Better Water LLC; rev. May 2020
Page 36 of 78
1232 RO Operator Manual
PROCEDURE
1.
Place a warning placard stating “
DO NOT USE
– CLEANING/DISINFECTING IN
PROGRESS
”. End users should be notified as well that this procedures in in progress.
2.
Open the
Control Box
and flip the
DIRECT-STBY-TANK Switch
to
DIRECT
.
3.
Prepare the
Tank
.
a.
Open the
Tank’s Bottom Valve
so it can be rinsed.
b.
Connect
Hose#1
from the
Reservoir’s 3-Way Valve
to the
Tank’s Top
Right Port
.
c.
Turn the
Reservoir’s 3-Way Valve
so it flows to this hose.
d.
Start the
RO
in normal Operate Mode and rinse the Tank with RO product water.
-
Turn the
OPER-DISINFECT-OFF
Switch
to
OPER
-
Turn the
OPER-DISINFECT Keyed Switch
to
OPER
-
Turn the
OPER-FLUSH
Switch
to
OPER
- Press the
ALARM RESET
Button
if the alarm sounds.
* Once the RO is in good water quality it will start to fill the Tank.
e.
After rinsing the
Tank
, close the
Tank’s Bottom Valve
.
f.
Fill the
Tank
with RO product water.
-
IF CLEANING
, fill
Tank
with 15 gallons (
approximately14 inches.
-
IF
DISINFECTING
, fill
Tank
with 20 gallons (
approximately 18 inches
).
- Once filled with the desired amount turn the RO OFF by turning the
OPER-DISINFECT-OFF
Switch
to
OFF
.
4.
Prepare
RO
and
Hoses
.
a.
Disconnect the
RO’s Drain Hose
from the
RO’s “To Drain” Connection
and connect
Hose#2
from that connection to the
Tank’s Top Left Port
.
b.
Connect
Hose#3
from the
RO Pump’s Clean/Disinfect Ball Valve
to the
Tank
’s Bottom
Valve
.
5.
Prime
Hose#3
a.
Loosen the Parker connection at the
RO Pump’s Clean/Disinfect Ball Valve
.
b.
Open the
Tank’s Bottom Valve
, prime the hose, and then tighten the loosened Parker
connection.
c.
Open the
RO Pump’s Clean/Disinfect Ball Valve
.
-
NOTE:
If this hose hasn’t been properly primed the pump will air lock and could cause damage
to the pump.
6.
Start
RO
in Disinfect Mode and begin circulation…
-
Turn the
OPER-DISINFECT-OFF Switch
to
DISINFECT
-
Turn the
OPER-DISINFECT Keyed Switch
to
DISINFECT
-
Turn the
OPER-FLUSH
switch to
OPER
*
Verify flow by looking at the Product and Reject Flow-Meters,
and visually see if water flowing back in to the Tank otherwise
re-prime Hose#3. Also check for leaks and correct before
proceeding.
7.
IF CLEANING
… before beginning cleaning, take a baseline pH reading from the product water
returning into the
Tank
to compare to tests to follow.
8.
Add chemicals for procedure…
-
IF DISINFECTING
, add 750 mL of either Renalin or MinnCare to the
Tank
.
Содержание 1232 RO
Страница 1: ...REA 2390 1232 RO Operator Manual Better Water LLC rev May 2020 ...
Страница 8: ...Better Water LLC rev May 2020 Page 4 of 78 1232 RO Operator Manual ...
Страница 15: ...Better Water LLC rev May 2020 Page 11 of 78 1232 RO Operator Manual DEVICE INFORMATION ...
Страница 47: ...Better Water LLC rev May 2020 Page 43 of 78 1232 RO Operator Manual SYSTEM MAINTENANCE ...
Страница 71: ...Better Water LLC rev May 2020 Page 67 of 78 1232 RO Operator Manual APPENDIX B SAMPLE CHECK LISTS ...
Страница 74: ...Better Water LLC rev May 2020 Page 70 of 78 1232 RO Operator Manual ...
Страница 75: ...Better Water LLC rev May 2020 Page 71 of 78 1232 RO Operator Manual APPENDIX C TECHNICAL SERVICE BULLETINS ...
Страница 79: ...Better Water LLC rev May 2020 Page 75 of 78 1232 RO Operator Manual APPENDIX D PRE SHIP TEST DATA ...
Страница 80: ...Better Water LLC rev May 2020 Page 76 of 78 1232 RO Operator Manual ...
Страница 82: ...Better Water LLC rev May 2020 Page 78 of 78 1232 RO Operator Manual ...