1.7 FITTING TO PRE-FABRICATED TWIN WALL METAL FLUE BOXES
The appliance may be fitted to twin wall metal flue boxes conforming to the
constructional requirements of BS 715 / BS EN 1856-2. The box must have a
minimum flue diameter of 125mm internal and minimum internal dimensions of
300mm deep by 685mm high by 470mm wide. There are no maximum
dimensional requirements for the box. The top face of the box must be insulated
with a minimum thickness of 50mm of non-combustible mineral wool insulation or
similar material. The flue box must stand on a non-combustible base of minimum
thickness 12mm.
1.8
HEARTHS
This appliance must only be installed on to a concrete or non-combustible hearth.
The hearth material must be a minimum thickness of 13mm with the top surface at
least 50mm above the floor. The hearth must be fitted symmetrically about the fire
opening and have a minimum width of 770mm and a minimum projection of
300mm forwards from the fire opening.
1.9
SPILLAGE MONITORING SYSTEM
This appliance is fitted with an atmosphere sensing spillage monitoring system in
the form of an oxygen sensing pilot. This is designed to shut the fire off in the
event of a partial or complete blockage of the flue causing a build up of
combustion products in the room in which the fire is operated.
The following are
important warnings relating to this spillage monitoring system
:-
1) The spillage monitoring system must not be adjusted by the installer.
2) The spillage monitoring system must not be put out of operation.
3) When the spillage monitoring system is exchanged only a complete original
manufacturers part may be fitted. It is not possible to replace individual parts on
the pilot system on this appliance, only a complete pilot assembly (including the
thermocouple) may be fitted.
8