Description
5-4
5.4
6 DIP switch
5.4.1
Current output range
DIP switch1 selects whether the current outputs of the
converter box 6012 have a range of 0 ... 20 mA or 4 ... 20
mA.
Only when the spanis set to 4 ... 20mA, a line break with
the software CFC-NET can be detected!
5.4.2
Current-Relay-Function (CRF)
DIP switch 2 activates the Current-Relay-Function of con-
verter module 6012. Here the generated current output is
only active if the flame relay is switched on.
The switch affects the output current for the frequency
and the DC-raw signal only as these were generated by
the converter box 6012. The current relay function for the
amplitude signal is set via the software CFC Com1at com-
pact flame controller CFC4000!
5.4.3
Channel
2 (Ch.2)
DIP switch 3 selects manually the second parameter set
of the CFC4000. Status LED (9) indicates when parame-
ter set 2 is active.
By default, the parameterset 1 is active. Besides the man-
ual selection with DIP-switch 3 a remote selection of pa-
rameter set 2 can be done by providing 24 V DC at the
terminal 22.
5.4.4
BUS termination
DIP switch 4 activates the interal BUS termination.
In a network the last device in a RS485 bus must be ter-
minated only.
Содержание 5012 SD
Страница 2: ......
Страница 11: ...General aspects 1 7 1 8 Declaration of conformity ...
Страница 20: ...Safety 2 8 ...
Страница 28: ...Transport Installation and Connection 4 4 4 6 2 Network Configuration ...
Страница 38: ...Description 5 8 ...
Страница 40: ...Commisioning 6 2 ...
Страница 42: ...Care and Maintenance 7 2 ...
Страница 44: ...Failures 8 2 ...
Страница 46: ...Order data 9 2 ...
Страница 47: ...Order data 9 3 ...
Страница 48: ...Order data 9 4 BFI Automation 2019 ...