Tighten the 3 corrugated pipe 
hoses with the gaskets on the 
module. 

6.3.

 

Hydraulic connection 

The pipelines are connected in accordance with the installation layout of this 
manual. See 1.2. Sample application: 
 

 

The path of the lines to the tank should be as short as possible! 

 

We recommend steel or copper pipes as the material for the lines. The 
installation sequence must be followed for all pipelines and fittings in order 
to prevent electrochemical corrosion. 

 

Installation in gravitational heating systems is not permissible! 

 

The expansion tank of the collector circuit must be connected directly. 

 

The installation of shut-off valves (except suitable maintenance units such as 
cap valves) is not permitted! 

 

Connections must be tightened only after the pipelines have been sealed. 
Tightening torques or impact of forces on components and connections that 
have already been pre-mounted must be avoided at all costs! 

 

 

In addition, all flat seal connections must be checked for the right tightening 
torque of the union nuts (screw connections may become loose during 
transport!). 

 

6.4.

 

Electrical connection 

The electrical components of the plant have been wired internally at the factory. 
Connection to the mains supply (230 V/AC, 50 Hz) takes place using the power 
supply line already connected to the terminals. 
The buffer sensors supplied with the appliance are placed at the appropriate 
measuring points of the buffer tank and connected to the corresponding 
terminals of the controller in the same manner as the collector sensor included in 
the scope of delivery. The controller manual contains comprehensive information 
on the controller integrated in the module. 
 
Work on live parts of the module is carried out only after following the respective 
regulations of the electricity supply company and the relevant standards 
applicable. 
 

Содержание Solar module 50

Страница 1: ...Solar Module 50 Operating Manual...

Страница 2: ...4 4 Structure of the solar module 4 5 Safety instructions 5 6 Assembly and commissioning 6 6 1 Assembly 6 6 2 Positioning the solar module 6 6 3 Hydraulic connection 10 6 4 Electrical connection 10 6...

Страница 3: ...ase note the warnings given in champter 3 Improper handling or operation may lead to damage of the system 1 1 Use The solar module 50 enables the buffer tank to be loaded depending on the temperature...

Страница 4: ...technical personnel should carry out the assembly maintenance and cleaning of the shift layer module Unauthorised modifications or changes are not permitted on the system for safety reasons and inevi...

Страница 5: ...7 NORM M7700 Solar heating and solar thermal plants Solar energy Terms with definitions DIN 18380 NORM M7701 Central heating systems and process water systems Solar plants Approximation procedure for...

Страница 6: ...he erection and installation must be done by an approved technical agency This agency also takes over the responsibility for correct installation and commissioning A dry frost free room that provides...

Страница 7: ...1 As given in the Drilling jig enclosed drill the boreholes marked with the 10 mm dia drill bit at least 8 cm deep 2 Next insert the dowels into the borehole and screw in the hanger bolts into the br...

Страница 8: ...8 Drilling jig for wall mounting...

Страница 9: ...material in 3 steps as follows Step 1 Figure above Step 2 Figure above Mount and tighten the 3 threaded rods and the 3 corrugated pipe hoses including the gaskets at the relevant connecting points on...

Страница 10: ...orces on components and connections that have already been pre mounted must be avoided at all costs In addition all flat seal connections must be checked for the right tightening torque of the union n...

Страница 11: ...ly de aerated Flow noises during operation of the buffer loading pump indicate that there is still some air in the plant which needs to be discharged via the pump and the manual bleeding or venting de...

Страница 12: ...the direction opposite to the flow 12 You can now switch the pump off and remove the connections of the filling pump from the KFE valves A and B 13 The solar circuit is now filled up completely and r...

Страница 13: ...al thread E Buffer inflow hot ball valve G1 external thread F Solar inflow G1 external thread G Solar return flow G1 external thread H Connection to the expansion tank G3 4 external thread Maximum ope...

Страница 14: ...14 7 1 Design...

Страница 15: ...15 7 2 Pump characteristics...

Страница 16: ...s a warranty of 2 years from the date of delivery for the products and components supplied Unauthorised modifications or changes are not permitted on the system for safety reasons and inevitably lead...

Страница 17: ...17 Notes...

Страница 18: ...18 Notes...

Страница 19: ...19...

Страница 20: ...Rev 1 05 12...

Отзывы: