437

8.2) Logics
-

TCA dwell time [0]

1 - Carries out automatic gate closing after the dwell time set (automatic

closing time). Automatic closure is activated by: the gate reaching the
open end-of-stroke position, the end of operation time during the
opening phase, and the gate stopping during the opening phase by
means of a start impulse.

0 - Excludes automatic closure.

-

2-step, 4-step logic [0]

1 - Enables 2-step logic (prevails over “3-step logic”). A start impulse has

the following effects:

     door closed: ................................................................................. opens
     on opening: .................................................................................. closes
     door open: ................................................................................... closes
     on closing: ................................................................................... opens
     after stopping: .............................................................................. opens
0  - Enables 4-step logic (prevails over “3-step logic” if it is the latest choice).

A start impulse has the following effects:

     door closed: ................................................................................. opens
     on opening: ................................... stops and enters TCA if configured
     door open: ................................................................................... closes
     on closing: .................................. stops and does not enter TCA (stop)
     after stopping: .............................................................................. opens

-

3-step logic [0]

1 - Enables 3-step logic (with 2 steps, 4 steps=0 logic). A start impulse has

the following effects:

     door closed: ................................................................................. opens
     on opening: ................................... stops and enters TCA if configured
     door open: ................................................................................... closes
     on closing: ................................................................................... opens
     after stopping: .............................................................................. opens
0 - Disables 3-step logic.

-

Impulse lock on opening [0]

1 - The start impulse has no effect during the opening phase.
0 - The start impulse becomes effective during the opening phase.

-

Impulse lock on closing [0]

1 -The start impulse has no effect during the closing stage.
0 -The start impulse is effective during the closing stage.

-

Impulse lock in TCA [0]

1 - The start impulse has no effect during the TCA dwell time.
0 - The start impulse is accepted during the TCA dwell time.

-

Pre-alarm [1]

1 - The blinker comes on for about 3 seconds before the motors start.
0 - The blinker comes on at the same time as the motors start.

-

Open/Close control (Hold to Run) [0]

Acts on the signals connected to terminals 44-45.

1 - Hold-to-run operation: the manoeuvre continues as long as the control

key is kept pressed.

NOTE: All the automatic controls and safety devices are excluded.
The STOP (terminal 33), OPEN (terminal 44) and CLOSE (terminal
45) controls, as well as the limit switches remain active.

0 - Impulse operation: one impulse opens the gate if closed, closes it

if open.

-

Courtesy light [0]

1  - Zone light. Remains active throughout the gate manoeuvring operation.
0 - Courtesy light. Remains active for 90 seconds after last operation.

-

Motor preheating [0]

1 - Function entered.
0 - Function not entered.

-

Rapid closure [0]

1- Closes the gate after photocell disengagement, before waiting for the

end of the TCA set.

0 - Control not entered.

-

Opening Ram blow [0]

1 - Before carrying out the opening manoeuvre, the gate pushes for about

2 seconds on closing. This allows the electric lock to be released
more easily.(not affected by limit switches)

0 - Excludes the ram blow.

IMPORTANT -

 When no adequate mechanical backstops are installed,

do not use this function. It is also to be  absolutely avoided in the
automation of sliding gates.

-

Lock hold [0]

1 - If the motors remain still in a totally open or closed position for over one

hour, they are activated for about 3 seconds in the respective direction.
This operation takes place once every hour.

N.B.:

 This function has the purpose of compensating any oil volume

decrease in the hydraulic motors, due to a temperature drop during
prolonged pauses, for instance at night, or to internal leaks.

IMPORTANT -

 When no adequate mechanical backstops are installed,

do not use this function. It is also to be  absolutely avoided in the
automation of sliding gates.

0 - Excludes the said function.

-

Time count [0]

1 - The control unit calculates the activation time of each motor, based on

the preceding manoeuvres.

0 - The control unit activates the motors at each manoeuvre for the time set.

N.B. 

Always set the operation time to a slightly higher value than needed

to carry out the complete manoeuvre.

-

Light/Alarm [1]

1  - Gate-open alarm output (activated if the gate remains open for twice the

TCA time set).

0 - Stair-light control (the impulse stays on for 1 second).

-

Type of lock [0]

1 - Suction-type lock.
0 - Click lock.

-

Clock / Pedestrian [0] 

 Input for the connection of an external timer

1 - The Clock input is only active in Motor 2, for the pedestrian time set.

A start command given during the clock phase carries out complete gate
opening and closing, resetting the open pedestrian position.

0 - The Clock input acts on both motors.

-

ADMAP photocell [1]

1 - Only on closure. If engaged on closing, it stops and reverses the

direction.

0  - Always active. If engaged on closing or opening, it stops until clear of the

obstacle; in any case moves to opening position.

-

Leaves [0]

1 - Only motor 2 activated (1 leaf).
0 - Both motors are activated (2 leaves).

-

Brake [0]

1 - Electronic braking activated.
0 - Electronic braking excluded.

-

Slow-down [0]

1 - Slow-down during end-of-run phase activated.
0 - Slow-down during end-of-run phase excluded.

Advanced logics - Address 11:
- Ram blow in closing [0]

1 - Before carrying out the closing manoeuvre, the gate pushes for about 2

seconds on opening. This allows the electric lock to be released more
easily.(not affected by limit switches)

IMPORTANT -

 When no adequate mechanical backstops are installed,

do not use this function. It is also to be  absolutely avoided in the
automation of sliding gates.

0 - Excludes the ram blow in closing.

8.3) Self-diagnosis

This is used to check that the control unit operates correctly and the
installation is correctly wired.
The control unit provides the UNIPRO programmer with continuous
information on the state of its inputs (terminals 29, 30, 31,33, 34, 35, 36, 38,
39, 40, 41, 43, 44, 45, 46, 48, 49). Diagnosis is to be carried out with the gate
half open (limit switches not pressed) and the motors stopped.

If the diagnosis is correct, with the motors stopped, also check the complete
opening and closing conditions (limit switch activation check).
Having connected the UNIPRO programmer, enter the CONTROL UNIT /
SELF-DIAGNOSIS menu, press enter and wait for the self-diagnosis
programme which will show the position and comments relating to problems
with inputs, as for example:
-

Stop engaged, input to terminal 33 - 

[errore stop]

 is displayed.

-

Admap engaged, input to terminal 34 - 

[admap error ]

 is displayed.

-

Opening safety devices engaged, input to terminal 35 - 

[safeop error ]

 is

displayed.

-

Closing safety devices engaged, input to terminal 36 - 

[safecl error ] 

is

displayed.

D811270_04

SUPER MA

SUPER MA

CONTROL UNITS

CONTROL UNITS

Содержание SUPER MA

Страница 1: ...SUPER MA D811270 20 09 02 Vers 04 CONTROL UNIT ...

Страница 2: ...fied in this documentation could damage the product and be dangerous The Company declines all responsibility for any consequences resulting from improper use of the product or use which is different from that expected and specified in the present documentation Do not install the product in explosive atmosphere The construction components of this product must comply with the following European Dire...

Страница 3: ...not used leave the jumper connected 37 41 Closing limit switch for motor 2 n c If not used leave the jumper connected 42 43 Pedestrian pushbutton n o Activation takes place on motor 2 moreover if the opening cycle has started not from pedestrian pushbutton the pedestrian control has the same effect as a Start command 42 44 Open Pushbutton n o 42 45 Close Pushbutton n o 42 46 Clock input n o If the...

Страница 4: ... takes place once every hour N B This function has the purpose of compensating any oil volume decrease in the hydraulic motors due to a temperature drop during prolonged pauses for instance at night or to internal leaks IMPORTANT When no adequate mechanical backstops are installed do not use this function It is also to be absolutely avoided in the automation of sliding gates 0 Excludes the said fu...

Страница 5: ...VE ON Preheating trimmer Regulates the preheating activation temperature Can be set from 8 to 8 10 4 SSR5 terminal board connections Fig 4 A Traffic light JP1 SUPER MA board connector JP2 1 phase 2 red light for traffic light 1 3 red light for traffic light 2 4 green light for traffic light 1 5 green light for traffic light 2 B Motor preheating JP3 6 Blinker EBP connection for preheating 7 8 Therm...

Страница 6: ... COM SAFE OP SAFE CL PED OPEN NO NO 45 44 46 CLOSE CLOCK SWO1 SWC1 NC NC NC SWO2 SWC2 COM 53 START I COM CH2 NO 40W max EBP 12 Vdc NC NC NO NO 3 4 5 6 7 8 9 10 11 12 13 1 2 14 15 16 17 18 19 20 21 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 53 52 51 50 49 48 47 230V 110V 230V 110V 230V 110V Fig 1 1 2 3 4 5 6 2 3 JP2 JP1 SSR5 8 7 JP3 1 8 C 8 C 22 23 24 25 26 27 28 29 30 31 D811270_04 SUPER MA SUPE...

Страница 7: ...nside traffic light 2 Feu 2 int rieur Ampel 2 Innen Sem foro 2 interior Sem foro 2 interno 1 2 3 4 5 6 1 2 3 4 5 6 2 3 JP2 JP1 DIP Function 1 Blinking 2 Red light in close position 3 Pre heat DL3 DL1 DL4 DL2 T L 1 T L 2 SSR5 LINE NEUTRE R1 R1 R2 G1 G2 R2 G1 G2 8 7 JP3 1 8 C 8 C T 40W max EBP D811270_04 SUPER MA SUPER MA CONTROL UNITS CONTROL UNITS ...

Страница 8: ... 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 29 34 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 30 35 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP ADMAP SAFE OP D811270_04 SUPER MA SUPER MA CONTROL UNITS CONTROL UNITS ...

Страница 9: ...3 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 35 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 30 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 31 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP SAFECL SAFEOP SAFECL ADMAP D811270_04 SU...

Страница 10: ... 35 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 27 30 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 27 31 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP Fig 15 Fig 16 ADMAP SAFEOP SAFECL D811270_04 SUP...

Страница 11: ...35 1 2 1 2 3 4 5 20 21 19 20 TX4 RX4 32 31 36 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 34 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 29 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP SAFEOP SAFECL ADMAP 1 2 1 2 3 4 5 20 21 19 20 TX4 RX4 32 30 35 1 2 1 2 3 4 5 20 21 19 20 TX5 RX5 32 31 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 29 32 19 20 21 22 23 24...

Отзывы: