- 79 -
MAINTENANCE
MAINTENANCE
sis check and adjustment if necessary as
described in the section "Gas valve - Ad
-
justment - Chimney Sweep Mode" of the
Service manual.
Fig. 10.14
Flue analysis
points
•
Make sure that the ambient thermostat is
in the position “call for heat”.
•
Withdraw an abundant amount of D.H.W.
by opening the taps.
•
Activate the “flue sweep function” at maxi
-
mum heating power (see "Setting the
boiler flue sweep function" on page 80).
•
Check the combustion of the boiler using
the outlets located on the flue tubes (Fig.
10.14) and compare the data measured
with that following.
Fig. 10.15
Model BASICA COND 24C - M275V.2024 SM
Nominal heat input
(A) (E)
kW
21,0
Nominal efficiency
%
98,2
Combustion efficiency
%
98,4
Air index
n
1,2
Flue gas CO
2
content
%
9,0 - 9,6
Flue gas O
2
content
%
4,1
Flue gas CO
content
ppm
140
Flue gas temperature
°C
82,0
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
Fig. 10.16
Model BASICA COND 28C - M275V.2428 SM
Nominal heat input
(A) (E)
kW
25,0
Nominal efficiency
%
98
Combustion efficiency
%
98,2
Air index
n
1,2
Flue gas CO
2
content
%
9,0 - 9,6
Flue gas O
2
content
%
4,1
Flue gas CO
content
ppm
180
Flue gas temperature
°C
85,0
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
Fig. 10.17
Model BASICA COND 32C - M275V.2832 SM
Nominal heat input
(A) (E)
kW
27,5
Nominal efficiency
%
98,2
Combustion efficiency
%
98,4
Air index
n
1,2
Flue gas CO
2
content
%
9,0 - 9,6
Flue gas O
2
content
%
4,1
Flue gas CO
content
ppm
190
Flue gas temperature
°C
83,0
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
The values in the tables are measured at
the nominal useful power with factory cali
-
bration.
10.12 Checking the condensate
drain pipe
The condensate drain pipe 32 (Fig. 10.18)
does not require any particular mainte
-
nance but just check:
•
That no solid deposits have formed, if so
remove them.
•
That the condensate drain piping is not
clogged.