LEO-D-MA - Ver. 03 -
15
D811469_03
INSTALLATION MANUAL
ENGLISH
9- Zone (
zone
) [ 0 ]
(UNIPRO
⇒
Advanced parameters
⇒
address 1)
Set the zone number between a minimum value of 0 and a maximum
value of 127. See paragraph 7 on “Serial connection”.
10-Slow-down Distance (
Cm. rall
) [ 000 ]
(UNIPRO
⇒
Advanced parameters
⇒
address 3)
Set the required slow-down distance for opening and closing between 0
cm and 100 cm The 000 cm value does not carry out any slow-down.
NOTE:
If a slow-down distance value other than 000cm is set, after the
first manoeuvre, power failure, reset, or manual gate release, the control
panel carries out a complete manoeuvre at reduced speed, in order to
learn the length of gate stroke.
6.2) Logic Menu (
logic.
)
- TCA (
tca
) [ ON ]
ON Activates automatic closing
OFF Excludes automatic closing
- 3 Steps (
3 step
) [ OFF ]
ON Enables 3-step logic. A start impulse has the following effects:
door closed: ..............................................................................opens
on opening: .............................stops and enters TCA (if configured)
door open: ............................................................................... closes
on closing: ..........................................stops and reverses movement
after stopping: ...........................................................................opens
OFF Disables 3-step logic.
- Opening Impulse lock (
Ibl open
) [ OFF ]
ON The Start impulse has no effect during the opening phase.
OFF The Start impulse becomes effective during the opening phase.
- Impulse lock TCA (
ibl TCA
) [ OFF ]
ON The Start impulse has no effect during the TCA dwell period.
OFF The Start impulse becomes effective during the TCA dwell period.
- Pre alarm (
pre-alarM
) [ OFF ]
ON The blinker comes on about 3 seconds before the motor starts.
OFF The blinker comes on at the same time as the motor starts.
- Hold-to-run (
hold-to-run
) [ OFF ]
ON Hold-to-run operation: the manoeuvre continues as long as the
command key is kept pressed.
OFF Impulse operation: one impulse opens the gate if closed, and closes
it if open.
- Rapid closing (
fast cls
) [ OFF ]
ON Closes the gate after photocell disengagement, before waiting for the
end of the TCA (automatic closing time) set.
OFF Command not entered.
- Photocells on opening (
photc. open
) [ OFF ]
ON: In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF: In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.
- Master/Slave (
Master
) [ OFF ]
(UNIPRO
⇒
Advanced logics
⇒
address 11)
ON The control panel is set as Master in a centralised connection (see
Paragraph 7).
OFF The control panel is set as Slave in a centralised connection (see
Paragraph 7).
- Photocell test (
test phot
) [ OFF ]
(UNIPRO
⇒
Advanced logics
⇒
address 13)
ON Activates photocell check (see fig. 7 to 14)
OFF Deactivates photocell check
- Electric edge test (
test bar
) [ OFF ]
(
UNIPRO
⇒
Advanced logics
⇒
address 14)
ON Activates electric edge check (see fig. 7 to 14)
OFF Deactivates electric edge check
- Gate-open or 2nd radio channel warning light (
SCA 2ch
) [ OFF ]
ON The output between terminals
12
and
13
is configured as Gate-open warn-
ing light, in this case the 2nd radio channel controls pedestrian opening.
OFF The output between terminals
12
and
13
is configured as 2nd radio
channel.
- Fixed code (
fixed code
) [ OFF ]
(UNIPRO
⇒
Advanced logics
⇒
address 13)
ON The receiver is configured for operation in fixed-code mode, see
paragraph on “Radio Transmitter Cloning”.
OFF The receiver is configured for operation in rolling-code mode, see
paragraph on “Radio Transmitter Cloning”.
- Radio transmitter programming (
radio prog
) [ ON ]
(UNIPRO
⇒
Advanced logics
⇒
address 15)
ON This enables transmitter storage via radio:
1 – First press the hidden key (P1) and then the normal key (T1, T2,
T3 or T4) of a transmitter already memorised in standard mode by
means of the radio menu.
2 – Within 10s press the hidden key (P1) and the normal key (T1, T2,
T3 or T4) of a transmitter to be memorised.
The receiver exits the programming mode after 10s, other new trans-
mitters can be entered before the end of this time.
This mode does not require access to the control panel.
OFF This disables transmitter storage via radio.
The transmitters can only be memorised using the appropriate Radio
menu.
6.3) Radio Menu (
radio
)
- Add (
add
)
Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the transmitter number in the
memory location (from 01 to 64).
NOTE:
When using transmitters with two or more channels, the first push-but-
ton which has been stored is associated to the START function. If a second
push-button is stored, it will be associated to the pedestrian function.
- Read (
read
)
Checks one key of a receiver; if stored it displays a message showing the
receiver number in the memory location (from 01 to 64), and the key number
(T1, T2, T3 or T4).
- Delete (
erase 1
)
Removes one single key of a transmitter from the receiver memory; after
deletion it displays a message showing the receiver number in the memory
location (from 01 to 64).
- Eliminate list (
erase 64
)
WARNING!
Completely removes all memorised radio control devices from
the receiver memory.
6.4) Language Menu (
Language
)
Allows you to set the language on the display programmer.
5 languages are available:
- ITALIAN (
TA
)
- FRENCH (
FRA
)
- GERMAN (
DEU
)
- ENGLISH (
ENG
)
- SPANISH (
ESP
)
6.5) MENU DEFAULT (
DEFAULT
)
Restores the preset default values on the control unit. After restoring, a new
autoset operation must be carried out.
6.6) DIAGNOSTICS AND MONITORING
The display on the
LEO-D-MA
panel shows some useful information, both
during normal operation and in the case of malfunctions.
Diagnostics:
In the case of malfunctions, the display shows a message indicating which
device needs to be checked:
STRT = START input activation
STOP = STOP input activation
PHOT = PHOT input activation
FLT = FAULT input activation for checked photocells
SWO
= input activation OPENING LIMIT SWITCH
SWC
= input activation CLOSING LIMIT SWITCH
PED
= input activation PEDESTRIAN
OPEN = OPEN input activation
CLS
= CLOSE input activation
BAR
= input activation SAFETY EDGE
TIME
= TIMER input activation
In the case where an obstacle is found, the
LEO-D-MA
panel stops the door
and activates a reverse manoeuvre; at the same time the display shows the
“BAR” message.
Monitoring
:
During the opening and closing phases, the display shows four digits sepa-
rated by a dot, for example
35.40.
Figures are constantly updated during the manoeuvre and represent the
instant torque reached by motor 1 (
35
) and threshold torque (opening, clos-
ing, slow-down) set in the parameter menu (
40
).
These values allow the torque setting to be corrected.
If the istant torque value reached during the manoeuvres turns out to be consid-
erably close to the threshold value set in the parameter menu, future operation
failures are likely to occur due to wearing or small door deformations.
It is therefore advisable to check the maximum torque reached during some
of the manoeuvres carried out in the course of installation, and if necessary
set a value about 5-10 percent points higher in the parameter menu.