background image

436

Gate-open warning light: ................................................... 24Vac 3W max
Blinker: ..............................................................................  230V 40W max
Dimensions: ............................................................................. see figure 1
Fuses: .....................................................................................  see figure 2
(* other voltages available on request)

7) TERMINAL BOARD CONNECTIONS 

(Fig.3)

WARNINGS - 

For wiring

 

and installation operations, refer to the current

standards and good technical principles.
Wires powered at different voltages must be physically separated, or
suitably insulated with at least 1 mm extra insulation. The wires must be
clamped by an extra fastener near the terminals, for example by bands.

WARNING! For connection to the mains, use a multipolar cable with
a minimum of 3x1.5mm

2

 cross section and complying with the

previously mentioned regulations. For example, if the cable is out side
(in the open), it has to be at least equal to H07RN-F, but if it is on the
inside (or outside  but placed in a  plastic cable cannel) it has to be or
at least egual to H05VV-F with section 3x1.5mm

2

.

JP1

1-2

230Vac

±

10%, 50-60Hz power supply (1 phase, 2 neutral).

JP2

3-4

230Vac max 300W for zone/courtesy light.

3-5

230Vac output for blinker light (40W max) and EBP 230V
modelelectric lock.

WARNING!

 If the SSR5 auxiliary board is used to preheat the

motors, move the JP2-5 connection to the JP2-6 terminal of
the SSR5 board.

6-7-8

Motor connection 1 (delayed opening), terminals 6-8 for motor
drive,terminal 7 common.

6-9

Motor capacitor connection 1.

10-11-12

Motor connection 2 (delayed closing), terminals 10-12 for
motor drive, terminal 11 common.

10-13

Motor capacitor connection 2.

N.B. 

If only one motor is used, use motor output 2 and

configure logic “no. Leaves”.

JP7

14-15

Light/alarm output with free n.o. contact, to pilot stair-light
timer or alarm signal for failed gate closure. As a light it
commands an impulse (impulse time 1 s) at the start of the
operation, as an alarm  it lights up if the gate remains open for
twice the TCA setting (inhibited by dwell TCA (automatic
closing time) logic = 0)

16-17

12Vdc electric lock output, with click (3-second impulse), or
suction

19-20

Output 24V AC (1A max) powers accessories and
photoreceivers.

20-21

Output 24V AC powers phototransmitters.

JP8-JP9

22-23-24-25-26-27-28-29-30-31-34-35-36 connections for
several photoreceivers, connect as shown in the diagrams in
fig.7 to fig.18.

JP8

32-33

Lock pushbutton (n.c.). If not used, leave the jumper connected.

21-34,28-29 Input for ADMAP (dangerous movement area accessible to

the public) photocell contact (n.c.). If this is not used, leave the
jumper connected.
With ADMAP Photocell Logic = 0: In case of activation before
opening, movement is prevented; if activation occurs during
opening, movement is stopped and the opening manoeuvre is
resumed after release.
With ADMAP Photocell Logic =1: Photocell excluded on
opening. The opening movement takes place even when an
obstacle is present.
N.B. Regardless of the ADMAP Photocell Logic, photocell
activation during the closing manoeuvre causes stopping and
reopening.

21-35,28-30 If not used, leave the jumper connected. Input for photocelledge

contact on opening SAFE OP(n.c.). In case of activation
during opening, the gate is stopped and partly closed. If not
used, leave the jumper connected

21-35,28-31Input for photocelledge contact on closing SAFE CL (n.c.). In

case of activation during closing, the gate is stopped and partly
reopened. If not used, leave the jumper connected.

37-38

Opening limit switch for motor 1 (n.c.). If not used, leave the
jumper connected.

37-39

Closing limit switch for motor 1 (n.c.). If not used, leave the
jumper connected.

37-40

Opening limit switch for motor 2 (n.c.). If not used, leave the
jumper connected.

37-41

Closing limit switch for motor 2 (n.c.). If not used, leave the

jumper connected.

