Extension Modules
BERGHOF Automation
70 DC1000_HB_en_2D0982003ZD00.doc
2VF100124FE01.doc
5.1.6. Digital
Input/Output Pin Assignments
Configured as
Connection
Signal
name
Digital I/O
TPU- I/O
Note
X12
9
L1+
Feed
X12
X9
X7
X6
X1
X2
1..8
9
1..9
1..9
9
9
M1
GND for module and I/O feed
X4
X5
1..9
1..9
+24V=
I/O feed
Across L1+
1
IN1
Digital IN +24V
Counter input, +24V
2
IN2
Digital IN +24V
Counter input, +24V
Form encoder 1
3
IN3
Digital IN +24V
Counter input, +24V
4
IN4
Digital IN +24V
Counter input, +24V
Form encoder 2
5
IN5
Digital IN +24V
6
IN6
Digital IN +24V
7
IN7
Digital IN +24V
X1
8
IN8
Digital IN +24V
1
IN9
Digital IN +24V
2
IN10
Digital IN +24V
3
IN11
Digital IN +24V
4
IN12
Digital IN +24V
5
I/O13
Digital I/O +24V
6
I/O14
Digital I/O +24V
7
I/O15
Digital I/O +24V
X2
8
I/O16
Digital I/O +24V
1
OUT1
Digital OUT +24V
2
OUT2
Digital OUT +24V
3
OUT3
Digital OUT +24V
4
OUT4
Digital OUT +24V
5
OUT5
Digital OUT +24V
6
OUT6
Digital OUT +24V
7
OUT7
Digital OUT +24V
X9
8
OUT8
Digital OUT +24V
Encoder interface
Groups of 2 inputs can be combined to form a quadrature encoder for evaluation.
Function
Input 1
Input 2
Encoder 1
IN 1 (X1)
IN 2 (X1)
Encoder 2
IN 3 (X1)
IN 4 (X1)
The encoder values are only reset (0) when the unit is switched on or rebooted af-
ter a reset.
Содержание DC1005
Страница 4: ...DIALOG CONTROLLER BERGHOF Automation 4 DC1000_HB_en_2D0982003ZD00 doc This page intentionally blank ...
Страница 8: ...DIALOG CONTROLLER BERGHOF Automation 8 DC1000_HB_en_2D0982003ZD00 doc This page intentionally blank ...
Страница 86: ...Annex BERGHOF Automation 86 DC1000_HB_en_2D0982003ZD00 doc 2VF100055FE02 doc 7 4 Nameplate 2VF100080DG01 cdr ...