LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516
Page 44 of 84
Revision E (Dec 2013)
~F:UdpIP
Ethernet UDP Destination Address
~F:UdpIP<CR>
Read Setting
Response Format:
ABEtherNet UdpIP <IP><CR>
~F:UdpIP=<IP><CR>
Set Value
Factory Default: 192.168.1.100
Where
<IP>
is the remote IP address to which UDP data messages will be sent.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the UDP Destionation Address to 192.168.10.111, send the
command:
~F:UdpIP=192.168.1.111<CR>
~F: .F
Ethernet Configuration Settings
~F<CR>
Read All Settings (with labels)
Example Response Format:
ABEtherNet
IP 192.168.1.111
Netmask 255.255.255.0
Gateway 0.0.0.0
UdpPort 4750
TcpPort 4751
UdpIP 192.168.1.100
Set All Values
~F<IP>,<NM>,<GW>,<UP>,<TP>,<UI><CR>
.F<CR>
Read All Settings (without labels)