42-43

Pedestrian pushbutton (n.o.). Activation takes place on motor
2; moreover, if the opening cycle has started (not from
pedestrian pushbutton), the pedestrian control has the same
effect as a Start command.

42-44

Open Pushbutton (n.o.).

42-45

Close Pushbutton (n.o.).

42-46

Clock input (n.o.). If the connected contact is open (n.o.), the
leaves close and get ready for normal operation. If the contact
is closed (n.c.), the leaves open and stay open until the
contact reopens.

JP3

47-48

Internal Start Pushbutton (n.o.). Internal Start command for
traffic light.

47-49

Start Pushbutton (n.o.). Parallel to radio receiver relay (CH1).
External Start command for traffic light.

50-51

Second radio channel output for double-channel receiver
board (n.o.). Activates the internal pedestrian or start command,
or the operation of other devices, through the second radio
channel.

52-53

Antenna input for radio receiver board (52 signal, 53 braid).

JP4

Radio receiver board connector.

JP6

Traffic-light / Preheating SSR5 board connector.

8) PROGRAMMING

The control unit is provided with a microprocessor and supplied with
operation parameters set by the manufacturer. The predefined parameters
can only be changed by means of the UNIPRO programmer.
Before modifying the parameters, carefully read the instructions relating to
the UNIPRO programmer, and proceed as described below.
Connect the UNIPRO programmer to the control unit through the UNIFLAT
accessory (See fig.5). Enter the “CONTROL UNIT” menu and the
“PARAMETERS” submenu, and scroll the display screenfuls using the up/
down arrows, then set the numerical values of the parameters listed below.
For the function logics, refer to the “LOGIC” submenu. Here is a list of the
meanings and values which can be ascribed to each parameter.
The predefined parameters are shown between square brackets [0].

8.1) Configuration
1 - Operation time [60s]

Set the numerical value of the operation time from 5 to 180 seconds.

2 - Pedestrian operation time [6s]

Set the numerical value of the pedestrian opening time from 5 to
90 seconds.

3 - Automatic closing time [40s]

Set the numerical value of the TCA automatic closing time from 3 to
120 seconds.

4 -  Opening delay time for leaf 1 [1s]

Set the opening delay time for motor 1 with respect to motor 2, which can
be adjusted from 0.5 to 6 seconds.

5 - Closing delay time for leaf 2 [5s]

Set the closing delay time for motor 2, which can be adjusted from 0.5
to 30 seconds.

6 - %Motor torque [99%]

Set the numerical torque value from 0 to 99%. Each time it starts, the
motor receives maximum torque for 2 seconds.

7 - Slow-down time [0s]

Set the end-of-run slow-down time from 0 to 10 seconds. NOTE- Only
use this function when limit switches are fitted.

8 - Traffic-light area clearance time [15s]

Set the required clearance time for the area involved in the traffic
governed by traffic light, from 0 to 30 seconds.

9 - %Braking [0%]

Set the required braking percentage from 0 to 99%, compatibly with the
weight of the gate and the existing mechanical stresses.

10 - %Preheating [30%]

Set the percentage value of the current (from 0 to 99%) which can be
made to pass through the motor windings to keep them at the right
temperature (if the 

“motor preheating”

 logic is at 1).

Advanced parameters
11- configuration 4:

% Emergency braking [60%]

Set the emergency braking numerical value from 0 to 99%; emergency
braking is carried out by activating the safety controls available at inputs 33
(Lock), 35 (SAFE OP), and 36 (SAFE CL).

12  - address 5:

%slowdown motor torque [50%]

Set numerically from 0% to 99% the value of motor torque during slowdown
time.

D811270_04

SUPER MA

SUPER MA

CONTROL UNITS

CONTROL UNITS

Содержание SUPER MA

Страница 1: ...SUPER MA D811270 20 09 02 Vers 04 CONTROL UNIT ...

Страница 2: ...fied in this documentation could damage the product and be dangerous The Company declines all responsibility for any consequences resulting from improper use of the product or use which is different from that expected and specified in the present documentation Do not install the product in explosive atmosphere The construction components of this product must comply with the following European Dire...

Страница 3: ...not used leave the jumper connected 37 41 Closing limit switch for motor 2 n c If not used leave the jumper connected 42 43 Pedestrian pushbutton n o Activation takes place on motor 2 moreover if the opening cycle has started not from pedestrian pushbutton the pedestrian control has the same effect as a Start command 42 44 Open Pushbutton n o 42 45 Close Pushbutton n o 42 46 Clock input n o If the...

Страница 4: ... takes place once every hour N B This function has the purpose of compensating any oil volume decrease in the hydraulic motors due to a temperature drop during prolonged pauses for instance at night or to internal leaks IMPORTANT When no adequate mechanical backstops are installed do not use this function It is also to be absolutely avoided in the automation of sliding gates 0 Excludes the said fu...

Страница 5: ...VE ON Preheating trimmer Regulates the preheating activation temperature Can be set from 8 to 8 10 4 SSR5 terminal board connections Fig 4 A Traffic light JP1 SUPER MA board connector JP2 1 phase 2 red light for traffic light 1 3 red light for traffic light 2 4 green light for traffic light 1 5 green light for traffic light 2 B Motor preheating JP3 6 Blinker EBP connection for preheating 7 8 Therm...

Страница 6: ... COM SAFE OP SAFE CL PED OPEN NO NO 45 44 46 CLOSE CLOCK SWO1 SWC1 NC NC NC SWO2 SWC2 COM 53 START I COM CH2 NO 40W max EBP 12 Vdc NC NC NO NO 3 4 5 6 7 8 9 10 11 12 13 1 2 14 15 16 17 18 19 20 21 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 53 52 51 50 49 48 47 230V 110V 230V 110V 230V 110V Fig 1 1 2 3 4 5 6 2 3 JP2 JP1 SSR5 8 7 JP3 1 8 C 8 C 22 23 24 25 26 27 28 29 30 31 D811270_04 SUPER MA SUPE...

Страница 7: ...nside traffic light 2 Feu 2 int rieur Ampel 2 Innen Sem foro 2 interior Sem foro 2 interno 1 2 3 4 5 6 1 2 3 4 5 6 2 3 JP2 JP1 DIP Function 1 Blinking 2 Red light in close position 3 Pre heat DL3 DL1 DL4 DL2 T L 1 T L 2 SSR5 LINE NEUTRE R1 R1 R2 G1 G2 R2 G1 G2 8 7 JP3 1 8 C 8 C T 40W max EBP D811270_04 SUPER MA SUPER MA CONTROL UNITS CONTROL UNITS ...

Страница 8: ... 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 29 34 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 30 35 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP ADMAP SAFE OP D811270_04 SUPER MA SUPER MA CONTROL UNITS CONTROL UNITS ...

Страница 9: ...3 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 35 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 30 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 31 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP SAFECL SAFEOP SAFECL ADMAP D811270_04 SU...

Страница 10: ... 35 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 27 30 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 27 31 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP Fig 15 Fig 16 ADMAP SAFEOP SAFECL D811270_04 SUP...

Страница 11: ...35 1 2 1 2 3 4 5 20 21 19 20 TX4 RX4 32 31 36 1 2 1 2 3 4 5 20 21 19 20 TX1 RX1 32 34 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 29 32 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 JP4 JP9 JP5 STOP SAFEOP SAFECL ADMAP 1 2 1 2 3 4 5 20 21 19 20 TX4 RX4 32 30 35 1 2 1 2 3 4 5 20 21 19 20 TX5 RX5 32 31 36 1 2 1 2 3 4 5 20 21 19 20 TX2 RX2 26 25 1 2 1 2 3 4 5 20 21 19 20 TX3 RX3 29 32 19 20 21 22 23 24...

Отзывы: