Push button comfort 1- 4gang, Flush-
mounted (Up)
751616xx, 751626xx, 751646xx
Technical
Documentation
© Gebr.Berker 2004
Act. version: 10.08.2004
Page: 17 / 23
(subject to prior change)
7516y6xx.doc
Part 2
Time between switching and
dimming
base
(FA)
130 ms
260 ms
520 ms
1 s
Time after which the long push-button-press
function (dimming) is executed.
Time = base
•
factor
Time between switching and
dimming
factor (2…127)
(FA)
2...127;
3
Time after which the long push-button-press
function (dimming) is executed.
Default: 130 ms
•
3 = 390 ms
Dimmming brighter by
(FA)
100 %
50 %
25 %
12.5 %
6 %
3 %
1.5 %
With a dimming telegram, the brightness can
be increased by x % max.
Dimming darker by
(FA)
100 %
50 %
25 %
12.5 %
6 %
3 %
1.5 %
With a dimming telegram, the brightness can
be reduced by x % max.
Telegram repetition
(FA)
YES
NO
Cyclical telegram repetition during push-
button-press.
Time between two telegrams
(FA)
200 ms
300 ms
400 ms
500 ms
750 ms
1 s
1.5 s
2 s
Time between two telegrams when telegram
repetition is active.
A new dimming telegram is triggered after
this period.
Send stop telegram ?
(FA)
YES
NO
On release of the push-button a stop
telegram is transmitted or not.
Push-button 1: "Blind/shutter control function" parameterized
Function of push button
UP
default: push-buttons 1, 3, 5, 7
DOWN
default: push-buttons 2, 4, 6, 8
TOGGLE
A short push-button-press triggers a STEP
telegram (UP), a long push-button-press
triggers a MOVE telegram (UP).
A short push-button-press triggers a STEP
telegram (DOWN), a long push-button-press
triggers a MOVE telegram (DOWN).
With this setting, the internally stored moving
direction is followed up viathe bus and
switched over after each long-time operation
(MOVE). If a STEP telegram is transmitted by
a short push-button-press, this STEP
command always has the opposite direction
of the last MOVE command. Several
successive STEP telegrams always have the
same direction.
Time between step and move
operation
base
(FA)
8 ms
130 ms
2.1 s
33s
Time after which the long push-button-press
function is executed (T1 see diagram below).
Time = base
•⋅
factor
Time between step and move
operation
factor
(FA)
0 ... 255;
46
Time after which the long push-button-press
function is executed (T1 see diagram below).
Default: 8 ms
•
46 = 368 ms