- 68 -
MAINTENANCE
GAS CONVERSION
Fig. 8.3
11
12
13
Fig. 8.4
Scroll the various parameters using keys
•
12 or 13 until the letters
Pr
that alternate
with code
05
are displayed on the LCD
display, indicating that "parameter 05"( Fig.
8.5 ) has been activated.
Fig. 8.5
Press keys
• 11
and
13
( Fig. 8.3
) at the
same time until the value of parameter
05(00=G20) is displayed on the LCD dis-
play ( Fig. 8.6 ).
Fig. 8.6
By pressing key
• 13
three times, it is pos-
sible to change the value of parameter 05
from
00
=G20 to
05
=G31, which is ok for
LPG gas.
By pressing key
•
11 ( Fig. 8.3 ) confi rmation
of the inserted value is obtained.
Press keys
• 11
and 12 ( Fig. 8.3 ) at the same
time to exit without changing the value (re-
turn to the parameters list Fig. 8.5 )
Press keys
• 11
- 12 - 13 ( Fig. 8.3 ) at the
same time for 10 seconds to exit the "pro-
gramming mode".
Calibrate the gas valve according to the
•
instructions given in the Service manual,
section Gas valve - Adjustment..
Reposition the controls panel and remount
•
the front panel of the body.
Apply the label indicating the gas nature
•
and pressure value for which the appli-
ance is regulated. The self adhesive label
is contained in the transformation kit.