INSTALLATION MANUAL
WARNING:
The electrical connections must be carried out workmanlike
by qualified experienced personnel, in conformity with all the current
standards and with the use of appropriate materials.
Lay out the electrical installation with reference to the current electrical
standards.
Keep the mains supply connections clearly separated from the service
connections.
In the initial section of the electrical installation, fit a circuit breaker with
a contact opening distance equal to or greater than 3,5 mm, provided
with magnetothermal protection and a differential switch having ad-
equate capacity for the appliance consumption. For the wiring, only
use cables conforming to the harmonised or national standards, having
a cross section corresponding to the initial protection, the appliance
consumption and the installation conditions, for example a 3x1.5 sq
mm (H 05 VV-F) cable.
Terminal
Definition
Description
Po
w
er supply
L
LINE
Single-phase power supply
220-230V ~50/60 Hz*
N
NEUTRAL
JP31
TRANSF PRIM
Transformer primary winding connection, 220-230V
~
.
JP32
JP13
TRANSF SEC
Board power supply:
24V~ Transformer secondary winding
M
ot
or
10
MOT +
Connection motor 1
11
MOT -
Au
x
20
AUX 0 - 24V POWERED CONTACT
(N.O.) (MAX. 1A)
AUX 0 configurable output - Default setting FLASHING LIGHT.
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND
MAINTENANCE
/
BARRIER STATUS OUTPUT. Refer to “AUX output configuration” table.
21
26
AUX 3 - FREE CONTACT (N.O.)
(Max. 24V 1A)
AUX 3 configurable output - Default setting 2ND RADIO CHANNEL Output.
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND
MAINTENANCE/ BARRIER STATUS OUTPUT. Refer to “AUX output configuration” table.
27
Limit
swit
ches
41
+ REF RIF
Common references
42
RIFC
Reference closing RIFC (N.C.)
43
RIFO
Reference opening RIFO (N.C.)
A
cc
essories po
w
er
supply
50
24V-
Accessories power supply output.
51
24V+
52
24 Vsafe+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
Output active only during operating cycle.
Commands
60
Common
IC 1 and IC 2 inputs common
61
IC 1
Configurable command input 1 (N.O.) - Default OPEN.
START E / START I / OPEN / CLOSE / TIMER / OPEN
Refer to the “Command input configuration” table.
62
IC 2
Configurable command input 2 (N.O.) - Default CLOSE.
START E / START I / OPEN / CLOSE / TIMER / OPEN
Refer to the “Command input configuration” table.
Saf
et
y de
vic
es
70
Common
STOP, SAFE 1 and SAFE 2 inputs common
71
STOP
The command stops movement. (N.C.)
If not used, leave jumper inserted.
72
SAFE 1
Configurable safety input 1 (N.C.) - Default PHOT.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2
Refer to the “Safety input configuration” table.
73
FAULT 1
Test input for safety devices connected to SAFE 1.
74
SAFE 2
Configurable safety input 2 (N.C.) - Default BAR.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2
Refer to the “Safety input configuration” table.
75
FAULT 2
Test input for safety devices connected to SAFE 2.
A
nt
enna
Y
ANTENNA
Antenna input.
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies close
to the antenna can interfere with radio reception. If the transmitter’s range is limited, move the antenna to a more
suitable position.
#
SHIELD
AUX output configuration
Aux logic= 0 - 2ND RADIO CHANNEL output.
Contact stays closed for 1s when 2nd radio channel is activated.
Aux logic= 1 - SCA GATE OPEN LIGHToutput.
Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIGHT command output.
Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIGHT command output.
Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIGHT output.
Contact stays closed for 1 second at start of operation.