Figure 2: Operation Drawing 

7. 

Maintenance and Inspection Test 

 

 

Warning

: Do not turn off the water supply, to make repairs, without notifying local 

security guards. 

7.1 

In any of the following inspections or testing procedures, if an abnormal 
condition exists, see Troubleshooting for possible cause and corrective action. 

7.2 

The Model FP 730UF valve is to be inspected, tested and maintained in 
accordance with the Maintenance Instructions of the plant, this Maintenance 
Manual, as well as the Standard for the Inspection, Testing and Maintenance of 
Water-Based Fire Protection Systems, NFPA 25. 

8. Weekly Inspection 

 

8.1 

The system should be inspected under flow conditions. 

8.2 

Check that the main valve, pilot system, accessories, tubing & fittings, are all in good condition, damage free 
and not leaking. 

8.3 

The fastening nut, of the pilot valve (2 figure 1) adjusting screw, should be fastened tightly. 

8.4 

For circulation type installations, verify that sufficient water flows through the valve when fire pump is operating 
at shut-off pressure (churn) to prevent the pump from overheating. 

8.5 

Verify that the pressure upstream of the relief valve fittings in the fire pump discharge piping does not exceed 
the pressure for which the system components are rated. 

Содержание 730-UF

Страница 1: ...change without notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 730 UF Sizes 2 12 PI7PE09 730 UF Bermad Pressure Re...

Страница 2: ...pump service The double chambered actuator design enables quick and smooth valve action According to the inlet pressure the pilot valve regulates the main valve throttling This valve requires only ex...

Страница 3: ...ischarge check valve It shall be attached in a way that it can be readily removed for repairs without disturbing the piping 4 3 Allow enough room around the valve assembly for any adjustments and futu...

Страница 4: ...contained in this document is subject to change without notice BERMAD shall not be liable for any errors contained herein All Rights Reserved Copyright by BERMAD Control Valves IOM Model FP 730 UF Siz...

Страница 5: ...actory pre set adjusted pressure 5 4 Slowly allow system flow so that system pressure falls below the relief valve adjusted pressure The relief valve should slowly shut to drip tight Readjusting Tools...

Страница 6: ...ned in accordance with the Maintenance Instructions of the plant this Maintenance Manual as well as the Standard for the Inspection Testing and Maintenance of Water Based Fire Protection Systems NFPA...

Страница 7: ...dle valve 21 not properly adjusted Factory set at or 1 open Adjust Valve fails to regulate Air trapped in main valve cover Loosen cover tube fitting at the highest point allow the air to escape and re...

Отзывы: