from the connection then turn it towards right...

Страница 15: ...re removing any covering or component 1 Remove the front and right hand side panels of the case 2 Empty the primary circuit and the d h w circuit of the boiler 3 Completely unscrew the two Allen key s...

Страница 16: ...turn the rotor in the direc tion of the arrow If there is a defect in starting the rotor will begin to turn normally only starting it manually n Check that the impeller is integral with the rotor Wit...

Страница 17: ...B brass spindle when the boiler operates in c h mode In both figures the relationship between the position of the actuator and the resistance of the motor windings the motor must be disconnected from...

Страница 18: ...t both c h and d h w temperature probe respectively H and I 6 Unscrew the connector J the c h flow connector and the d h w outlet connector F G J H I Fig 25 7 Remove the d h w heat exchanger see secti...

Страница 19: ...es inlet in formation coming from the boiler the sensors or from the outside knobs room thermostat etc processes it and consequently acts with outlet commands on other components of the boiler Fig 28...

Страница 20: ...trol panel through the adjustment made by the user knob 75 C Fig 31 Normally the result of the comparison between these two signals directly operates the adjustment elements of the gas valve modulatio...

Страница 21: ...le to select the various boiler control function modes In Fig 32 the selectors are illustrated in the configur ation in which the boiler is set in the factory natural gas boiler ON 1 OFF 0 1 2 3 4 8 G...

Страница 22: ...ectronic control p c b does not supply any de vice pump fan etc check that the fuse 12 Fig 29 is complete If the fuse has blown replace it with one that has the same characteristics after having ident...

Страница 23: ...ake sure the c h and d h w tem perature adjustment knobs can move freely for the complete range If not remove the spindle again as described at step 3 turn the knob half a turn and re insert the spind...

Страница 24: ...or heat from room thermostat Starts the circulator Operates motorised valve Supplies the ignition device NO Circulator off Operates motorised valve Ignition device off YES YES Fig 40 10 11 Thermal con...

Страница 25: ...r connection f Gas injectors blocked f Faulty modulation gas valve faulty on off oper ators or not electrically supplied f Faulty Full sequence ignition device Other components like the air pressure s...

Страница 26: ...sure switch at work NO YES starts ignition discharges opens gas valve beginning of ignition period flame presence end of ignition period NO NO YES closes gas valve stops fan interrupts ignition discha...

Страница 27: ...e input connect a suitable pressure gauge and check the gas pressure of the supply network 3 Remove the gauge and close the pressure test point 6 4 Open the gas valve outlet pressure test point 8 in F...

Страница 28: ...case as explained in the section 2 3 of this manual 2 Disconnect the connector D Fig 47 3 Unscrew the screw E and remove on off oper ator coils 4 Reassemble the coils carrying out the removal operati...

Страница 29: ...the switch box verify the position of the shaft B referring to Fig 50 B Boiler OFF Boiler ON Fig 50 n Electrical check It is possible to verify the general operation of the switch by measuring the ele...

Страница 30: ...rrect value 14 3 Removal of the expansion vessel If there is at least 400 mm clearance above the boiler and the rear exit flue can be easily removed the expan sion vessel can be changed without removi...

Страница 31: ...ssory 10 Threaded ring 1 2 3 4 5 6 7 8 9 10 Fig 59 15 3 Checks Warning isolate the boiler from the mains electricity supply before removing any covering or component n Flow switch sensor operation 1 R...

Страница 32: ...tch sensor 1 and bring the ring in touch with the sensor as illustrated in Fig 61 4 Observe the lamp B placed on the sensor body that should light If not reverse the ring and repeat the previous opera...

Страница 33: ...flow c h return d h w inlet d h w outlet A B Fig 63 16 2 Checks n Temperature resistance relationship Warning isolate the boiler from the mains electricity supply before removing any covering or compo...

Страница 34: ...e is fitted on the rear side of the div erter group A Fig 65 17 2 Removal Warning isolate the boiler from the mains electricity supply before removing any covering or component 1 Remove all the case p...

Страница 35: ...measure the electrical resistance of the motor that has to be about 43 W M96 24SM 25 W M96 28SM at ambient temperature D A C Fig 68 n Check of the Air pressure switch operation Warning isolate the bo...

Страница 36: ...ls the sealed chamber lid and the combustion chamber lid 2 Disconnect the connectors D and the earth con nection E Fig 68 3 Disconnect the pipe which connect the venturi device to the Air pressure swi...

Страница 37: ...manual B H I Fig 73 18 5 Removal of the Air pressure switch Warning isolate the boiler from the mains electricity supply before removing any covering or component 1 Remove all the case panels and the...

Страница 38: ...e removing any covering or component 1 Remove all the case panels the sealed chamber lid and the combustion chamber lid 2 Check for the integrity of the insulation of wires which connect the electrode...

Страница 39: ...cur Warning isolate the boiler from the mains electricity supply before removing any covering or component n Electrical function 1 Remove all the case panels and the lid of the sealed chamber 2 Remove...

Страница 40: ...der a protective cap B in Fig 81 and can be re ached by unscrewing the cap The intervention of the Flue thermostat may be caused by a defective operation of the device but more probably is due to a po...

Страница 41: ...ec trode Fig 84 C B Fig 84 If the drain pipe is plugged or in any case in which the condensate isn t correctly evacuated the condensate level in the trap rises putting in contact the electrodes thus c...

Страница 42: ...E83 178 Combustion chamber side panels 2 BI1326 100 10 E83 180 Combustion chamber rear panel mod M96 24SM 1 BI1326 107 E83 181 Combustion chamber rear panel mod M96 28SM 1 BI1326 108 11 E83 196 Combus...

Страница 43: ...Short spare parts list 41 1 2 6 4 5 7 3 8 15 18 12 13 20 22 23 24 26 27 14 16 25 17 19 9 10 11 9 21...

Страница 44: ...796210720 17962 1072 0 2404 44A4 UK Biasi U K Ltd Unit 31 33 Planetary Road Industrial Estate Neachells Lane Willenhall Wolverhampton WV 13 3XB Technical helpline 01902 304 400 Web site www biasi co u...

Отзывы: