XI. APPENDIX

- 15 -

A. Serial Network Connection 

     (previously Master/Slave Connection)

NOTE: ONLY AIR CURTAINS FROM THE SAME SERIES CAN BE 

NETWORKED TOGETHER. IF UNITS FROM DIFFERENT SERIES 

ARE NETWORKED OR ARE INCOMPATIBLE, AN ER61 WILL 

DISPLAY EVERY TIME A COMMAND IS ENTERED.

Serial Network Connection Operation

For Serial Network Connection a serial cable connection must 

be made between all Intelliswitch™ controls of each air curtain 

to be linked. Once air curtains are linked all Menu settings 

made through any air curtain display or remote control will 

transfer to all other linked air curtain. Parameter changes made 

on any linked air curtain will update all other boards “live” upon 

menu selections.

1. 

All air curtains equipped with an Intelliswitch and 

the Serial Communication Option have two RJ11 

connectors (telephone plug) located in the wiring 

compartment. Serial cable(s) with the corresponding 

RJ11 socket (telephone jack) on each end are shipped 

separately.

2. 

Once the air curtains are installed, connect all units 

that are to be networked together using the serial 

cable(s) and either of the two RJ11 connectors in 

each wiring compartment. For example, two units 

networked together require one cable and leaves 

an unused connector in each wiring compartment. 

Three units networked together requires two serial 

cables, leaves two units with one connector unused 

in each wiring compartment and one unit with both 

connectors used.

3. 

A wiring diagram is included in the wiring 

compartment of each air curtain and illustrates the 

provision where the serial cable is connected to 

network additional air curtains.

4. 

Once all serial cables are connected and all air curtains 

have power the units can be programmed from any 

handheld remote or air curtain display on the network. 

All program settings are included in the installation 

instructions shipped with the air curtain.

5. 

If the air curtains were purchased with the WiFi option, 

when connected to the local WiFi network they can 

be programmed from a smart phone using the Berner 

app. 

Serial Network Connection - Settings

When units with the Intelliswitch™ are operated in a network 

there are three options available under the Programming Menu 

that manage how they interact with each other.

• 

Door Switch (door)

• 

Thermostat (temp)

• 

Stand By (Stby)

Each option can be set to “ind” or “ALL”.

“ind” = the option only is activated on this unit or independent 

of the other units

“ALL” = the option activates ALL of the units connected on the 

network 

1.   To access the Serial Network Connection hold the left 

arrow for 5 seconds and “Pro” will display

2.  Use the left/right arrows to locate the desired option 

(door/temp/Stby)

3.  When located, use the down arrow to enter into that 

setting.

4.  Use the left/right arrow to change the setting between 

“ind” and “ALL”

EXAMPLE: Stand By function

If set to independent, when STOP is pressed only the unit 

where STOP is pressed will stop. If set to ALL, all of the 

connected units set to ALL will stop.

EXAMPLE: Door Switch function

If set to independent, the door switch connected to a unit will 

only activate that unit. If set to ALL, all of the connected units 

set to ALL will activate.

B. Remote Mounted Display Faceplate

 

for operation of the Intelliswitch™ through a remote mounted 

display faceplate.

NOTE: Maximum mounting distance between the Display 

Faceplate and the unit is 20’. 

 The unit MUST be factory 

ordered with the remote mounted faceplate option. 

When the remote faceplate option is ordered  from the 

factory the air curtain comes equipped with the 

blank faceplate and 20’ ribbon attached. The Display 

Faceplate is shipped loose ready for field installation.  

1. 

Locate the male end of the 14-conductor ribbon 

cable in the wiring tray and run to the remote display 

location. The cable is minimum CL2 rated and should 

not need to be in conduit.  

2. 

Connect the ribbon cable to the 14-pin socket with red 

stripe positioned on the top left when facing the front 

of the display board.  

3. 

Mount remote faceplate to the wall.  

4. 

Reinstall the wiring tray cover. 

C. Infra-red Remote Control

The handheld infra-red remote control buttons, layout and 

operation are the same as that on the Intelliswitch™ air curtain 

display (including multiple button presses) with one exception, 

the Lock Button.

There is no need for multi-button press and hold for lock/un-

lock activation. The Lock Button will lock/unlock display in one 

press. 

The Infra-red Remote Control has a range of 15 feet.

Содержание AED08

Страница 1: ...ELECTRICAL CONNECTIONS 6 VI FIELD CONNECTIONS 7 VII OPERATING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 10 FAQ s FREQUENTLY ASKED QUESTIONS 12 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 9 X T...

Страница 2: ...drilling into wall or ceiling do not damage electrical wiring and other hidden utilities F To reduce the risk of fire do not store or use gasoline or other flammable vapors and liquids in the vicinit...

Страница 3: ...ance from combustible material A I R A I R Electrically Heated Units Only INTERIOR EXTERIOR Architectural Elite 8 Simple to Install Easy to operate maintain NOTE Mount large hole of keyhole slots on t...

Страница 4: ...from 0 to 20 toward the door opening If the air stream strikes any obstruction the top edge of the doorway a door opening device etc the effectiveness of the air curtain will be greatly reduced See Fi...

Страница 5: ...two 2 locking screws at the bottom corners 4 Do not install the perforated intake grill or the louvered discharge grill at this time 5 Proceed to Section V ELECTRICAL CONNECTIONS III WALL MOUNTING IV...

Страница 6: ...by lowering the bottom hinged access cover Remove the two bolts located on the intake side of the unit and the access cover will swing down to rest in the vertical position exposing the wiring compar...

Страница 7: ...trolled by the unit mounted sensor a remote mounted thermostator manually through the Intelliswitch located on bottom access cover of the air curtain Overheating protection is provided by auto reset t...

Страница 8: ...e energizing the unit loosening the nozzle vane locking screws and adjusting vanes VIII MAINTENANCE CLEANING Figure 10 20 AIR Discharge Nozzle A I R INTERIOR EXTERIOR 3 12 Handkerchief A I R 8 CAUTION...

Страница 9: ...uild up from the inside of the access cover air inlet grille blower wheels housings interior of the unit and heating coils if applicable Remove the dirt build up from the blower wheels through the dis...

Страница 10: ...ay air curtain becomes active Stop Time Programmable time of day air curtain stops running T Stat Mode Set only heat or heat fan Set Time Day Programmable clock Locked Unit will run as programmed but...

Страница 11: ...curtain turns off Door opens The air curtain activates Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF 5 Standard Mode of Operation...

Страница 12: ...ice panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device...

Страница 13: ...ain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelliswit...

Страница 14: ...ruction or reposition air curtain move out 3 8 for every 1 up from the door Negative pressure Relieve negative pressure by providing make up air UNEVEN AIR Shaft rotating inside fan Tighten set screws...

Страница 15: ...operated in a network there are three options available under the Programming Menu that manage how they interact with each other Door Switch door Thermostat temp Stand By Stby Each option can be set t...

Страница 16: ...bility for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorizatio...

Отзывы: