The burner is on when:

Manifold temperature <=Setpoint – ignition hysteresis.

Ignition hysteresis can be set, CH_Low_hyst_on = Par. 26, 

preset to 5°C, can be set between 0 and 20°C.

The Master control unit converts the heat demand into 

power demand for each slave control unit.

The burners are off when:

Manifold temperature >=Se shut-off hysteresis .

Shut-off hysteresis can be set (CH_Low_Hyst_off=Par. 27, 

preset to 3, can be set between 0 and 20°C).

With the low temperature circuit attenuation parameter, Par. 

25≠0, the low temperature thermostat contact is ignored 

and a heat demand is present for the low temperature 

circuit when:

Manifold temperature <=Setpoint – ignition hysteresis

The heat demand stops when:

Manifold temperature >=Se shut-off hysteresis .

The setpoint in this case coincides with the value set for 

parameter 3 (Setpoint_t_ch_low) if the low temperature 

thermostat contact is closed, whereas it is calculated as the 

value set for parameter 3 less the attenuation (Setpoint_t_

ch_low-Attenuation_low) if the contact is open.

OPERATION WITH CLIMATIC CONTROL, PAR. 22=1

If the low temperature circuit attenuation is equal to 0 , 

Attenuation_low=Par. 25=0, its behaviour is the same as 

the previous paragraph, with the exception that the setpoint 

is calculated based on the outdoor temperature.

If the outdoor temperature = Tout_min=Par. 37, preset to 

0°C, then setpoint =setpoint_T_Ch_low.

If the outdoor temperature = Tout_max=Par. 38, preset 

to 18°C, then setpoint T_ch_high_ foot=Par. 24, preset to 

50°C.

The setpoint is calculated linearly between the 2 outdoor 

temperature values.

Preset to 0.

3

 T_out_correct

 

Outdoor temperature correction (parameter 39)

Normally, the displayed value is the value read by the 

microcontroller plus or minus a correction value (T_

visualizzata = T read by the /- correction).

The read value of the outdoor temperature can be corrected 

by varying the value of parameter 39, (the permitted limit 

for the correction is +/- 30 °C). In this phase, it is suggested 

to use a reference thermometer.

Preset to 0.

4

  Summer Mode

 

Summer function (parameter 38.)

The Summer Mode function is used to deactivate requests 

received by the High Temperature and Low Temperature 

circuits and from the zones when the outside temperature, 

T outside, is equal to or above the value set in parameter 

38.

The Parameter 38. can be set with values between 0 and 

30 [°C].

Preset to 0 (summer function disabled).

5

 T4_frost_protection

 

Antifreeze protection (parameter 35)

The electronic control unit has active antifreeze protection 

also in stand-by mode. The antifreeze protection has two 

levels, the first that activates the pump and the second that 

activates the pump and the burner.

If the manifold temperature ≤ 5°C, the high temperature 

circuit pump and the system pump (third pump) are active

or, with CH_type=1 and outdoor sensor connected,

if the outdoor temperature ≤ 3°C (par. 35) the high 

temperature pump and the system pump (third pump) are 

active

If after 10’ the manifold temperature ≤ 5°C

a burner is on at maximum until the manifold temperature 

≥ 20°C.

If after 10’ the manifold temperature ≥ 5°C but, with CH_

type=1 (Par. 14 or 22) and outdoor sensor connected, the 

outdoor temperature ≤ 3°C (par. 35) the pump continues to 

operate until the outdoor temperature ≥ 3°C. Parameter 35 

can be set between -30°C and 15°C.

Preset to 3.

6

 Power_control_mode

 

Cascading management (parameter 33)

To manage the power delivered by the system, two 

cascading strategies are possible. In both cases, the 

Master control unit can only add a new burner when 

another is on.

If the Master control unit must increase the number of 

ignited burners, first check that the next burner can be 

ignited: no errors present and modular system temperature 

below the maximum. Otherwise, check another burner. If 

no burner is ready for ignition, the master will decrease the 

number of burners to ignite.

Содержание Power Plus Box 1001 EXT

Страница 1: ...Installation Manual CONDENSING Power Plus Box 1001 INT EXT Installation Manual EN...

Страница 2: ...1 4 9 Condensate outlet 11 4 10 Water circuit 12 4 11 Exhaust flue 12 5 INSTALLATION DIAGRAMS 12 6 ELECTRICAL SYSTEM 14 6 1 Power supply 14 6 2 Electrical connections 14 6 2 1 Connection to mains 14 6...

Страница 3: ...r their part to be kept marking the beginning of the period of guarantee at the terms and conditions specified on the relative slip The appliance in its original packing may be exposed to temperatures...

Страница 4: ...iate disposal likewise making it possible to recuperate the materials it is made of with substantial savings in energy and resources 3 TECHNICAL FEATURES 3 1 Main features Power Plus Box 1001 is a mod...

Страница 5: ...tion system includes automatic resetting safety thermostat differential water pressure switch acting as a flowmeter temperature probe on flow and return controlled by a certified electronic device to...

Страница 6: ...Vent valve 7 Safety thermostat 8 Min and differential pressure 9 Flow temperature control 10 Return temperature control 11 Flue temperature control 12 Return pipe 13 Flow pipe 14 Gas pipe 15 Air inlet...

Страница 7: ...ure 4 1 Flow low temperature 2 Return low temperature 3 Flow high temperature 4 Return high temperature 5 Return high temperature 6 Return hot water 7 Flow low temperature 8 Return low temperature 9 R...

Страница 8: ...rner 20 Fan 21 Venturi tubes 22 Air inlet pipe 23 Gas valve 24 Exhaust flue duct 25 Condensate drainpipe 26 Vent valve 27 Ignition detection electrode 28 Safety thermostat 29 Gas cock 30 Diff Pressure...

Страница 9: ...uct name Serial number Product identification code CE certification number Gas type and pressures from mains Power type from mains Rated heat capacity Qn Rated working power Pn Efficiency according to...

Страница 10: ...tructions b b An automatic filling system may not be used for topping up which must be done manually and recorded in the unit handbook b b If there are more than one boiler they must all be put into s...

Страница 11: ...lation When positioning the appliance in the heating system account for the fact that water gas and condensate drainage connections must be made on the right hand side of the cupboard adequate room mu...

Страница 12: ...l exceeds 35 kW and can therefore only be installed in premises with air vents opening towards the outside and made in conformity to provisions of the law in force Ministerial Decree D M 12 04 1996 a...

Страница 13: ...ow temperature system users 4 Remote controlled water tank 5 Check valve 6 Pressure reducer 7 Filter 8 Expansion tank EAF Water from mains A High temperature kit B Low temperature kit C Water tank kit...

Страница 14: ...people without experience to use the appliance and switch off the heating unit if the power cable should break call in qualified personnel to replace it Always refer to the data given in the diagrams...

Страница 15: ...ful to fix the latter to its cable guide For example by connecting the low temperature circulator to a timer and or external room thermostat the electrical installation will be the one shown in Figure...

Страница 16: ...7 37079 12 16563 31 8016 50 4161 69 2296 88 1336 107 815 6 35463 13 15912 32 7731 51 4026 70 2229 89 1300 108 796 5 33925 14 15289 33 7458 52 3897 71 2164 90 1266 109 776 4 32461 15 14694 34 7196 53...

Страница 17: ...a Master board malfunction The master board can in fact be excluded so as to enable the system to work with a flow temperature preset in default by the manufacturer guaranteeing the heating unit with...

Страница 18: ...nr 15 All the fans in the system will work at the set speed this will be displayed on the first digit to the left H maximum speed The other 2 digits will show the flow temperature e g T1 80 C Adjust...

Страница 19: ...buttons pressed together Furthermore each button has a specific function depending on the selected user mode Figure 21 BUTTON KEY DESCRIPTION S1 Reset button Serves to release the electric board after...

Страница 20: ...and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by pressing...

Страница 21: ...he desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc for 10 secs...

Страница 22: ...d change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s the second...

Страница 23: ...dentifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with the first e...

Страница 24: ...stop flashing after 3 sec and will be operative A detailed description of all the parameters and the factory preset values can be found in the Parameter list chapter 9 1 Setting the heating parameter...

Страница 25: ...imatic curve on every circuit 3 CH_Priority Heating priority parameter 16 If set to 0 the system will work without heating priority with the high temperature and low temperature circuits served in par...

Страница 26: ...H_High_Hyst_off Par 20 preset to 3 can be set between 0 and 20 C With the high temperature circuit attenuation parameter Par 21 0 the high temperature thermostat contact is ignored and a heat demand i...

Страница 27: ...lue of the outdoor temperature can be corrected by varying the value of parameter 39 the permitted limit for the correction is 30 C In this phase it is suggested to use a reference thermometer Preset...

Страница 28: ...rt up and shut off function If the manifold temperature Setpoint 70 C the burners are ignited at time intervals equal to 2s If the manifold temperature Setpoint 4 C the burners are shut off at time in...

Страница 29: ...o T_Ch_high_foot Par 18 T_Ch_low_foot Par 24 9V to a setpoint equal to SetPoint_Ch_high Par 1 SetPoint_Ch_low Par 3 The setpoint is calculated linearly between 2V and 9V Hysteresis for the end of dema...

Страница 30: ...ed no 48 and the fan operates for 10 minutes at maximum The Slave card is able to protect the primary exchanger from the hazards of low water circulation both using a flow switch as well as checking t...

Страница 31: ...n 5 rapid exchanger with flowmeter 6 water tank with thermostat 7 h w max poten 230 1 255 Setpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Pri...

Страница 32: ...and by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 1 0 1 Third pump setpoint 0 Main pump of system loop 1 L...

Страница 33: ...3 Slaves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E34 4...

Страница 34: ...s pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min replace the Slave card E35 35 Water differential pressure switch error contact ope...

Страница 35: ...35 12 WIRING DIAGRAMS...

Страница 36: ...36...

Страница 37: ...sate production per hour 100 50 30 C with G20 gas 17 2 kg h Efficiency at rated power 80 60 C 98 6 Efficiency at rated power 50 30 C 108 6 Efficiency at rated power Tm 50 C 60 40 C 104 2 Efficiency at...

Страница 38: ...w temperature rating P1 41 8 kW EFFICIENCY at rated thermal input and at high temperature rating 4 88 7 at 30 of rated thermal input and at low temperature rating 1 98 1 ADDITIONAL ENERGY CONSUMPTION...

Страница 39: ...39...

Страница 40: ...oilers com Beretta reserves the right to modify the characteristics and specifications given in this publication at any time and without prior notice as part of its policy of continuous product improv...

Отзывы: