HORIZONTAL DISCHARGE (Rod-mount from Ceiling)

1.

Install  four  threaded  mounting  rods  in  the  threaded  holes

and secure in place using lock nuts.  (See Table 2).

2.

Securely attach the four mounting rods to the ceiling.  (Refer

to Table  1  for  wall  and  ceiling  clearances,  and Table  2  for
mounting rod spacing).

VERTICAL DISCHARGE (Rod-Mount from Ceiling)

1.

Remove  bolts    from  the  threaded  holes  in  the  back  of  the

heater.

2.

Install  four  threaded  mounting  rods  in  the  threaded  holes

and and secure in place using lock nuts.

3.

Securely attach the four mounting rods to the ceiling.  (Refer

to Table  1  for  wall  and  ceiling  clearances,  and Table  3  for
mounting rod spacing dimensions.)

WIRING

BRANCH CIRCUIT (POWER)

1.

Connect heater only to the voltage, amperage and frequen-

cy specified on the nameplate.

2.

Field wiring must be properly sized to carry the amperage in

accordance with the NEC.

3.

The  access  door  is  hinged.    There  are  either  one  or  two

screws accessible from the bottom, that must be removed
to gain access.  

4.

Aknockout is provided in the back of the heater close to the

power terminal block and the control terminal board. The 
control terminal board knockout is 1/2 inch (12.7 mm) con-
duit  size.    The  power  terminal  block  knockout  is  multiple
diameter.    Use  the  diameter  that  fits  the  required  conduit
size.

5.

Aground  terminal  is  provided  near  the  power  terminal

board.  The ground wire should be connected before other
connections are made.

6.

The  power  terminal  board  is  equipped  with  box  terminals

sized  to  accept  the  correct  size  power  supply  wire.    Wire
rated  at  600  V  and  60° C  is  satisfactory  for  the  heater
branch circuit.  Either aluminum or copper wire is satisfac-
tory for connection to the heater power terminal board box
terminal.  Copper wire is recommended and must be used
with built-in disconnect switch.

Table 2. Rod Thread and Spacing Dimensions, inches (mm)
for Horizontal Discharge

Rod Thread

Unit

Type

A

B

C

D

3 - 5 kW

6

4

1

/

16

3

/

4

6

1

/

16

(152.4)

(103.1)

(19.0)

7.5 - 10 kW

(153.9)

15 - 20 kW

5

/

16

- 18

11

3

/

8

8

7

/

8

5

1

/

8

3

/

4

(289.0)

(225.6)

(130.3)

(19.0)

25 - 30 kW

10

9

/

16

14 

1

/

2

6

3

/

16

5

/

8

(268.2)

(368.3)

(157.2)

(16.0)

40 - 50 kW

3

/

8

- 16

15

15

/

16

14 

1

/

2

6

3

/

16

5

/

8

(404.9)

(368.3)

(157.2)

(16.0)

Figure 2. Vertical Discharge Mounting and Rod Spacing

Table 3. Rod Thread Type and Spacing Dimensions, inches
(mm) for Vertical Discharge

Rod Thread

Unit

Type

E

F

G

H

3 - 5 kW

6

9

3

/

4

2

4

1

/

16

5

/

16

- 18

(152.4)

247.7)

(50.8)

(103.1)

7.5 - 20 kW

8

7

/

8

14

5

/

8

2

5

1

/

8

(225.6)

(371.6)

(50.8)

(130.3)

25 - 30 kW

3

/

8

- 16

14

1

/

2

21

1

/

4

2

3

/

16

6

3

/

16

(308.1)

(539.8)

(55.6)

(157.2)

3

Unit

Discharge

Ceiling

Side Wall

Back Wall

3 & 5 kW

Horiz.

2 (50.8)

6 (152.4)

9 (228.6)

Vert.

6 (152.4)

18 (457.2)

18 (457.2)

7.5 to 10 kW

Horiz.

6 (152.4)

6 (152.4)

13 (330.2)

Vert.

6 (152.4)

24 (609.6)

24 (609.6)

15 to 10 kW

Horiz.

6 (152.4)

9 (228.6)

12

1

/

2

(317.5)

Vert

6 (152.4)

24 (609.6)

24 (609.6)

25 to 50 kW

Horiz.

16 (406.4)

12 (304.8)

18

1

/

2

(470.0)

Vert.

12 (304.8)

36 (914.4)

36 (914.4)

Table 1. Wall and Ceiling Clearance, inches (mm)

Figure 1. Horizontal Discharge Mounting and Spacing.

Содержание HUHAA520

Страница 1: ...n accordance with the National and Local Electrical Codes and the heater must be grounded as a pre caution against possible electric shock 3 Verify the power supply voltage coming to heater matches th...

Страница 2: ...thread ed rod sizes required Observe the detailed procedures in the following installation instructions The heater may also be suspended from the wall or ceiling by means of an optional mounting brack...

Страница 3: ...und wire should be connected before other connections are made 6 The power terminal board is equipped with box terminals sized to accept the correct size power supply wire Wire rated at 600 V and 60 C...

Страница 4: ...any other wiring The element lead wire marked B1 which is factory connected to the power termi nal block terminal located closest to the elements must be moved to terminal B on the three phase termin...

Страница 5: ...D FOR SINGLE PHASE POWER FIELD WIRED FOR THREE PHASE POWER B 3 PHASE BLOCK FACTORY WIRED FOR SINGLE PHASE POWER C1 D1 D1 C1 C D B C D 3 PHASE BLOCK B 3 PHASE BLOCK FIELD WIRED FOR THREE PHASE POWER C1...

Страница 6: ...AA MT 2 HUHAA MT 1 Figure 4 Control Terminal Board for Heaters Without Contactors Mounting Basic Model Height Width Depth Weight No in mm in mm in mm lbs kg Table 4 Specifications HUHAA320 HUHAA324 HU...

Страница 7: ...TERNAL THERMOSTAT MHRT HEAT RECOVERY THERMOSTAT OR REMOTE FAN SWITCH MRFS 2 BLACK RED RED BLACK C R W1 W2 F2 F1 G TR T S S REMOTE SUMMER FAN SWITCH MRFS 1 FAN RELAY FOR MRFS 2 AMD MHRT SUMMER FAN SWIT...

Страница 8: ...ould be returned to the nearest Marley authorized service center or the Marley Engineered Products Service Center and we will repair or replace at our option at no charge to you with return freight pa...

Отзывы: