Best Power Unity/I UT3K Скачать руководство пользователя страница 2

UTY 618

2

RESTRICTED

November 1995

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS!

This publication contains important instructions that you should follow during battery replacement.

CAUTION

Full voltage and current are always present at the battery terminals.

The batteries used in this system can produce dangerous voltages, extremely high currents, and a risk
of electric shock. They may cause severe injury if the terminals are shorted together or to ground
(earth). You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation. Do not touch uninsulated battery terminals.

A qualified technician or electrician who is familiar with battery systems and required precautions must
service the batteries. Any battery used with this UPS shall comply with the applicable requirements for
batteries in the standard for emergency lighting and power equipment, UL 924. Batteries must be
replaced with BEST battery number BAT-XXXX or equivalent. The installation must conform to
national and local codes.

Keep unauthorized personnel away from batteries. 

The technician or electrician must take these precautions:

1.

Wear protective clothing and eye wear. Batteries contain caustic acids and toxic materials and can
rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and
jewelry. Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.

2.

Tools must have insulated handles and must be insulated so that they will not short battery
terminals. Do not allow a tool to short a battery terminal to another battery terminal or to the
cabinet at any time. Do not lay tools or metal parts on top of the batteries, and do not lay them
where they could fall onto the batteries or into the cabinet.

3.

When connecting cables, never allow a cable to short across a battery’s terminals, the string of
batteries, or to the cabinet.

4.

Align the cables on the battery terminals so that the cable lug will not contact any part of the
cabinet even if the battery is moved. Keep the cable away from any sharp metal edges.

5.

Install the battery cables so they cannot be pinched by the battery cabinet door or UPS covers.

Содержание Unity/I UT3K

Страница 1: ...while performing this procedure call BEST Power Worldwide Service at 1 608 565 2100 or 1 800 356 5737 U S A and Canada or call your local BEST office Replace batteries with the same series and type b...

Страница 2: ...alent The installation must conform to national and local codes Keep unauthorized personnel away from batteries The technician or electrician must take these precautions 1 Wear protective clothing and...

Страница 3: ...al is inadvertently grounded remove the source of the ground Contacting any part of a grounded battery can cause a risk of electric shock An electric shock will be less likely if you disconnect the gr...

Страница 4: ...ntenance mode if necessary Battery maintenance mode allows a qualified technician to service the batteries without powering down the UPS or the load equipment Use the two questions below to help deter...

Страница 5: ...ets shut off the DC disconnect switches on all of the cabinets 101 5 Skip Section 102 Go to Section 200 on page 8 Section 102 Using Battery Maintenance Mode Battery maintenance mode allows a qualified...

Страница 6: ...ions on viewing the system log Look for the system event code in inverter 102 2 Access parameter mode and enter the user password 377 as follows NOTE When the unit is in parameter mode each of the fro...

Страница 7: ...ter 63 Battery Maintenance Mode to 1 as follows a The display should read P XX where XX is a parameter number Use the LOAD key or the VOUT key to change the display reading to P 63 b Press CANCEL The...

Страница 8: ...panel s See Figure 2 NOTE On a UT8K also remove the front kick plate found below the front ventilation panel slide it upward then pull it away from the unit 200 2 Remove the battery tray handle from t...

Страница 9: ...connect switch on the external battery cabinet s b Disconnect the external battery cable from the BATT post at top of the fuse board see Figure 3 Insulate the cable lead with electrical tape or heat s...

Страница 10: ...t far enough to expose all of the battery terminals Section 300 Replacing the Batteries 300 1 Replace the old batteries with new ones of the same series and type and rewire in the same order See Figur...

Страница 11: ...a small spark e Replace any tie wraps that were removed 300 8 Remove the handle from the battery drawer and reattach it to the back of the unit 300 9 Replace the bolt that secures the front of the ba...