INSTALLER WARNINGS

Anything that is not explicitly provided for in the installation ma-

nual is not allowed. The operator’s proper operation can only be 

guaranteed if the information given is complied with. The Firm shall 

not be answerable for damage caused by failure to comply with the 

instructions featured herein.

While we will not alter the product’s essential features, the Firm reserves 

the right, at any time, to make those changes deemed opportune to 

improve the product from a technical, design or commercial point of 

view, and will not be required to update this publication accordingly.

WARNING! Important safety instructions. Carefully read and comply with 

all the warnings and instructions that come with the product as incorrect 

installation can cause injury to people and animals and damage to property. 

The warnings and instructions give important information regarding safety, 

installation, use and maintenance. Keep hold of instructions so that you can 

attach them to the technical file and keep them handy for future reference.
GENERAL SAFETY

This product has been designed and built solely for the purpose indicated herein. 

Uses other than those indicated herein might cause damage to the product and 

create a hazard.

- The units making up the machine and its installation must meet the requirements

of the following European Directives, where applicable: 2014/30/UE, 2014/35/UE, 

2006/42/UE, 2011/305/UE, 2014/53/UE and later amendments. For all countries 

outside the UE, it is advisable to comply with the standards mentioned, in addi-

tion to any national standards in force, to achieve a good level of safety.

- The Manufacturer of this product (hereinafter referred to as the “Firm”) disclaims 

all responsibility resulting from improper use or any use other than that for

which the product has been designed, as indicated herein, as well as for failure 

to apply Good Practice in the construction of entry systems (doors, gates, etc.) 

and for deformation that could occur during use.

- Installation must be carried out by qualified personnel (professional installer,

according to EN 12635), in compliance with Good Practice and current code.

- Before installing the product, make all structural changes required to produce 

safety gaps and to provide protection from or isolate all crushing, shearing and 

dragging hazard areas and danger zones in general in accordance with the

provisions of standards EN 12604 and 12453 or any local installation standards. 

Check that the existing structure meets the necessary strength and stability

requirements.

- Before commencing installation, check the product for damage.

- The Firm is not responsible for failure to apply Good Practice in the construction 

and maintenance of the doors, gates, etc. to be motorized, or for deformation 

that might occur during use. 

- Make sure the stated temperature range is compatible with the site in which the 

automated system is due to be installed.

- Do not install this product in an explosive atmosphere: the presence of flammable

fumes or gas constitutes a serious safety hazard.

- Disconnect the electricity supply before performing any work on the system.

Also disconnect buffer batteries, if any are connected.

- Before connecting the power supply, make sure the product’s ratings match the 

mains ratings and that a suitable residual current circuit breaker and overcurrent 

protection device have been installed upline from the electrical system. Have

the automated system’s mains power supply fitted with a switch or omnipolar 

thermal-magnetic circuit breaker with a contact separation that provide full

disconnection under overvoltage category III conditions.

- Make sure that upline from the mains power supply there is a residual current 

circuit breaker that trips at no more than 0.03A as well as any other equipment 

required by code.

- Make sure the earth system has been installed correctly: earth all the metal parts 

belonging to the entry system (doors, gates, etc.) and all parts of the system

featuring an earth terminal.

- Installation must be carried out using safety devices and controls that meet

standards EN 12978 and EN 12453.

- Impact forces can be reduced by using deformable edges.

- In the event impact forces exceed the values laid down by the relevant standards, 

apply electro-sensitive or pressure-sensitive devices.

- Apply all safety devices (photocells, safety edges, etc.) required to keep the

area free of impact, crushing, dragging and shearing hazards. Bear in mind the 

standards and directives in force, Good Practice criteria, intended use, the instal-

lation environment, the operating logic of the system and forces generated by 

the automated system.

- Apply all signs required by current code to identify hazardous areas (residual

risks). All installations must be visibly identified in compliance with the provisions 

of standard EN 13241-1.

Once installation is complete, apply a nameplate featuring the door/gate’s data.

- This product cannot be installed on leaves incorporating doors (unless the motor 

can be activated only when the door is closed).

- If the automated system is installed at a height of less than 2.5 m or is accessible, 

the electrical and mechanical parts must be suitably protected.

- For roller shutter automation only

1) The motor’s moving parts must be installed at a height greater than 2.5 m

above the floor or other surface from which they may be reached.

2) The gearmotor must be installed in a segregated and suitably protected space 

so that it cannot be reached without the aid of tools.

- Install any fixed controls in a position where they will not cause a hazard, away 

from moving parts. More specifically, hold-to-run controls must be positioned 

within direct sight of the part being controlled and, unless they are key operated, 

must be installed at a height of at least 1.5 m and in a place where they cannot 

be reached by the public.

- Apply at least one warning light (flashing light) in a visible position, and also

attach a Warning sign to the structure. 

- Attach a label near the operating device, in a permanent fashion, with informa-

tion on how to operate the automated system’s manual release.

- Make sure that, during operation, mechanical risks are avoided or relevant

protective measures taken and, more specifically, that nothing can be banged, 

crushed, caught or cut between the part being operated and surrounding parts.

- Once installation is complete, make sure the motor automation settings are

correct and that the safety and release systems are working properly.

- Only use original spare parts for any maintenance or repair work. The Firm dis-

claims all responsibility for the correct operation and safety of the automated

system if parts from other manufacturers are used.

- Do not make any modifications to the automated system’s components unless 

explicitly authorized by the Firm.

- Instruct the system’s user on what residual risks may be encountered, on the

control systems that have been applied and on how to open the system manu-

ally in an emergency. give the user guide to the end user.

- Dispose of packaging materials (plastic, cardboard, polystyrene, etc.) in accord-

ance with the provisions of the laws in force. Keep nylon bags and polystyrene 

out of reach of children.

WIRING

WARNING! For connection to the mains power supply, use: a multicore cable with 

a cross-sectional area of at least 5x1.5mm

2

 or 4x1.5mm

2

 when dealing with three-

phase power supplies or 3x1.5mm

2

 for single-phase supplies (by way of example, 

type H05RN-F cable can be used with a cross-sectional area of 4x1.5mm

2

). To con-

nect auxiliary equipment, use wires with a cross-sectional area of at least 0.5 mm

2

.

-  Only use pushbuttons with a capacity of 10A-250V or more.

-  Wires must be secured with additional fastening near the terminals (for example,

using cable clamps) in order to keep live parts well separated from safety extra 

low voltage parts.

-  During installation, the power cable must be stripped to allow the earth wire 

to be connected to the relevant terminal, while leaving the live wires as short 

as possible.  The earth wire must be the last to be pulled taut in the event the 

cable’s fastening device comes loose.

WARNING! safety extra low voltage wires must be kept physically separate from 

low voltage wires.

Only qualified personnel (professional installer) should be allowed to access 

live parts.
CHECKING THE AUTOMATED SYSTEM AND MAINTENANCE

Before the automated system is finally put into operation, and during maintenance 

work, perform the following checks meticulously:

- Make sure all components are fastened securely.

- Check starting and stopping operations in the case of manual control.

- Check the logic for normal or personalized operation.

- For sliding gates only: check that the rack and pinion mesh correctly with 2 mm 

of play along the full length of the rack; keep the track the gate slides on clean 

and free of debris at all times.

- For sliding gates and doors only: make sure the gate’s running track is straight 

and horizontal and that the wheels are strong enough to take the weight of the 

gate.

- For cantilever sliding gates only: make sure there is no dipping or swinging

during operation.

- For swing gates only: make sure the leaves’ axis of rotation is perfectly vertical.

-For barriers only: before opening the door, the spring must be decompressed

(vertical boom).

- Check that all safety devices (photocells, safety edges, etc.) are working properly 

and that the anti-crush safety device is set correctly, making sure that the force 

of impact measured at the points provided for by standard EN 12445 is lower

than the value laid down by standard EN 12453.

- Impact forces can be reduced by using deformable edges.

- Make sure that the emergency operation works, where this feature is provided.

- Check opening and closing operations with the control devices applied.

- Check that electrical connections and cabling are intact, making extra sure that 

insulating sheaths and cable glands are undamaged.

- While performing maintenance, clean the photocells’ optics.

- When the automated system is out of service for any length of time, activate the 

emergency release (see “EMERGENCY OPERATION” section) so that the operated 

part is made idle, thus allowing the gate to be opened and closed manually.

- If the power cord is damaged, it must be replaced by the manufacturer or their

technical assistance department or other such qualified person to avoid any risk .

- If “D” type devices are installed (as defined by EN12453), connect in unverified 

mode, foresee mandatory maintenance at least every six months

- The maintenance described above must be repeated at least once yearly or at

shorter intervals where site or installation conditions make this necessary.

WARNING! 

Remember that the drive is designed to make the gate/door easier to use and

will not solve problems as a result of defective or poorly performed installation 

or lack of maintenance

 SCRAPPING

Materials must be disposed of in accordance with the regulations in 

force. Do not throw away your discarded equipment or used batteries 

with household waste. You are responsible for taking all your waste 

electrical and electronic equipment to a suitable recycling centre.

DISMANTLING

If the automated system is being dismantled in order to be reassembled at another 

site, you are required to:

- Cut off the power and disconnect the whole electrical system.

- Remove the actuator from the base it is mounted on.

- Remove all the installation’s components.

- See to the replacement of any components that cannot be removed or happen 

to be damaged.

DECLARATIONS OF CONFORMITY CAN BE FOUND AT http://www.bft-

automation.com/CE

 

INSTRUCTIONS FOR USE AND ASSEMBLY CAN BE FOUND IN THE DOWN-

LOAD SECTION.

D811766_17

10

 - GIOTTO BT A 30-60 S U / GIOTTO BT A 30-60 U  

D812433 00100_06

Содержание GIOTTO BT A 30 U

Страница 1: ... ELECTROMECHANICAL CONTROL DEVICE FOR VEHICULAR BARRIERS A INSTALLATION AND USER S MANUAL GIO GIO T T T T O B O B T A 30 60S U T A 30 60S U GIO GIO T T T T O B O B T A 30 60 U T A 30 60 U Caution Read Warnings inside carefully ...

Страница 2: ...movementsiftherearemechanical faults or loss of balance When using roller shutter openers keep an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly in the event of wear or breakage The breakage or wear of any mechanical parts of the door operated part ...

Страница 3: ...USER S MANUAL MANUAL OPERATION Fig Y 8 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 4: ... least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant ...

Страница 5: ...5 mm 2 3 8 m m 70 mm 340 mm 2 2 0 m m 3m GIOTTO BT A 30S U GIOTTO BT A 30 U 6m GIOTTO BT A 60S U GIOTTO BT A 60 U I 2x0 75mm 2 3x0 75mm 2 B 45 90 5x0 75 mm 2 QR RMM S AL 3x0 75 M F Ft CF T Fr A CS GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U 15 D812433 00100_06 ...

Страница 6: ... V 1 1 2 3 5 4 B1 V 12 35 B2 2 3 With foundation plate embedded in ground With anchor bolts Not supplied Not supplied 16 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 7: ... 45 OK 0 45 3 6 5 Not supplied Assembly of boom Make sure the spring is not under tension See manuals for boom assembly Boom balancing MANUAL AUTOMATIC MANUAL AUTOMATIC MANUAL AUTOMATIC MANUAL AUTOMATIC GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U 17 D812433 00100_06 ...

Страница 8: ...m 5 m B MIN L 4 4 m 2 4 m 2 5 m 2 6 m 2 9 m 2 9 m 3 1 m 3 2 m 3 3 m 3 5 m 3 7 m 2 7 m 2 7 m 2 8 m 3 2 m 3 3 m 3 4 m 3 6 m 3 7 m 3 9 m MAX L 5 m 3 3 m 3 3 m 3 5 m 3 9 m 4 m 4 2 m 4 3 m 4 4 m 4 7 m 5 m 3 5 m 3 6 m 3 7 m 4 2 m 4 3 m 4 5 m 4 7 m 4 9 m 5 m A MIN L 2 4 m 2 5 m 2 5 m 2 9 m 2 9 m 2 7 m 2 7 m 2 8 m MAX L 2 7 m 2 7 m 2 8 m 3 m 3 m 2 9 m 2 9 m 3 m B MIN L 1 9 m 2 m 2 m 2 3 m 2 3 m 2 5 m 2 5 ...

Страница 9: ...OTTO BT A U 120V 2 AT GIOTTO BT A S U 230V 4 AT GIOTTO BT A S U 120V F1 10 26 41 43 50 51 52 60 61 62 21 27 70 10 26 41 43 50 51 52 60 61 62 21 27 70 1 2 Terminal board wiring Optional board connector Display plus programming keys Power supply Motor Safety devices Commands Accessories power supply Limit switch assembly connection Palmtop programmer connector Encoder connector ITALIANO ENGLISH FRAN...

Страница 10: ...2 AUX 0 6 24V 20 21 AUX0 24V MAX 1A 20 21 24V 26 27 26 27 AUX 3 0 AUX 3 2 AUX 3 3 AUX 3 4 AUX 3 5 AUX 3 6 AUX 3 7 AUX 3 8 AUX 3 9 AUX 3 10 AUX 3 12 AUX 3 12 AUX 3 12 AUX 3 1 24 V SCA 26 27 26 27 50 51 Connection To Car park Management System Connection of 1 pair of non tested photocells 20 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 11: ...ed button e hidden button re otes x1 0 10 150 1520 ok Exit Menù Confirm Switch on display Scroll up Scroll down language type 60 30 KEY PRESET DEFAULT ar sr ac sc ind PARAMETERS Automatic closing time s 10 10 10 5 5 5 LOGIC Automatic Closing Time 1 1 0 1 0 0 Step by step movement 1 1 0 1 0 0 Pre alarm 0 0 0 1 1 0 Deadman 0 0 0 0 0 1 Block pulses during opening 1 0 0 1 1 0 Password entry Request wi...

Страница 12: ... acceler accel beschleunigung PRG ok OK P1 P2 70 PRG ok OK P1 P2 P2 3 x 2 x 2 OK default default default default default default freno brake frein bremse PRG ok OK P1 2 default cal ch clos calib cal ferm sch kal cal cie 1 1 Edit the following values until you are happy with boom movement PRELIMINARY ADJUSTMENTS ITALIANO ENGLISH FRANÇAIS DEUTSCH ESPAÑOL PORTUGUÊS ITALIANO ENGLISH FRANÇAIS DEUTSCH E...

Страница 13: ...the spring is not under tension and the boom is not fitted Remove the spring assembly Ret the right hand spring assembly Open in other direction 1 Inversion Open in other direction 0 Inversion ASSEMBLY OF RIGHT BOOM 28 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 14: ...flashing light on the barrier using the screw V1 See the photocell s manuals and post mount s manuals for instructions on installing the photocell and photocell with post mount PLEASE NOTE Remove cover A B or C to install the photocell or post mount PLEASE NOTE Fasten the photocell on the barrier using the screw V2 Installing the flashing light Installing the photocells Installing the photocell wi...

Страница 15: ...2 70 71 72 73 74 75 S1 S2 S3 OK F3 1 25A T 10 11 20 21 26 27 41 42 43 50 51 52 60 61 62 70 71 72 73 74 75 S1 S2 S3 OK 8888 L M S1 S2 S3 OK S1 S2 S3 OK 70 71 COM STOP S1 S2 S3 OK S1 S2 S3 OK 8888 rst8 8888 1 2 3 4 6 5 3s MASTER SLAVE CC1 BAR CC2 BAR ON OFF EXPANSION BOARD Universal palmtop programmer address 0 serial mode 3 address 0 serial mode 2 TO CONNECT SEVERAL PHOTOCELLS REFER TO FIG P 30 GIO...

Страница 16: ...5 S 6 S 70 73 72 70 1 S 2 S 4 S 5 S 3 S 70 73 6 S 70 72 8 2Kohm 5 SAFETY EDGE SAFETY EDGE 1 SAFE1 6 3 2 5 4 SAFE 2 1 2 1 2 3 4 5 51 TX1 RX1 Bar 1 1 2 3 4 5 6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX4 RX4 Bar 1 1 2 3 4 5 ...

Страница 17: ...gic settings ER02 Safety edge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Checkphotocellconnectionand orparameter logicsetting ER04 Closing photocell test failed Checkphotocellconnectionand orparameter logicsetting ER05 Safety edge test on slave motor failed opposite leaves connection Check safety edge connection and or parameter logic settings...

Страница 18: ...ated in Fig A WARNING before opening the door the spring must be unloaded vertical boom The door of the box must be facing towards the inside oftheproperty Whenyoustandinthemiddleofthepassageway facing outwards if the box is on your left the barrier is left hand fitted if the box is on your right the barrier is right hand fitted The actuator is always supplied for left hand side fitting 6 Right ha...

Страница 19: ...ferences 42 RIFC Reference closing RIFC N C 43 RIFO Reference opening RIFO N C Accessories power supply 50 24V Accessories power supply output 51 24V 52 24 Vsafe Tested safety device power supply output photocell transmitter and safety edge transmitter Output active only during operating cycle Commands 60 Common IC 1 and IC 2 inputs common 61 IC 1 Configurable command input 1 N O Default OPEN STAR...

Страница 20: ...beam is broken photocell operation is disabled during opening During closing movement is reversed immediately SAFE logic 6 Input configured as Bar safety edge non tested fig N ref 3 Enables connection of devices not equipped with supplementary test contacts The command reverses movement for 2 sec If not used leave jumper inserted SAFE logic 7 Input configured as Bar tested safety edge fig N ref 4 ...

Страница 21: ...ontactisthenopenedbytheStopcommandorbytheclosinglimitswitch open calib Specialpar 1 0 100 75 Opening value calibration Opening value calibration Set the reference value from 0 0 to 100 0 for the required opening position see Paragraph Limit Switch Setting clos calib Specialpar 6 0 100 25 Closing value calibration Closing value calibration Set the reference value from 0 0 to 100 0 for the required ...

Страница 22: ... devices are not enabled IBL OPEN Block pulses during opening 1 0 Pulse from inputs configured as Start E Start I has effect during opening 1 Pulse from inputs configured as Start E Start I has no effect during opening IBL TCA Block pulses during TCA 0 0 Pulse from inputs configured as Start E Start I has effect during TCA pause 1 Pulse from inputs configured as Start E Start I has no effect durin...

Страница 23: ...he board s parameters can be edited via the U link network 1 A You are prompted to enter the password to access the programming menus The default password is 1234 No change in behaviour of functions B C D E from 0 logic setting 2 A You are prompted to enter the password to access the programming menus The default password is 1234 B Wireless memorizing of transmitters is disabled C Wirelessautomati...

Страница 24: ...command 6 Input configured as Timer Pedestrian command 7 Input configured as Phot photocell safety 8 Input configured as Phot op safety photocell active during opening only 9 Input configured as Phot cl safety photocell active during closing only 10 Input configured as Bar safety safety edge EXPO1 Configuration of EXPO2 output on input output expansion board 4 5 11 0 Output configured as 2nd Radio...

Страница 25: ...O2 in de uitbreidingskaart ingangen uitgangen 6 7 11 6 Uitgang geconfigureerd als Knipperlicht 7 Uitgang geconfigureerd als Klikslot 8 Uitgang geconfigureerd als Magneetslot 9 Uitgang geconfigureerd als Onderhoud 10 Uitgang geconfigureerd als Zwaailicht en Onderhoud 11 Uitgang geconfigureerd als Beheer stoplicht met TLB kaart 12 uitgang geconfigureerd als status barrière TRAFFIC LIGHT PREFLASHING ...

Отзывы:

Похожие инструкции для GIOTTO BT A 30 U