INSTALLATION MANUAL

WARNING:

 The electrical connections must be carried out workmanlike 

by qualified experienced personnel, in conformity with all the current 

standards and with the use of appropriate materials. 

Lay out the electrical installation with reference to the current electrical 

standards. 

Keep the mains supply connections clearly separated from the service 

connections. 

In the initial section of the electrical installation, fit a circuit breaker with 

a contact opening distance equal to or greater than 3,5 mm, provided 

with magnetothermal protection and a differential switch having ad-

equate capacity for the appliance consumption. For the wiring, only 

use cables conforming to the harmonised or national standards, having 

a cross section corresponding to the initial protection, the appliance 

consumption and the installation conditions, for example a 3x1.5 sq 

mm (H 05 VV-F) cable. 

Terminal

Definition

Description

Po

w

er supply

L

LINE

Single-phase power supply 

220-230V ~50/60 Hz*

N

NEUTRAL

JP31

TRANSF PRIM

Transformer primary winding connection, 220-230V 

~

.

JP32

JP13

TRANSF SEC

Board power supply:   

24V~ Transformer secondary winding 

M

ot

or

10

 MOT +

Connection motor 1

11

MOT -

Au

x

20

AUX 0 - 24V POWERED CONTACT 

(N.O.)  (MAX. 1A)

AUX 0 configurable output - Default setting FLASHING LIGHT. 

2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ 

GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND 

MAINTENANCE

BARRIER STATUS OUTPUT. Refer to “AUX output configuration” table.

21

26

AUX 3 - FREE CONTACT (N.O.)  

(Max. 24V 1A)

AUX 3 configurable output - Default setting 2ND RADIO CHANNEL Output. 

2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ 

GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND 

MAINTENANCE/ BARRIER STATUS OUTPUT. Refer to “AUX output configuration” table.

27

Limit 

swit

ches

41

+ REF RIF

Common references

42

RIFC

Reference closing RIFC (N.C.)

43

RIFO

Reference opening RIFO (N.C.)

A

cc

essories po

w

er 

supply

50

24V-

Accessories power supply output.

51

24V+

52

24 Vsafe+

Tested safety device power supply output (photocell transmitter and safety edge transmitter). 

Output active only during operating cycle.

Commands

60

Common

IC 1 and IC 2 inputs common

61

IC 1

Configurable command input 1 (N.O.) - Default OPEN. 

START E / START I / OPEN / CLOSE / TIMER / OPEN

Refer to the “Command input configuration” table.

62

IC 2

Configurable command input 2 (N.O.) - Default CLOSE. 

START E / START I / OPEN / CLOSE / TIMER / OPEN 

Refer to the “Command input configuration” table.

Saf

et

y de

vic

es

70

Common

STOP, SAFE 1 and SAFE 2 inputs common

71

STOP 

The command stops movement. (N.C.) 

If not used, leave jumper inserted.

72

SAFE 1

Configurable safety input 1 (N.C.) - Default PHOT. 

PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2 

Refer to the “Safety input configuration” table.

73

FAULT 1 

Test input for safety devices connected to SAFE 1.

74

SAFE 2

Configurable safety input 2 (N.C.) - Default BAR. 

PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2 

Refer to the “Safety input configuration” table.

75

FAULT 2 

Test input for safety devices connected to SAFE 2.

A

nt

enna

Y

ANTENNA

Antenna input. 

Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies close 

to the antenna can interfere with radio reception. If the transmitter’s range is limited, move the antenna to a more 

suitable position.

#

SHIELD

AUX output configuration

Aux logic= 0 - 2ND RADIO CHANNEL output.  

Contact stays closed for 1s when 2nd radio channel is activated. 
Aux logic= 1 - SCA GATE OPEN LIGHToutput.  

Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIGHT command output.  

Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIGHT command output.   

Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIGHT output.   

Contact stays closed for 1 second at start of operation. 

42

 - GIOTTO BT A 30-60 S U / GIOTTO BT A 30-60 U  

D812433 00100_06

Содержание GIOTTO BT A 30 U

Страница 1: ... ELECTROMECHANICAL CONTROL DEVICE FOR VEHICULAR BARRIERS A INSTALLATION AND USER S MANUAL GIO GIO T T T T O B O B T A 30 60S U T A 30 60S U GIO GIO T T T T O B O B T A 30 60 U T A 30 60 U Caution Read Warnings inside carefully ...

Страница 2: ...movementsiftherearemechanical faults or loss of balance When using roller shutter openers keep an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly in the event of wear or breakage The breakage or wear of any mechanical parts of the door operated part ...

Страница 3: ...USER S MANUAL MANUAL OPERATION Fig Y 8 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 4: ... least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant ...

Страница 5: ...5 mm 2 3 8 m m 70 mm 340 mm 2 2 0 m m 3m GIOTTO BT A 30S U GIOTTO BT A 30 U 6m GIOTTO BT A 60S U GIOTTO BT A 60 U I 2x0 75mm 2 3x0 75mm 2 B 45 90 5x0 75 mm 2 QR RMM S AL 3x0 75 M F Ft CF T Fr A CS GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U 15 D812433 00100_06 ...

Страница 6: ... V 1 1 2 3 5 4 B1 V 12 35 B2 2 3 With foundation plate embedded in ground With anchor bolts Not supplied Not supplied 16 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 7: ... 45 OK 0 45 3 6 5 Not supplied Assembly of boom Make sure the spring is not under tension See manuals for boom assembly Boom balancing MANUAL AUTOMATIC MANUAL AUTOMATIC MANUAL AUTOMATIC MANUAL AUTOMATIC GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U 17 D812433 00100_06 ...

Страница 8: ...m 5 m B MIN L 4 4 m 2 4 m 2 5 m 2 6 m 2 9 m 2 9 m 3 1 m 3 2 m 3 3 m 3 5 m 3 7 m 2 7 m 2 7 m 2 8 m 3 2 m 3 3 m 3 4 m 3 6 m 3 7 m 3 9 m MAX L 5 m 3 3 m 3 3 m 3 5 m 3 9 m 4 m 4 2 m 4 3 m 4 4 m 4 7 m 5 m 3 5 m 3 6 m 3 7 m 4 2 m 4 3 m 4 5 m 4 7 m 4 9 m 5 m A MIN L 2 4 m 2 5 m 2 5 m 2 9 m 2 9 m 2 7 m 2 7 m 2 8 m MAX L 2 7 m 2 7 m 2 8 m 3 m 3 m 2 9 m 2 9 m 3 m B MIN L 1 9 m 2 m 2 m 2 3 m 2 3 m 2 5 m 2 5 ...

Страница 9: ...OTTO BT A U 120V 2 AT GIOTTO BT A S U 230V 4 AT GIOTTO BT A S U 120V F1 10 26 41 43 50 51 52 60 61 62 21 27 70 10 26 41 43 50 51 52 60 61 62 21 27 70 1 2 Terminal board wiring Optional board connector Display plus programming keys Power supply Motor Safety devices Commands Accessories power supply Limit switch assembly connection Palmtop programmer connector Encoder connector ITALIANO ENGLISH FRAN...

Страница 10: ...2 AUX 0 6 24V 20 21 AUX0 24V MAX 1A 20 21 24V 26 27 26 27 AUX 3 0 AUX 3 2 AUX 3 3 AUX 3 4 AUX 3 5 AUX 3 6 AUX 3 7 AUX 3 8 AUX 3 9 AUX 3 10 AUX 3 12 AUX 3 12 AUX 3 12 AUX 3 1 24 V SCA 26 27 26 27 50 51 Connection To Car park Management System Connection of 1 pair of non tested photocells 20 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 11: ...ed button e hidden button re otes x1 0 10 150 1520 ok Exit Menù Confirm Switch on display Scroll up Scroll down language type 60 30 KEY PRESET DEFAULT ar sr ac sc ind PARAMETERS Automatic closing time s 10 10 10 5 5 5 LOGIC Automatic Closing Time 1 1 0 1 0 0 Step by step movement 1 1 0 1 0 0 Pre alarm 0 0 0 1 1 0 Deadman 0 0 0 0 0 1 Block pulses during opening 1 0 0 1 1 0 Password entry Request wi...

Страница 12: ... acceler accel beschleunigung PRG ok OK P1 P2 70 PRG ok OK P1 P2 P2 3 x 2 x 2 OK default default default default default default freno brake frein bremse PRG ok OK P1 2 default cal ch clos calib cal ferm sch kal cal cie 1 1 Edit the following values until you are happy with boom movement PRELIMINARY ADJUSTMENTS ITALIANO ENGLISH FRANÇAIS DEUTSCH ESPAÑOL PORTUGUÊS ITALIANO ENGLISH FRANÇAIS DEUTSCH E...

Страница 13: ...the spring is not under tension and the boom is not fitted Remove the spring assembly Ret the right hand spring assembly Open in other direction 1 Inversion Open in other direction 0 Inversion ASSEMBLY OF RIGHT BOOM 28 GIOTTO BT A 30 60 S U GIOTTO BT A 30 60 U D812433 00100_06 ...

Страница 14: ...flashing light on the barrier using the screw V1 See the photocell s manuals and post mount s manuals for instructions on installing the photocell and photocell with post mount PLEASE NOTE Remove cover A B or C to install the photocell or post mount PLEASE NOTE Fasten the photocell on the barrier using the screw V2 Installing the flashing light Installing the photocells Installing the photocell wi...

Страница 15: ...2 70 71 72 73 74 75 S1 S2 S3 OK F3 1 25A T 10 11 20 21 26 27 41 42 43 50 51 52 60 61 62 70 71 72 73 74 75 S1 S2 S3 OK 8888 L M S1 S2 S3 OK S1 S2 S3 OK 70 71 COM STOP S1 S2 S3 OK S1 S2 S3 OK 8888 rst8 8888 1 2 3 4 6 5 3s MASTER SLAVE CC1 BAR CC2 BAR ON OFF EXPANSION BOARD Universal palmtop programmer address 0 serial mode 3 address 0 serial mode 2 TO CONNECT SEVERAL PHOTOCELLS REFER TO FIG P 30 GIO...

Страница 16: ...5 S 6 S 70 73 72 70 1 S 2 S 4 S 5 S 3 S 70 73 6 S 70 72 8 2Kohm 5 SAFETY EDGE SAFETY EDGE 1 SAFE1 6 3 2 5 4 SAFE 2 1 2 1 2 3 4 5 51 TX1 RX1 Bar 1 1 2 3 4 5 6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX4 RX4 Bar 1 1 2 3 4 5 ...

Страница 17: ...gic settings ER02 Safety edge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Checkphotocellconnectionand orparameter logicsetting ER04 Closing photocell test failed Checkphotocellconnectionand orparameter logicsetting ER05 Safety edge test on slave motor failed opposite leaves connection Check safety edge connection and or parameter logic settings...

Страница 18: ...ated in Fig A WARNING before opening the door the spring must be unloaded vertical boom The door of the box must be facing towards the inside oftheproperty Whenyoustandinthemiddleofthepassageway facing outwards if the box is on your left the barrier is left hand fitted if the box is on your right the barrier is right hand fitted The actuator is always supplied for left hand side fitting 6 Right ha...

Страница 19: ...ferences 42 RIFC Reference closing RIFC N C 43 RIFO Reference opening RIFO N C Accessories power supply 50 24V Accessories power supply output 51 24V 52 24 Vsafe Tested safety device power supply output photocell transmitter and safety edge transmitter Output active only during operating cycle Commands 60 Common IC 1 and IC 2 inputs common 61 IC 1 Configurable command input 1 N O Default OPEN STAR...

Страница 20: ...beam is broken photocell operation is disabled during opening During closing movement is reversed immediately SAFE logic 6 Input configured as Bar safety edge non tested fig N ref 3 Enables connection of devices not equipped with supplementary test contacts The command reverses movement for 2 sec If not used leave jumper inserted SAFE logic 7 Input configured as Bar tested safety edge fig N ref 4 ...

Страница 21: ...ontactisthenopenedbytheStopcommandorbytheclosinglimitswitch open calib Specialpar 1 0 100 75 Opening value calibration Opening value calibration Set the reference value from 0 0 to 100 0 for the required opening position see Paragraph Limit Switch Setting clos calib Specialpar 6 0 100 25 Closing value calibration Closing value calibration Set the reference value from 0 0 to 100 0 for the required ...

Страница 22: ... devices are not enabled IBL OPEN Block pulses during opening 1 0 Pulse from inputs configured as Start E Start I has effect during opening 1 Pulse from inputs configured as Start E Start I has no effect during opening IBL TCA Block pulses during TCA 0 0 Pulse from inputs configured as Start E Start I has effect during TCA pause 1 Pulse from inputs configured as Start E Start I has no effect durin...

Страница 23: ...he board s parameters can be edited via the U link network 1 A You are prompted to enter the password to access the programming menus The default password is 1234 No change in behaviour of functions B C D E from 0 logic setting 2 A You are prompted to enter the password to access the programming menus The default password is 1234 B Wireless memorizing of transmitters is disabled C Wirelessautomati...

Страница 24: ...command 6 Input configured as Timer Pedestrian command 7 Input configured as Phot photocell safety 8 Input configured as Phot op safety photocell active during opening only 9 Input configured as Phot cl safety photocell active during closing only 10 Input configured as Bar safety safety edge EXPO1 Configuration of EXPO2 output on input output expansion board 4 5 11 0 Output configured as 2nd Radio...

Страница 25: ...O2 in de uitbreidingskaart ingangen uitgangen 6 7 11 6 Uitgang geconfigureerd als Knipperlicht 7 Uitgang geconfigureerd als Klikslot 8 Uitgang geconfigureerd als Magneetslot 9 Uitgang geconfigureerd als Onderhoud 10 Uitgang geconfigureerd als Zwaailicht en Onderhoud 11 Uitgang geconfigureerd als Beheer stoplicht met TLB kaart 12 uitgang geconfigureerd als status barrière TRAFFIC LIGHT PREFLASHING ...

Отзывы: