9. Trouble-Shooting Problems
The following guide can be used to pinpoint the cause of operational problems with the BWC XL.1 wind
turbine and the PowerCenter controller. For problems or symptoms not found in the following listing,
please contact the Service Department at Bergey Windpower Co. at:
Tel: 405-364-4212
Fax: 405 364-2078
e-mail:
PROBLEM CAUSE(S) DIAGNOSIS REMEDY
Battery voltage gets
too high.
PowerCenter regulating
voltage set too high or
no dump load being
used.
Excessive battery gas-
sing. Use voltmeter to
check battery cell volt-
ages or hydrometer to
check the specific grav-
ity – compare to battery
manufacturers recom-
mendations.
Contact the BWC Ser-
vice Department for the
voltage regulation set-
point adjustment proce-
dure.
Batteries do not reach
full state of charge.
PowerCenter regulating
voltage set too low.
Use hydrometer to
check the specific grav-
ity of the battery cells.
Compare with battery
manufacturer’s recom-
mendation.
Contact the BWC Ser-
vice Department for the
voltage regulation set-
point adjustment proce-
dure.
Loads are too large.
Remove largest load. If
battery bank reaches
higher state of charge,
then the system is over-
loaded.
Consult with BWC about
possible remedies.
Rotor turns, but the
system doesn’t charge
the batteries.
Open circuit breaker.
Check circuit breaker on
the side of the Power-
Center.
Switch to “On”
Blow output fuse.
No lights on PowerCen-
ter.
Replace 90A battery
fuse on PowerCenter
circuit board.
Power transistor failure.
Turbine voltage is
above 10 VDC and Tur-
bine light is on, but no
current is being deliv-
ered.
Return complete Pow-
erCenter to BWC for
repair.
Turbine rectifier failure.
Check voltage from the
turbine.
Replace rectifier as-
sembly.