HEATER LOCATION INSTRUCTIONS

Arrange units so their discharge air streams:
a.

are  subjected  to  a  minimum  of  interference  from  columns,

machinery and partitions;

b.

wipe exposed walls without blowing directly at them;

c.

are directed away from room occupants in comfort heating;

d.

are  directed  along  the  windward  side  when  installed  in  a

building exposed to a prevailing wind.

Locate thermostats approximately 5' (1524mm) above the floor
on interior partition walls of posts, away from cold drafts, internal
heat sources and away from heater discharge air streams.

Small rooms can be heated by one unit heater.

Large rooms require multi-unit installations. Number and capac-
ity of units will be determined by volume of building and square
feet of floor area to be heated. Arrange units to provide perime-
ter air circulation where each unit supports the air stream from
another.

MOUNTING THE HEATER

GENERAL

The heater may be mounted to discharge the heated air either
horizontally or vertically. When the heater is mounted for vertical
discharge,  it  is  recommended  that  the  heater  be  positioned  so
that  the  access  door  will  open  away  from  the  wall  to  provide

greater  access  to  the  wiring  and  control  compartment.  If  the
heater is to be mounted with the access door facing a wall, the
heater must be mounted far enough from that wall to allow full
opening  of  the  access  door  (a  distance  approximately  equal  to
the  width  of  the  heater  ...  check  clearance  before  installing).
Refer to Table 1 for wall and ceiling clearances before mounting
heater. 

The heater may be mounted for either vertical or horizontal dis-
charge by the use of threaded rods. (Refer to Table 2 for thread-
ed  rod  sizes  required.)  Observe  the  detailed  procedures  in  the
following installation instructions.

The  heater  may  also  be  suspended  from  the  wall  or  ceiling  by
means  of  an  optional  mounting  bracket  (type  HUHAAB  or
HCMB) which permits horizontal pivoting of the heater.

After  the  heater  is  installed,  the  louvers  may  be  positioned  to
direct the heated air in the desired direction. When the heater is
installed for horizontal discharge,the louvers should direct the air
either straight ahead or downward. Directing the air upward may
cause  the  heated  air  to  remain  in  the  ceiling  area  and  waste
energy.

DO  NOT MOUNT MERCURY TYPE  THERMOSTAT
DIRECTLY ON  UNIT.  VIBRATION  COULD  CA USE
HEATER TO MALFUNCTION.  

MANUAL

RESET LIMIT

(FACTORY

INSTALLED

OPTION  ONLY.)    THE  LIMIT SWITCH  IS  LOCATED  INTER-
NALLY ON THE REAR OF THE HEATER.  ON THE 3KW
AND 5KW MODELS, THE ACCESS TO THE RESET BUTTON
IS  ON  THE  RIGHT SIDE  (WHEN  FACING  REAR  OF

ALL BUILT-IN THERMOSTATS: IF THE HEATER IS USED TO
PREVENT PIPING OR LIQUIDS FROM FREEZING, AND IF
THE THERMOSTAT IS  SET BELOW  45° F  (7°C), THE  FAN
MUST RUN CONTINUOUSLY. 

CAUTION 

TO  PREVENT POSSIBLE  OVERHEATING  OR  DAMAGE
DUE  TO  OVERHEATING,  KEEP AT LEAST 5'  (1524mm)
CLEARANCE IN FRONT OF HEATER. REFER TO TABLE 1
FOR SIDE, TOP, AND BACK CLEARANCE REQUIREMENTS.

THE HEATER MUST BE MOUNTED AT LEAST 7' (2134mm)
ABOVE  THE  FLOOR  TO  PREVENT ACCIDENTAL CONTACT
WITH THE FAN BLADE WHICH COULD CAUSE INJURY.

CAUTION 

THE  CEILING  MOUNTING  STRUCTURE  AND  THE

ANCHORING  PROVISIONS  MUST BE  OF  SUFFI-

CIENT STRENGTH  TO  SUPPORT THE  COMBINED

WEIGHT OF THE HEATER AND MOUNTING BRACKET.

(SEE TABLE 4).

HEATER);  ON  ALL OTHER  MODELS  IT IS  NEAR  THE
TOP REAR OF THE HEATER.

THE  MANUAL RESET LIMIT IS  IN  SERIES  WITH  THE
AUTOMATIC  RECYCLING  PROTECTOR  (LIMIT).  THE
MANUAL RESET LIMIT WILL NOT RESET UNTIL THE
HEATER HAS COOLED AND THE BUTTON IS PUSHED
IN.

IMPORTANT

!

2

!

!

CAUTION 

!

CAUTION 

!

Содержание HUHAA520

Страница 1: ...n accordance with the National and Local Electrical Codes and the heater must be grounded as a pre caution against possible electric shock 3 Verify the power supply voltage coming to heater matches th...

Страница 2: ...thread ed rod sizes required Observe the detailed procedures in the following installation instructions The heater may also be suspended from the wall or ceiling by means of an optional mounting brack...

Страница 3: ...und wire should be connected before other connections are made 6 The power terminal board is equipped with box terminals sized to accept the correct size power supply wire Wire rated at 600 V and 60 C...

Страница 4: ...any other wiring The element lead wire marked B1 which is factory connected to the power termi nal block terminal located closest to the elements must be moved to terminal B on the three phase termin...

Страница 5: ...D FOR SINGLE PHASE POWER FIELD WIRED FOR THREE PHASE POWER B 3 PHASE BLOCK FACTORY WIRED FOR SINGLE PHASE POWER C1 D1 D1 C1 C D B C D 3 PHASE BLOCK B 3 PHASE BLOCK FIELD WIRED FOR THREE PHASE POWER C1...

Страница 6: ...AA MT 2 HUHAA MT 1 Figure 4 Control Terminal Board for Heaters Without Contactors Mounting Basic Model Height Width Depth Weight No in mm in mm in mm lbs kg Table 4 Specifications HUHAA320 HUHAA324 HU...

Страница 7: ...TERNAL THERMOSTAT MHRT HEAT RECOVERY THERMOSTAT OR REMOTE FAN SWITCH MRFS 2 BLACK RED RED BLACK C R W1 W2 F2 F1 G TR T S S REMOTE SUMMER FAN SWITCH MRFS 1 FAN RELAY FOR MRFS 2 AMD MHRT SUMMER FAN SWIT...

Страница 8: ...ould be returned to the nearest Marley authorized service center or the Marley Engineered Products Service Center and we will repair or replace at our option at no charge to you with return freight pa...

Отзывы: