USER HANDBOOK 1.2 | ECC DIO / ECC AIO
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
250000600_ECC-DIO-AIO_Anwenderhandbuch_EN.docx
21
9
I 9
+24 V DC
0 V DC
0 V DC
+24 V DC
10
I 10
+24 V DC
0 V DC
0 V DC
+24 V DC
11
I 11
+24 V DC
0 V DC
0 V DC
+24 V DC
12
I 12
+24 V DC
0 V DC
0 V DC
+24 V DC
13
I 13
+24 V DC
0 V DC
0 V DC
+24 V DC
14
I 14
+24 V DC
0 V DC
0 V DC
+24 V DC
15
I 15
+24 V DC
0 V DC
0 V DC
+24 V DC
16
I 16
+24 V DC
0 V DC
0 V DC
+24 V DC
Data from the digital inputs
Feature
Value
Description
Type of inputs
Type 1
Positive (to IEC 61131-2)
or negative switching
Cable length
max. 30 m
For unshielded connection cables
Cables over 30 m in length must be shielded.
Cable cross-section
within the control
cabinet
0.14 – 1.5 mm²
(26-16 AWG)
Aim for plug connector limits to UL specifications.
Field wiring
according to regulations
and standards
Comply with all local regulations and the
stipulations of DIN EN 61131-2.
Rated load voltage
24 V DC (SELV)
–
Delay time
1 ms
Applies for transitions from 0 to 1 and 1 to 0
Signal evaluation
cyclical
Dependent on the cycle time set in the
programming system
Protection against
reverse polarity
yes
–
Potential isolation
no
–
Status display
yes
One orange LED per input
Lights at logical 1